1.4  Programming

1.4.1 Programming with the Local Control

Panel (LCP)

NOTE

The frequency converter can also be programmed from a
PC via RS-485 com-port by installing the MCT 10 Set-up
Software. This software can either be ordered using code
number 130B1000 or downloaded from the Danfoss Web
site: www.danfoss.com/BusinessAreas/DrivesSolutions/
softwaredownload

1.4.2 Local Control Panel (LCP)

The following instructions are valid for the FC 111 LCP. The
LCP is divided into four functional sections.

A. Alphanumeric display

B. Menu key

C. Navigation keys and indicator lights (LEDs)

D. Operation keys and indicator lights (LEDs)

Ba

ck

Com

1-20 Motor Power
[2] 0.12kW-0.16HP
Setup 1

A

B

1

12

13

14

15

11

11

10

9

8

7

6

5

4

3

2

C

D

Status

Main

Menu

Quick

Menu

Hand

On

OK

Menu

Off

Reset

Auto

On

Alarm

Warn

On

130BB765.10

A. Alpha Numeric Display
The LCD-display is back-lit with 2 alpha-numeric lines. All
data is displayed on the LCP.

A number of information can be read from the display.

1

Parameter number and name.

2

Parameter value.

3

Set-up number shows the active set-up and the edit set-
up. If the same set-up acts as both active and edit set-up,
only that set-up number is shown (factory setting). When
active and edit set-up differ, both numbers are shown in
the display (Setup 12). The number flashing, indicates the
edit set-up.

4

Motor direction is shown to the bottom left of the display
– indicated by a small arrow pointing either clockwise or
counterclockwise.

5

The triangle indicates if the LCP is in status, quick menu or
main menu.

B. Menu Key
Use the menu key to select between status, quick menu or
main menu.

C. Navigation keys and indicator lights (LEDs)

6 Com led: Flashes when bus communication is communi-

cating.

7 Green LED/On: Control section is working.
8 Yellow LED/Warn.: Indicates a warning.
9 Flashing Red LED/Alarm: Indicates an alarm.
10 [Back]: For moving to the previous step or layer in the

navigation structure

11 Arrows [

] [

]: For maneuvering between parameter groups,

parameters and within parameters. Can also be used for
setting local reference.

12 [OK]: For selecting a parameter and for accepting changes to

parameter settings

D. Operation keys and indicator lights (LEDs)

13 [Hand On]: Starts the motor and enables control of the

frequency converter via the LCP.

NOTE

Terminal 27 Digital Input (

5-12 Terminal 27 Digital

Input

) has coast inverse as default setting. This means

that [Hand On] will not start the motor if there is no
24 V to terminal 27. Connect terminal 12 to terminal
27.

14 [Off/Reset]: Stops the motor (off). If in alarm mode the

alarm will be reset.

15 [Auto On]: frequency converter is controlled either via

control terminals or serial communication.

Quick Guide

VLT

®

 HVAC Basic Drive Cascade Controller Quick Guide

12

MG18F202 - VLT

®

 is a registered Danfoss trademark

1

1

Содержание PK37

Страница 1: ...MAKING MODERN LIVING POSSIBLE Quick Guide VLT HVAC Basic Drive Cascade Controller...

Страница 2: ...ectrical Installation 8 1 3 8 Control Terminals 10 1 3 9 Electrical Overview 11 1 4 Programming 12 1 4 1 Programming with the Local Control Panel LCP 12 1 4 3 The Start up Wizard for Open Loop Applica...

Страница 3: ...e conductor Where a residual current device RCD is used for extra protection only an RCD of Type B time delayed shall be used on the supply side of this product See also Danfoss Application Note on RC...

Страница 4: ...not be disposed of together with domestic waste It must be separately collected with electrical and electronic waste according to local and currently valid legislation 1 3 Installation 1 3 1 Before S...

Страница 5: ...29 13 240 9 4 100 3 9 74 2 9 206 8 1 5 5 H4 IP20 11 15 kW 15 20 Hp 296 11 7 359 14 1 275 10 8 135 5 3 105 4 1 241 9 5 7 H5 IP20 18 5 22 kW 25 30 Hp 334 13 1 402 15 8 314 12 4 150 5 9 120 4 7 255 10 7...

Страница 6: ...37 1 5 1 4 0 8 0 8 0 5 0 8 0 5 H2 IP20 2 2 4 1 4 0 8 0 8 0 5 0 8 0 5 H3 IP20 5 5 7 5 1 4 0 8 0 8 0 5 0 8 0 5 H4 IP20 11 15 1 2 1 2 1 2 0 5 0 8 0 5 H5 IP20 18 5 22 1 2 1 2 1 2 0 5 0 8 0 5 H6 IP20 30 4...

Страница 7: ...s possible to reduce the noise level and leakage currents For further details on mounting of the decoupling plate please see instruction MI02QXYY Also see EMC Correct Installation in the Design Guide...

Страница 8: ...rnational regulations Short circuit protection Danfoss recommends using the fuses mentioned in the following tables to protect service personnel or other equipment in case of an internal failure in th...

Страница 9: ...0 80 37 FRS R 100 KTS R100 JKS R100 JJS R100 100 45 FRS R 125 KTS R125 JKS R125 JJS R125 125 55 FRS R 150 KTS R150 JKS R150 JJS R150 150 75 FRS R 200 KTS R200 JKS R200 JJS R200 200 90 FRS R 250 KTS R2...

Страница 10: ...etc Panel Mains supply Min 200mm between control cable mains cable and between mains motor cable PLC Protective earth Reinforced protective earth 130BB761 10 Illustration 1 3 EMC correct Electrical In...

Страница 11: ...nput 29 mode is set in 5 03 Digital Input 29 Mode PNP is default value Control terminals Illustration 1 5 shows all control terminals of the frequency converter Applying Start term 18 connection betwe...

Страница 12: ...OV PNP 24V NPN OV PNP Bus ter Bus ter RS 485 Interface RS 485 N PS 485 69 P RS 485 68 Com RS 485 61 PNP Source NPN Sink ON Terminated OFF Unterminated ON 1 2 240V AC 3A Not present on all power sizes...

Страница 13: ...lashing indicates the edit set up 4 Motor direction is shown to the bottom left of the display indicated by a small arrow pointing either clockwise or counterclockwise 5 The triangle indicates if the...

Страница 14: ...nal analog reference voltage or current and optionally also relay signals but no feed back signal from the process applied FC 24V DIG IN DIG IN DIG IN DIG IN COM DIG IN A OUT D OUT A OUT D OUT 18 19 2...

Страница 15: ...tion of Relay 1 0 Alarm Set Maximum Reference 0050 Hz Set Minimum Reference 0016 Hz AMA running OK OK B a c k Status Main Menu Quick Menu Hand On OK Menu Off Reset Auto On Alarm Warn On AMA failed Do...

Страница 16: ...rom nameplate data 1 25 Motor Nominal Speed 100 0 9999 0 RPM Size related Enter motor nominal speed from nameplate data 4 12 Motor Speed Low Limit Hz 0 0 400 Hz 0 Hz Enter the minimum limit for low sp...

Страница 17: ...m Select the function to control output relay 1 5 40 Function Relay 1 Function relay See 5 40 Function Relay Drive running Select the function to control output relay 2 1 29 Automatic Motor Adaption A...

Страница 18: ...50 Hz 6 22 Terminal 54 Low Current 4 mA 6 24 Terminal 54 Low Ref Feedb Value 0016 Hz 6 23 Terminal 54 High Current 20 mA 6 25 Terminal 54 High Ref Feedb Value 50 0 01 s 20 81 PI Normal Inverse Contro...

Страница 19: ...summing all references 3 10 Preset Reference 100 100 0 Enter the set point 6 29 Terminal 54 mode 0 Current 1 Voltage 1 Select if terminal 54 is used for current or voltage input 6 20 Terminal 54 Low...

Страница 20: ...maximum limit for high speed 3 41 Ramp 1 Ramp up Time 0 05 3600 0 s Size related Ramp up time from 0 to rated motor frequency 1 23 Motor Frequency No Name Range Default Function 3 42 Ramp 1 Ramp Down...

Страница 21: ...ad pump alternation takes place every time the event occurs Selections include whenever an alternation timer expires when the lead pump goes into sleep mode Staging is determined by the actual system...

Страница 22: ...erminal 27 29 and 42 45 External Interlock Coast to stop Cut out built in relays are de energized Function of buttons on LCP Variable speed pump lead Fixed speed pumps lag Hand On Ramps up if stopped...

