Instructions
4 | AN23308644013404-001201
© Danfoss | DCS (CC) | 2019.01
vacuum tube or air nozzle.
If the refrigerant system has been opened, the
system has to be flushed with dry air or nitrogen
to remove moisture and a new filter drier has to
be installed. If evacuation of refrigerant has to be
done, it shall be done in such a way that no refri-
gerant can escape to the environment.
Service panel removal procedure for
W09 Version.
OP-LSQM014, 018, OP-MSGM018, 021, OP-
MSYM009, 012, 014, OP-MSGM012, 015
OP-MSYM018, OP-LSQM026 - 034 - 048 - 068
- 074, OP-MSBM018 - 024 - 026 - 034, OP-
MSXM034 - 044 - 046 - 057, OP-MSGM026 -
033, OP-LSQM067 - 084 - 098, OP-MSXM068
- 080 - 093 - 099 - 108
Step 1: Pull the cap from the isolator switch
using screw driver.
Step 2: Unscrew the isolator switch from the ser-
vice panel.
Step 3: Take out the isolator switch.
Step 4: Removing the service panel.
13 – Declaration of conformity
• Pressure Equipment Directive 2014/68/EU
EN 378-2:2016 - Refrigerating systems and
Heat Pumps - Safety and environmental requi-
rements-Parts 2: Design, construction, testing,
marking and documentation
Low Voltage Directive 2014/35/EU EN 60335-
1:2012 + A11:2014- Household and similar elec-
trical appliances-Safety-Part 1: General requi-
rements-for all above mentioned condensing
units
Eco-design DIRECTIVE 2009/125/ EC, esta-
blishing a framework for the setting of Eco-de-
sign requirements for energy-related products.
REGULATION (EU) 2015/1095, implementing
Eco-design Directive 2009/125/EC with regard
to Eco-design requirements for professional
refrigerated storage cabinets, blast cabinets,
condensing units and process Chiller.
• Condensing unit measurements are made
according to standard “EN 13771-2:2007” – Com-
pressor and condensing units for refrigeration-
performance testing and test methods- part 2:
Condensing units
14 - Warranty
Always transmit the model number and serial num-
ber with any claim filed regarding this product.
The product warranty may be void in following
cases:
• Absence of nameplate.
• External modifications; in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the
compressor.
• Use of a refrigerant or lubricant not approved
by Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or main-
tenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmit-
ted with the warranty claim.
15 – Disposal
Danfoss recommends that condensing
units and oil should be recycled by a
suitable company at its site.
16 - Fan speed controller setting for R134a/R513A
refrigerant
FSC type
Fan speed Controller
Spare part number
Refrigerant
letter
For Refrigerant
Factory
setting
Action required
XGE-2C
061H3144
Q
R404A/R452A/R507
15 bar
360°=1 turn = Approx 0.8 bar
(Clockwise rotation =
Increase pressure setting,
Counter clockwise rotation =
Decrease pressure setting)
H
R404A/R507
15 bar
X
R404A/R507/R134a/R513A/ R407A/
R407F/R448A/R449A/R452A
15 bar
Y
R404A/R507/R449A
15 bar
B
R404A/R507/R449A/R452A
15 bar
G
R134a/R513A
8 bar
X
If refrigerant used is R134a or R513A
15 bar
Rotate the screw by 9 turns in counter
clockwise direction to reach 8 bar
17 - Pressostat factory settings
Refrigerants
High pressure settings (bar (g))
Low pressure settings (bar (g))
ON
OFF
ON
OFF
R404A/R507/R407A/R407F/R448A/R449A/R452A
23
27
2
1
R134a/R513A
13
17
2
1