FRCC.EI.003.A6.02 © Danfoss Commercial Compressors 01/14

sh 240 - 295 - 300 - 380 - 485 
sy 240 - 300 - 380 
sz 240 - 300 - 380

These Danfoss compressors

 

motors are protected by an external module 

protecting against phase loss/reversal, over heating and high current 

draw. 

A1

A3

A2

MPM

S

KS

LPS

CC

Legend:

Fuses ..........................................................................................F1

Compressor contactor .........................................................KM

Control relay ...........................................................................KA

Safety lock out relay .............................................................. KS

Optional short cycle timer (3 min)  ............................... 180 s

External overload protection ...............................................F2

Pump-down pressure switch ...............................................LP

High pressure safety switch.................................................HP

Control device .........................................................................TH

Liquid Line Solenoid valve ............................................... LLSV

Discharge gas thermostat ................................................DGT

Fused disconnect ...................................................................Q1

Motor safety thermostat ................................................... thM

Compressor motor ................................................................. M

Motor Protection Module ............................................... MPM

Thermistor chain.......................................................................S

Safety pressure switch ........................................................ LPS

Control circuit  ........................................................................CC

All Wiring diagrams are with pump-down cycle

Instructions

1 – Introduction

These instructions pertain to the Danfoss SM, 
SY, SZ, SH & WSH scroll compressors used for air-
conditioning systems. They provide necessary 
information regarding safety and proper usage 
of this product.

2 – Handling and storage

 •  Handle the compressor with care. Use the 

dedicated handles in the packaging. Use the 
compressor lifting lug and use appropriate 
and safe lifting equipment.

 •  Store and transport the compressor in an 

upright position.

  •   Store the compressor between -35°C and 50°C.
 •   Don’t expose the compressor and the packa-

ging to rain or corrosive atmosphere.

3 – Safety measures before assembly

 Never use the compressor in a flammable 

atmosphere.

 •  The compressor ambient temperature may 

not exceed 50°C during off-cycle.

 •  Mount the compressor on a horizontal flat 

surface with less than 3° slope.

 •   Verify that the power supply corresponds to 

the compressor motor characteristics (see  
nameplate).

 •   When installing SZ or SH or WSH, use equip-

ment specifically reserved for HFC refrige-
rants which was never used for CFC or HCFC 
refrigerants.

 •   Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

  •   Use clean and dehydrated system components.
 •  The piping connected to the compressor must 

be flexible in 3 dimensions to dampen vibrations.

4 – Assembly

  •   In parallel assemblies of SH, WSH, SM112 - 124 

- SM/SZ147 the compressor requires a rigid 
mounting on the rails. Use the rigid spacers 
from the tandem mounting kit or the rigid spa-
cers delivered with dedicated tandem com-
pressors.

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Remove the gaskets when brazing rotolock 

connectors.

  •   Always use new gaskets for assembly.
 •  Connect the compressor to the system as 

soon as possible to avoid oil contamination 
from ambient moisture.

  •   Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 
cannot be removed.

  •   Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 
remove the internal valve.

 •  

Do not exceed the maximum tightening 
torque for rotolock connections: 

Rotolock connections Tightening torque

1” rotolock

80 Nm

1 1/4 “ rotolock

90 Nm

1 3/4” rotolock

110 Nm

2 1/4” rotolock

130 Nm.

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

 •   SM 084 to 185, SY 380, SZ 084 to 185, SZ 380, SH 

090 to 184, WSH 090 to 184:  Pressurize the system 
on HP side first and then on LP side. Never let the 

pressure on LP side exceed the pressure on HP 
side with more than 5 bar. Such pressure diffe-
rence could cause internal compressor damage.

  •   Do not use dye for leak detection.
  •   Perform a leak detection test on the complete 

system.

  •   The test pressure must not exceed : 

Models

LP side

HP side

SY / SZ 240 - 380 

20 bar

32 bar 

SM / SZ 84 - 185 

25 bar

32 bar

SH 180 - 485

30 bar 

45 bar 

SH / WSH 090 - 184  33 bar

45 bar

 
  •   When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the 

system.

  •   Connect a vacuum pump to both the LP & HP 

sides.

  •   Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

  •   Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 
this may cause internal damage.

7 – Electrical connections

  •   Switch off and isolate the main power supply. 

See overleaf for wiring details.

 •   All electrical components must be selected as per 

local standards and compressor requirements.

  •   Refer to page  2 for electrical connections details.
 •  The Danfoss scroll compressor only works 

correctly in one rotation direction. Line 
phases L1, L2, L3 must absolutely be connec-
ted to compressor terminals T1, T2, T3 to 
avoid reverse rotation.

 •   Use ø 4.8 mm (3/16”) screws and ¼” ring ter-

Содержание SM Serires

Страница 1: ...ish http instructions cc danfoss com Svenska Swedish Portugu s Portuguese Nederlands Dutch Gaeilge Irish Suomi Finnish Lietuviu kalba Lithuanian Latviesu valoda Latvian Eesti Estonian Elinika Greek Po...

Страница 2: ......

Страница 3: ...Instructions Sm Sy sz sh WSH Compressors Installation and servicing of the compressor by qualified personnel only Follow these instructions and sound refrigeration engineering practice relating to in...

Страница 4: ...g the cir cuit against over current CC F1 F1 KA KA KA HP LPS T1 T2 T3 KM DGT KS KS 1 2 M ThM KS KS KA KM KM LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185 versions with thermostat SZ 1...

Страница 5: ...rails Use the rigid spacers from the tandem mounting kit or the rigid spa cers delivered with dedicated tandem com pressors Slowly release the nitrogen holding charge through the schrader port Remove...

