Termix VVX-I-R FI - 7 Series DS fully insulated
Operating Guide - Components
Heating controls
Temperature setting
Relation between scale numbers 1-5 and closing temperature.
(the values given are approximate)
1 = 30 °C
2 = 40 °C
3 = 52 °C
4 = 64 °C
5 = 76 °C
Thermostatic control
The flow temperature in the space heating circuit is controlled using
the temperature regulation of the heat interface unit, depending
on model and type.
The temperature of the HE flow line is adjusted as follows:
To increase the temperature, turn the handle on the thermostatic
controller to select a higher number.
To decrease the temperature, turn the handle on the thermostatic
controller to select a lower number.
RAVK controller (35-75 °C)
07
see diagram
Activating the thermoactuators
The thermoactuators are supplied with a “first open” function, which
means that they are slightly open for frost protection until the electrical
controller is installed. During commissioning, the “first open”function
is disabled by removing the red mounting split on the thermoactuator.
Please check that the thermoactuators can fully close following
disabling of the “first open” function.
See the installation guide included with the thermoactuator.
Thermoactuators
69
see diagram
Removing the RAVK sensor
1. Setting
Before removing the RAVK sensor from the valve turn to setting 5.
2. Loosen screw
Loosen the screw as much as you can still keeping it in place.
3. Remove
Remove the RAVK sensor.
Setting 5
Screw