Parameter Overview
[2] Feedback
[3] Motor speed
[4] Motor current
[6] Motor power
[7] Motor voltage
[8] DC-link voltage
[12] Analog in 53
[13] Analog in 54
[20] Alarm number
[30] Counter A
[31] Counter B
13-11 Comparator Operator
[0] Less Than
*[1] Approx. Equal
[2] GreaterThan
13-12 Comparator Value
-9999.0 - 9999.0, * 0.0
13-2* Timers
13-20 SL Controller Timer
0.00 - 3600.00, * 0.00
13-4* Logic Rules
13-40 Logic Rule Boolean 1
See par. 13-01, *[0] False
13-41 Logic Rule Operator 1
*[0] Disabled
[1] AND
[2] OR
[3] AND NOT
[4] OR NOT
[5] NOT AND
[6] NOT OR
[7] NOT AND NOT
[8] NOT OR NOT
13-42 Logic Rule Boolean 2
See par. 13-01, *[0] False
13-43 Logic Rule Operator 2
See par. 13-41, *[0] Disabled
13-44 Logic Rule Boolean 3
See par. 13-01, *[0] False
13-5* States
13-51 SL Controller Event
See par. 13-01, *[0] False
13-52 SL Controller Action
*[0] Disabled
[1] No action
[2] Select set-up 1
[3] Select set-up 2
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[25] Qstop
[26] DC Brake
[27] Coast
[28] Freeze output
[29] Start timer 0
[30] Start timer 1
[31] Start timer 2
[32] Set digital out A low
[33] Set digital out B low
[34] Set digital out C low
[35] Set digital out D low
[38] Set digital out A high
[39] Set digital out B high
[40] Set digital out C high
[41] Set digital out D high
[60] Reset Counter A
[61] Reset Counter B
[70] Start timer 3
[71] Start timer 4
[72] Start timer 5
[73] Start timer 6
[74] Start timer 7
[100] Reset Alarm
14-** Special Functions
14-0* Inverter Switching
14-01 Switching Frequency
[0] Ran3
[1] Ran5
[2] 2.0 kHz
[3] 3.0 kHz
[4] 4.0 kHz
[5] 5.0 kHz
[6] 6.0 kHz
[7] 8.0 kHz
[8] 10.0 kHz
[9] 12.0kHz
[10] 16.0kHz
14-03 Overmodulation
[0] Off
*[1] On
14-08 Damping Gain Factor
0 - 100-%, * 96
14-1* Mains on/off
14-12 Function at Mains
Imbalance
*[0] Trip
[1] Warning
[2] Disabled
[3] Derate
14-2* Reset Functions
14-20 Reset Mode
*[0] Manual reset
[1] Automatic reset x 1
[2] Automatic reset x 2
[3] Automatic reset x 3
[4] Automatic reset x 4
[5] Automatic reset x 5
[6] Automatic reset x 6
[7] Automatic reset x 7
[8] Automatic reset x 8
[9] Automatic reset x 9
[10] Automatic reset x 10
[11] Automatic reset x 15
[12] Automatic reset x 20
[13] Infinite auto reset
14-21 Automatic Restart Time
0 - 600s, * 10
14-22 Operation Mode
*[0] Normal operation
[2] Initialisation
14-27 Action At Inverter Fault
[0] Off
*[1] On
14-28 Production Settings
*[0] No action
[1] Service reset
[3] Software Reset
14-29 Service Code
0 - 0x7FFFFFFF, * 0
14-3* Current Limit Ctrl.
14-4* Energy Optimising
14-40 VT Level
40 - 90%, * 90%
14-41 AEO Minimum Magnetisation
40 - 75%, * 66
14-5* Environment
14-50 RFI Filter
[0] Off
*[1] On
14-51 DC-link Voltage Compen-
sation
[0] Off
*[1] On
14-52 Fan Control
*[0] Auto
[4] Auto Low temp env
14-53 Fan Monitor
[0] Disabled
*[1] Warning
[2] Trip
14-55 Output Filter
*[0] No Filter
[1] Sine-Wave Filter
[3] Sine-Wave Filter with Feedback
14-63 Min Switch Frequency
1 - 16kHz, * 1
15-** Drive Information
15-0* Operating Data
15-00 Operating Hours
0 - 2147483647, * 0
15-01 Running Hours
0 - 2147483647, * 0
15-02 kWh Counter
0 - 65535, * 0
15-03 Power Up's
0 - 2147483647, * 0
15-04 Over Temp's
0 - 65535, * 0
15-05 Over Volt's
0 - 65535, * 0
15-06 Reset kWh Counter
*[0] Do not reset
[1] Reset counter
15-07 Reset Running Hours Counter
*[0] Do not reset
[1] Reset counter
15-3* Fault Log
15-30 Fault Log:
Error Code 0 - 255, * 0
15-4* Drive Identification
15-40 FC Type
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-44 OrderedTypeCode
15-46 Frequency Converter
Ordering No
15-47 Power Card Ordering No
15-48 LCP Id No
15-49 Software ID Control Card
15-50 Software ID Power Card
15-51 Frequency Converter Serial
Number
15-53 Power Card Serial Number
16-** Data Readouts
16-0* General Status
16-00 Control Word
0 - 65535, * 0
16-01 Reference [Unit]
-4999.000 - 4999.000, * 0.000
16-02 Reference
% -200.0 - 200.0, * 0.0
16-03 Status Word
0 - 65535, * 0
16-05 Main Actual Value [%]
-200.00 - 200.00, * 0.00
16-09 Custom Readout
0.00 - 9999.00, * 0.00
16-1* Motor Status
16-10 Power [kW]
0.000-4.294, 967.500, *0.000
16-11 Power [hp]
0.000 - 2.294, 967.500 *0.000
16-3* Drive Status
Quick Guide
VLT
®
HVAC Basic Drive Cascade Controller Quick Guide
26