Страница 6: ...may take up to several hours If the internal pressure relief valve is opened SY SZ 240 300 380 and SH 380 SH 485 the compressor sump will be warm and the com pressor will trip out on the motor protect...

Страница 7: ...uctions Compresseurs Sm Sy sz sh WSH Toute op ration de montage et d entretien du compresseur doit exclusivement tre effectu e par un personnel qualifi Le montage la mise en service la maintenance et...

Страница 8: ...SV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185 versions avec thermostat SZ 115 125 160 175 185 Ces compresseurs Danfoss sont fournis avec un thermostat unipolaire bilame situ danslesenro...

Страница 9: ...d di s R duire progressivement la pression d azote interne via le raccord Schrader Retirer les joints pour braser les raccords Ro tolock Utiliser syst matiquement des joints neufs pour l assemblage R...

Страница 10: ...arm Cela peut n cessiter plusieurs heures en fonction de la temp rature ambiante Si le d tendeur de pression interne est ouvert SY SZ 240 300 380 et SH 380 SH 485 le carter du compresseur sera chaud...

Страница 11: ...C D A B A D B E C F 5 30 T C C T0 C R407C R404A R507A R22 R417A T C C T0 C 5 R134a T C C T0 C SZ 240 300 380 T C C T0 C SZ 240 300 380 R410A SH SM SY T C C T0 C SZ 084 185 T C C T0 C SZ 084 185 t c c...

Страница 12: ...10 120 147 148 161 SH WSH 140 3 161 3 184 SH140 3 161 3 184 WSH140 3 161 3 184 Danfoss CC F1 F1 KA KA KA HP LPS T1 T2 T3 KM DGT KS KS 1 2 M ThM KS KS KA KM KM LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP S...

Страница 13: ...ss SM SY SZ SH WSH 2 35 C 50 C 3 50 C 3 SZ SH WSH HFC CFC HCFC 4 SH WSH SM112 SM124 SM147 SZ147 1 80 Nm 1 1 4 90 Nm 1 3 4 110 Nm 2 1 4 130 Nm 5 SM 084 185 SY 380 SZ 084 185 SZ 380 SH 090 184 WSH 090 1...

Страница 14: ...0 161 184 7 9 SH 180 240 295 300 13 5 SH 380 14 5 SH 485 17 9 SM SY SZ 0 5 bar g SH WSH 1 5 bar g 12 6 10 Danfoss SH WSH 090 184 SM 112 124 147 SZ147 SM SZ 084 090 100 110 112 120 124 147 148 161 SH W...

Страница 15: ...C EI 003 A6 06 Danfoss Commercial Compressors 01 14 15 Istruzioni Compressori SM SY SZ SH WSH Seguire queste istruzioni e le corrette procedure relative a installazione messa in servizio manutenzione...

Страница 16: ...hM KS KS KA KM KM LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185 versioni con termostato SZ 115 125 160 175 185 I compressori Danfoss sono dotati di termostato bimetallico monopolare a...

Страница 17: ...alla valvola Schrader Rimuovere le guarnizioni prima della brasa tura dei raccordi rotolock Utilizzare nuove guarnizioni per il montaggio Collegare prima possibile il compressore al sistema per evitar...

Страница 18: ...ecessarie diverse ore Se la valvola limitatrice della pressione inter na aperta SY SZ 240 300 380 e SH 380 SH 485 lo scarico del compressore si surriscalda ed il compressore si arresta su intervento d...

Страница 19: ...01 14 19 Instrucciones Compresores Sm Sy sz sh WSH La instalaci n y el mantenimiento del compresor deben ser realizados nicamente por personal cualificado Siga estas instrucciones y las pr cticas de...

Страница 20: ...miendautilizartambi nunaprotecci nadicionalexternaconrearmemanual CC F1 F1 KA KA KA HP LPS T1 T2 T3 KM DGT KS KS 1 2 M ThM KS KS KA KM KM LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185...

Страница 21: ...carga de nitr geno a tra v s de la boquilla schrader Al soldar los conectores Rotolock retire las juntas Utilice siempre juntas nuevas para el mon taje Conecte el compresor al sistema lo antes po sibl...

Страница 22: ...rir va rias horas Si se abre la v lvula de descarga de presi n in terna SY SZ 240 300 380 y SH 380 SH485 el c rter del compresor se calentar y el pro tector del motor parar el compresor 11 Comprobacio...

Страница 23: ...mpressors 01 14 23 INSTRUKTION SCROLL Verdichter SM SY SZ SH WSH Installation und Wartung des Verdichters d rfen nur von qualifiziertem Fachpersonal durchgef hrt werden Diese Anleitung befolgen und be...

Страница 24: ...M LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185 Ausf hrungen mit Thermostat SZ 115 125 160 175 185 Diese Danfoss Verdichter verf gen ber ein bimetallisches SPST Ther mostat in den Mot...

Страница 25: ...lter aus dem Tandem Einbausatz oder die starren Abstandhalter im Lieferumfang spezieller Tandem Verdichter verwenden Die Stickstofff llung langsam durch das Schraderventil ablassen Zum Hartl ten der R...

Страница 26: ...et Lediglich die Verdichter SH WSH 090 184 und SM 112 124 und 147 SZ147 verf gen nicht ber einen integrierten Schutz vor falscher Drehrichtung Ein Betrieb mit falscher Drehrichtung von f hrt bei die s...

Страница 27: ......

Страница 28: ...oducts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the re...

Отзывы: