Parameter Overview
1-50 Motor Magnetisation at
Zero Speed
0 - 300, * 100%
1-52 Min Speed Normal
Magnetising [Hz]
0.0 - 10.0, * 0.0
1-55 U/f Characteristic - U
0 - 999 V, *0V
1-56 U/f Characteristic - F
0 - 400 Hz, *(0)
1-6* Load Depend. Setting
1-62 Slip Compensation
-400 - 399%, * 0%
1-63 Slip Compensation Time
Constant
0.05 - 5.00 s, * 0.10
1-64 Resonance Dampening
0 - 500%, * 100
1-65 Resonance Dampening Time
Constant
0.001 - 0.050 s, * 0.005
1-7* Start Adjustments
1-71 Start Delay
0.0 - 10.0 s, * 0.0
1-72 Start Function
[0] DC Hold/delay time
*[2] Coast/delay time
1-73 Flying Start
*[0] Disabled
[1] Enabled
1-8* Stop Adjustments
1-80 Function at Stop
*[0] Coast
[1] DC hold/MotorPreheat
1-82 Min Speed for Function at
Stop [Hz]
0.0 - 20.0 Hz, * 0.0
1-9* Motor Temperature
1-90 Motor Thermal Protection
*[0] No protection
[1] Thermistor warning
[2] Thermistor trip
[3] ETR warning 1
[4] ETR trip 1
1-93 Thermistor Resource
*[0] None
[1] Analog input 53
[6] Digital input 29
2-** Brakes
2-0* DC-Brake
2-00 DC Hold/Motor Preheat
Current
0 - 160%, * 50
2-01 DC Brake Current
0 - 150%, * 50
2-02 DC Braking Time
0.0 - 60.0 s, * 10.0
2-04 DC Brake Cut In Speed
0.0 - 400.0 Hz, * 0.0
2-1* Brake Energy Funct.
2-17 Over-voltage Control
[0] Disabled
*[2] Enabled
3-** Reference / Ramps
3-0* Reference Limits
3-02 Minimum Reference
(-4999.000) - 4999.000, * 0.000
3-03 Maximum Reference
(-4999.000) - 4999.000, * 50.000
3-1* References
3-10 Preset Reference
-100.00 - 100.00 %, * 0.00
3-11 Jog Speed [Hz]
0.0 - 400.0 Hz, * 5.0
3-14 Preset Relative Reference
-100.00 - 100.00, * 0.00
3-15 Reference Resource 1
[0] No function
*[1] Analog in 53
[2] Analog in 54
[11] Local bus reference
3-16 Reference 2 Resource
[0] No function
[1] Analog in 53
*[2] Analog in 54
[11] Local bus reference
3-17 Reference 3 Resource
[0] No function
[1] Analog in 53
[2] Analog in 54
*[11] Local bus reference
3-4* Ramp 1
3-41 Ramp 1 Ramp up Time
0.05 - 3600.00 s, *Size related
3-42 Ramp 1 Ramp Down Time
0.05 - 3600.00 s, *Size related
3-5* Ramp 2
3-51 Ramp 2 Ramp up Time
0.05 - 3600.00 s, *Size related
3-52 Ramp 2 Ramp down Time
0.05 - 3600.00 s, *Size related
3-8* Other Ramps
3-80 Jog Ramp Time
0.05 - 3600.00 s, *Size related
3-81 Quick Stop Ramp Time
0.05 - 3600.00 s, *Size related
4-** Limits / Warnings
4-1* Motor Limits
4-10 Motor Speed Direction
[0] Clockwise
*[2] Both directions
4-12 Motor Speed Low Limit [Hz]
0.0 - 400 Hz, * 0.0 Hz
4-14 Motor Speed High Limit
[Hz]
0.1 - 400 Hz, * 65.0 Hz
4-18 Current Limit
0 - 300%, * 110
4-19 Max Output Frequency
0.0 - 400.0 Hz, * 65.0
4-4* Adj. Warnings 2
4-40 Warning Freq. Low
0.0-400.0 Hz, *400.0
4-41 Warning Freq. High
0.0-400.0 Hz, *400.0
4-5* Adj. Warnings
4-50 Warning Current Low
0.00 - 194.00 A, * 0.00
4-51 Warning Current High
0.00 - 194.00 A, * 194.00
4-54 Warning Reference Low
-4999.000 - 4999.000, *-4999.000
4-55 Warning Reference High
-4999.000 - 4999.000, *4999.000
4-56 Warning Feedback Low
-4999.000 - 4999.000, *-4999.000
4-57 Warning Feedback High
-4999.000 - 4999.000, *4999.000
4-58 Missing Motor Phase
Function
[0] Off
*[1] On
4-6* Speed Bypass
4-61 Bypass Speed From [Hz]
0.0 - 400.0, * 0.0
4-63 Bypass Speed To [Hz]
0.0 - 400.0, * 0.0
4-64 Semi-Auto Bypass Set-up
*[0] Off
[1] Enable
5-** Digital In/Out
5-0* Digital I/O mode
5-00 Digital Input Mode
*[0] PNP
[1] NPN
5-03 Digital Input 29 Mode
*[0] PNP
[1] NPN
5-1* Digital Inputs
5-10 Terminal 18 Digital Input
[0] No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
*[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire mode
[52] Run permissive
[53] Hand Start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
[120] Lead Pump Start
[121] Lead Pump Alternation
[130] Pump 1 Interlock
[131] Pump 2 Interlock
[132] Pump 3 Interlock
[133] Pump 4 Interlock
[134] Pump 5 Interlock
5-11 Terminal 19 Digital Input
See par. 5-10, *[0] No operation
5-12 Terminal 27 Digital Input
See par. 5-10, *[2] Coast inverse
5-13 Terminal 29 Digital Input
See par. 5-10, *[14 Jog]
5-3* Digital Outputs
5-34 On Delay, Digital Output
0.00 - 600.00 s, *0.01 s
5-35 Off Delay, Digital Output
0.00 - 600.00 s, *0.01 s
5-4* Relays
5-40 Function Relay
*[0] No operation
[1] Control ready
[2] Drive ready
[3] Drive ready/remote control
[4] Enable / no warning
[5] VLT running
[6] Running / no warning
[7] Run in range/no warning
[8] Run on ref/no warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
Quick Guide
VLT
®
HVAC Basic Drive Cascade Controller Quick Guide
MG18F202 - VLT
®
is a registered Danfoss trademark
23
1