Parameter Overview
16-30 DC Link Voltage
0 - 65535, * 0
16-34 Heatsink Temp.
0 - 255, * 0
16-35 Inverter Thermal
0 - 255%, * 0
16-36 Inv. Nom. Current
0.00 - 655.35, * 0.00
16-37 Inv. Max. Current
0.00 - 655.35
16-38 SL Controller State
0 - 255, * 0
16-5* Ref. and Feedb.
16-50 External Reference
-200.0 - 200.0%, * 0.0
16-52 Feedback
-4999.000 - 4999.000, * 0.000
16-6* Inputs and Outputs
16-60 Digital input
0 - 65535, * 0
16-61 Terminal 53 Setting
*[0] Current mode
[1] Voltage mode
16-62 Analog Input 53
0.00 - 10.00, * 1.00
16-63 Terminal 54 Setting
*[0] Current mode
[1] Voltage mode
16-64 Analog Input 54
0.00 - 20.00, * 1.00
16-65 Analog Output 42 [mA]
0.00 - 20.00, * 0.00
16-61 Digital Output
16-72 Counter A
-32768 - 32767, * 0
16-73 Counter B
-32768 - 32767, * 0
16-79 Analog output 45
20 - 20mA, * 0
16-8* Fieldbus / FC Port
16-86 FC Port REF 1
-32768 - 32767, * 0
16-9* Diagnosis Readouts
16-90 Alarm Word
0 - 0xFFFFFFFFUL, * 0
16-91 Alarm Word 2
0 - 0xFFFFFFFFUL, * 0
16-92 Warning Word
0 - 0x7FFFFFFFUL, * 0
16-93 Warning Word 2
0 - 0x7FFFFFFFUL, * 0
16-94 Ext. Status Word
0 - 0x7FFFFFFFUL, * 0
16-95 Ext. Status Word 2
0 - 0x7FFFFFFFUL, * 0
18-**Extended Motor Data
18-1* Firemode Log
18-10 Firemode log: Event
0-255, *0
20-** FC Closed Loop
20-0* Feedback
20-00 Feedback 1 Source
*[0] No function
[1] Analog in 53
[2] Analog in 54
[100] Bus Feedback 1
20-01 Feedback 1 Conversion
*[0] Linear
[1] Square root
20-8* PI Basic Setting
20-81 Process PI Normal/ Inverse Control
*[0] Normal
[1] Inverse
20-83 Process PI Start Speed[Hz]
0.0 - 200.0, * 0.0
20-84 On Reference Bandwidth
0 - 200%, * 5
20-9* PI Controller
20-91 PI Anti Windup
[0] Off
*[1] On
20-93 PI Proportional Gain
0.00 - 10.00, * 0.01
20-94 PI Integral Time
0.10 - 9999.00s, * 9999.00
20-97 Process PI Feed Forward Factor
0 - 400%, * 0
22-** Appl. functions
22-4* Sleep mode
22-40 Minimum Run Time
0 - 600 s, * 10
22-41 Minimum Sleep Time
0 - 600 s, * 10
22-43 Wake-Up Speed [Hz]
0.0 - 400.0, * 100.0
22-44 Wake-Up Ref./FB difference
0 - 100%, * 10
22-45 Setpoint Boost
-100 - 100%, * 0
22-46 Maximum Boost Time
0 - 600 s, * 60
22-47 Sleep Speed [Hz]
0.0 - 400.0, * 0.0
22-6* Broken Belt Detection
22-60 Broken Belt Detection
*[0] Off
[1] Warning
[2] Trip
22-61 Broken Belt Torque
5 - 100%, * 10
22-62 Broken Belt Delay
0 - 600 s, * 10
24-** Appl. functions 2
24-0* Fire mode
24-00 Fire Mode Function
*[0] Disabled
[1] Enabled Run Forward
[2] Enabled Run Reverse
[3] Enable-Coast
[4] Enabled - Run Fwd/Rev
24-05 Fire Mode Preset Reference
-100 - 100%, * 0
24-09 Fire Mode Alarm Handling
*[1] Trip, Critical Alarms
[2] Trip, All Alarms/Test
24-1* Drive Bypass
24-10 Drive Bypass Function
*[0] Disabled
[2] Enabled (Fire Mode only)
24-11 Bypass Delay Timer
0 - 600 s, * 0
Quick Guide
VLT
®
HVAC Basic Drive Cascade Controller Quick Guide
MG18F202 - VLT
®
is a registered Danfoss trademark
27