Страница 23: ...00 0 37 Display Text 1 0 38 Display Text 2 0 39 Display Text 3 0 4 LCP Keypad 0 40 Hand on Key on LCP 0 Disabled 1 Enabled 0 42 Auto on Key on LCP 0 Disabled 1 Enabled 0 44 Off Reset Key on LCP 0 Dis...

Страница 24: ...rections 4 12 Motor Speed Low Limit Hz 0 0 400 Hz 0 0 Hz 4 14 Motor Speed High Limit Hz 0 1 400 Hz 65 0 Hz 4 18 Current Limit 0 300 110 4 19 Max Output Frequency 0 0 400 0 Hz 65 0 4 4 Adj Warnings 2 4...

Страница 25: ...01 6 29 Terminal 54 mode 0 Current mode 0 Current mode 1 Voltage mode 6 7 Analog Output 45 6 70 Terminal 45 Mode 0 0 20 mA 1 4 20 mA 2 Digital Output 6 71 Terminal 45 Analog Output 0 No operation 100...

Страница 26: ...0 000s 5 000 8 37 Max Inter char delay 0 025 0 025s 0 025 8 5 Digital Bus 8 50 Coasting Select 0 Digital input 1 Bus 2 Logic AND 3 Logic OR 8 51 Quick Stop Select 0 Digital input 1 Bus 2 Logic AND 3 L...

Страница 27: ...et x 2 3 Automatic reset x 3 4 Automatic reset x 4 5 Automatic reset x 5 6 Automatic reset x 6 7 Automatic reset x 7 8 Automatic reset x 8 9 Automatic reset x 9 10 Automatic reset x 10 11 Automatic re...

Страница 28: ...3 2 Analog in 54 100 Bus Feedback 1 20 01 Feedback 1 Conversion 0 Linear 1 Square root 20 8 PI Basic Setting 20 81 Process PI Normal Inverse Control 0 Normal 1 Inverse 20 83 Process PI Start Speed Hz...

Страница 29: ...ncy converter See parameter group 8 0 24 50 Fan Fault X X The fan is not working Only on 400 V 30 90 kW units 30 19 U phase loss X X Motor phase U is missing Check the phase See 4 58 Missing Motor Pha...

Страница 30: ...sink Temperature Low X This warning is based on the temperature sensor in the IGBT module Only on 400 V 30 90 kW units 69 1 Pwr Card Temp X X X The temperature sensor on the power card is either too...

Страница 31: ...80 440 V A 1 3 2 4 4 1 5 8 7 9 9 9 13 2 17 1 25 3 34 0 40 7 46 8 67 1 80 3 99 0 116 0 161 0 194 0 Continuous 3x440 480 V A 1 1 2 1 3 4 4 8 6 3 8 2 11 0 14 0 21 0 27 0 34 0 40 0 52 0 65 0 80 0 105 0 13...

Страница 32: ...8 98 1 9 7 9 98 0 9 7 8 98 1 9 7 9 98 1 9 7 9 97 8 97 9 97 1 98 3 98 3 98 3 Output current 50 C ambient temperature Continuous 3x380 440 V A 1 04 1 93 3 7 4 85 6 3 8 4 10 9 14 0 20 9 28 0 34 1 38 0 48...

Страница 33: ...nals U V W If a motor phase is missing the frequency converter trips and issues an alarm If a mains phase is missing the frequency converter trips or issues a warning depending on the load Monitoring...

Страница 34: ...ge on input 28 V DC Input resistance Ri Approx 4 k Digital input 29 as thermistor input Fault 2 9 k and no fault 800 Digital output Programmable digital outputs 2 Terminal number 27 291 Voltage level...

Страница 35: ...EN 60664 1 Overvoltage category III pollution degree 2 1 IEC 60947 parts 4 and 5 Control card 10 V DC output Terminal number 50 Output voltage 10 5 V 0 5 V Max load 25 mA All inputs outputs circuits...

Страница 36: ...the frequency converter is operated at high ambient temperature the continuous output current should be decreased For derating curve see Design Guide MG18C3YY 1 9 2 Derating for Low Air Pressure The...

Страница 37: ...www danfoss com drives MG18F202 130R0265 MG18F202 Rev 2011 11 03...

Отзывы: