FRCC.EI.026.A5.02 © Danfoss Commercial Compressors 09/14

Instructions

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

  •  Do not use dye for leak detection.

  •  Perform a leak detection test on the complete 

system.

  •  The maximum test pressure is 32 bar.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

  •  Never use the compressor to evacuate the system.

  •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

μm Hg (0.67 mbar) absolute.

  •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

  •  Switch off and isolate the main power supply.

  •  Ensure that power supply can not be switched 

on during installation.

  •  All electrical components must be selected as 

per local standards and unit requirements.

 •  Refer to wiring diagram for electrical connec-

tions details.

 •  Ensure that the power supply corresponds to 

the unit characteristics and that the power 

supply is stable (nominal voltage ±10% and 

nominal frequency ±2,5 Hz).

 •  Dimension the power supply cables accor-

ding to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing.

 •  Make the power supply according to local 

standards and legal requirements.

 •  The unit is equipped with high and low pres-

sure switches, which directly cut the power 

supply to the compressor in case of activation. 

Parameters for high and low pressure cut outs 

should be set by installer considering compres-

sor model, refrigerant and application. Units 

with Danfoss MLZ, LLZ and NTZ compressors 

are also equipped with phase sequence relay to 

protect the unit against phase loss/sequence/ 

asymmetry and under-/over-voltage.

For units with a 3-phase scroll compressor, cor-

rect phase sequence for compressor rotation 

direction shall be observed.

 •  Determine the phase sequence by using a 

phase meter in order to establish the phase 

orders of line phases L1, L2 and L3.

 •  Connect line phases L1, L2 and L3 to main 

switch terminals T1, T2 and T3 respectively.

8 – Filling the system

  •  Wear protective stuff like goggles and protec-

tive gloves.

 •  Never start the compressor under vacuum. 

Keep the compressor switched off.

 •  Before charging the refrigerant, verify that the 

oil level is between ¼ and ¾ on the compressor 

oil sight glass. If additional oil is required please 

refer to the compressors label for type of oil.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 

charging of the system to 4 – 5 bar for R404A / 

R507A or R22 and approx. 2 bar for R134a.

  •  Do not put liquid refrigerant through suction line.

 •  It is not allowed to mix additives with the oil 

and/or refrigerant

 •  The remaining charge is done until the instal-

lation has reached a level of stable nominal 

condition during operation.

 •  Never leave the filling cylinder connected to 

the circuit.

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in com-

pliance with both generally and locally appli-

cable regulations and safety standards. Ensure 

that they are operational and properly set.

 Check that the settings of high-pressure swit-

ches and relief valves don’t exceed the maximum 

service pressure of any system component.

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must 

be energized at least 12 hours before initial 

start-up and start-up after prolonged shut-

down period.

10 – Start-up

 •  Never start the unit when no refrigerant is 

charged.

  •  All service valves must be in the open position.

See picture 3.

 •  Check compliance between unit and power 

supply.

  •  Check that the crankcase heater is working.

  •  Check that the fan can rotate freely.

 •  Check that the protection sheet has been re-

moved from the backside of condenser.

  •  Balance the HP/LP pressure.

 •  Energize the unit. It must start promptly. If 

the compressor does not start, check wiring 

conformity, voltage on terminals and se-

quence phase.

 •  Eventual reverse rotation of  a 3-phase com-

pressor can be detected by following phe-

nomena; unit doesn’t start, the compressor 

doesn’t build up pressure, it has abnormally 

high sound level and abnormally low power 

consumption. In such case, shut down the 

unit immediately and connect the phases to 

their proper terminals.

  •  If the rotation direction is correct the low pres-

sure indication on the low pressure gauge 

shall show a declining pressure and the high 

pressure indication on the high pressure 

gauge shall show an increasing pressure.

11 – Check with running unit

  •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

  •  Check current draw and voltage.

 •  Check suction superheat to reduce risk of 

slugging.

  •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

  •  Respect the operating limits.

  •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 

far away as possible from the compressor. The 

compressor must be operating during this pro-

cess.

  •  Do not overcharge the system.

  •  Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

  •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 – Maintenance

 Always switch off the unit at main switch 

before remove fan panel.

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related problems, following

Periodic  maintenance is recommended:

 •  Verify that safety devices are operational and 

properly set.

  •  Ensure that the system is leak tight.

  •  Check the compressor current draw.

 •  Confirm that the system is operating in a way 

consistent with previous maintenance re-

cords and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 •  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 

tubes and electrical connections.

The condenser must be checked at least once 

a year for clogging and be cleaned if deemed 

necessary. Access to the internal side of the 

condenser takes place through the fan panel. 

Microchannel coils tend to accumulate dirt on 

the surface rather than inside, which makes 

them easier to clean than fin-&-tube coils.

 •  Switch off the unit at main switch before re-

move any panel from the condensing unit.

 •  Remove surface dirt, leaves, fibres, etc. with 

a vacuum cleaner, equipped with a brush or 

other soft attachment. Alternatively, blow 

compressed air through the coil from the in-

side out, and brush with a soft bristle. Do not 

use a wire brush. Do not impact or scrape the 

coil with the vacuum tube or air nozzle.

If the refrigerant system has been opened, the 

system has to be flushed with dry air or nitrogen 

to remove moisture and a new filter drier has to

be installed. If evacuation of refrigerant has to 

be done, it shall be done in such a way that no 

refrigerant can escape to the environment.

13 - Warranty

Always transmit the model number and serial num-

ber with any claim filed regarding this product.

The product warranty may be void in following 

cases:

  •  Absence of nameplate.

 •  External modifications; in particular, drilling, 

welding, broken feet and shock marks.

  •  Compressor opened or returned unsealed.

 •  Rust, water or leak detection dye inside the 

compressor.

  •  Use of a refrigerant or lubricant not approved 

by Danfoss.

 •  Any deviation from recommended instruc-

tions pertaining to installation, application or 

maintenance.

  •  Use in mobile applications.

  •  Use in explosive atmospheric environment.

 •  No model number or serial number transmit-

ted with the warranty claim.

14 – Disposal

Danfoss recommends that condensing 

units and oil should be recycled by a 

suitable company at its site.

Содержание Optyma Slim Pack OP-LSHM Series

Страница 1: ...panish p 22 Deutsch German p 28 Dansk Danish p 34 Svenska Swedish p 40 Portugu s Portuguese p 46 Nederlands Dutch p 52 Suomi Finnish p 58 Elinika Greek p 64 Norsk Norwegian p 70 B lgarski Bulgarian p...

Страница 2: ...FRCC EI 026 A5 ML Danfoss Commercial Compressors 09 14 2 OP LSHM026 034 048 068 074 OP MSHM024 026 034 OP MSUM034 046 057 OP LSHM015 018 OP MSHM010 012 015 018 Instructions...

Страница 3: ...3 FRCC EI 026 A5 ML Danfoss Commercial Compressors 09 14 Instructions OP LSHM067 084 098 OP MSUM068 080 093 099 108...

Страница 4: ...dtransporttheunitinanuprightposition Store the unit between 35 C and 50 C Don t expose the packaging to rain or corro sive atmosphere After unpacking check that the unit is com plete and undamaged 3 I...

Страница 5: ...voltage on terminals and se quence phase Eventual reverse rotation of a 3 phase com pressor can be detected by following phe nomena unit doesn t start the compressor doesn t build up pressure it has...

Страница 6: ...N P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP...

Страница 7: ...PT NAME 1 1 wiring diagram Schaltplan plan de circuits u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D...

Страница 8: ...E 4 0A 4 8A APP c d e REV models A1 05 09 14 AJ FH models OP LSHM074FHW05E 7 9A Code G OP MSUM093 Code E OP LSHM048 068 074 OP MSHM026 034 OP MSUM034 046 057 9 8 7 6 5 4 1 0 2 3 DATE SHEET OF DRAWING...

Страница 9: ...8 25 A1 CC RCU 13A 15A 16A 15A OP MSUM068MLW05E OP MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E OP LSHM067LLW05E OP LSHM084LLW05E OP LSHM098LLW05E 12A 15A 15A 114X7092 114X7075 114X7091 OP LSHM067L...

Страница 10: ...ne temp rature comprise entre 35 C et 50 C N exposez pas l emballage la pluie ou une atmos ph re corrosive Apr s le d ballage v rifiez que le groupe est com plet et qu il n est pas endommag 3 Pr cauti...

Страница 11: ...i ci doit d marrer rapide ment S il ne d marre pas v rifiez la conformit des c blages la tension aux bornes et l ordre des phases Il est possible de d terminer si le sens de rotation d un compresseur...

Страница 12: ...X1 BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW05G OP MSHM018SCW05G OP MSHM026AJW05G OP...

Страница 13: ...its u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC RCU OP MSUM068MLW05G OP MSUM080M...

Страница 14: ...A 5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 380 400V3N 50Hz L1 L2...

Страница 15: ...MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E OP LSHM067LLW05E OP LSHM084LLW05E OP LSHM098LLW05E 12A 15A 15A 114X7092 114X7075 114X7091 OP LSHM067LLW05E OP LSHM084LLW05E OP LSHM098LLW05E 114X7068 11...

Страница 16: ...azynowa agregat w temperaturze od 35 C do 50 C Chroni opakowanie przed dzia aniem deszczu oraz innych czynnik w atmosferycznych powoduj cych korozj Po rozpakowaniu sprawdzi czy agregat jest kom pletny...

Страница 17: ...zaciskach oraz kolejno pod czenia faz Odwrotny kierunek obrot w spr arki 3 fazowej mo na wykry w nast puj cy spos b agregat uru chamia si praca spr arki nie powoduje zwi ksza nia ci nienia ale jest ba...

Страница 18: ...BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW05G OP MSHM018SCW05G OP MSHM026AJW05G OP MSH...

Страница 19: ...249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC RCU OP MSUM068MLW05G OP MSUM080MLW05G...

Страница 20: ...P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 380 400V3N 50Hz L1 L2 PE L3 N 1 2 3 4 5 6 7 8 F1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 114X7088 114X...

Страница 21: ...4 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2 F3 95 96 97 98 1 2 3 4 5 6 K1 BK GY BN M 3 M1 xxA 5 6 3 4 1 2 F2 BK BU BK BN 1 N2 N1 BN B...

Страница 22: ...Almacene la unidad a temperaturas comprendidas entre 35 C y 50 C No exponga el embalaje a la lluvia o a atm sferas de car cter corrosivo Tras desembalar la unidad compruebe que no falte ning n compon...

Страница 23: ...rminales y la secuencia de fases El giro en sentido inverso de un compresor trif sico se puede detectar a trav s de los siguientes s nto mas la unidad no se pone en marcha no se acumula presi n en el...

Страница 24: ...A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW05G OP MSHM018SCW05G OP MSHM026AJW05G OP MSHM034AJW0...

Страница 25: ...u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC RCU OP MSUM068MLW05G OP MSUM080MLW05G 32A 38...

Страница 26: ...3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 380 400V3N 50Hz L1 L2 PE L...

Страница 27: ...OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2 F3 95 96 97 98 1 2 3 4 5 6 K1 BK GY BN M 3 M1 x...

Страница 28: ...Sicherheitsvorkehrungen bei der Installation Nicht l ten solange die Verfl ssigereinheit unter Druck steht Stellen Sie den Verfl ssigungssatz niemals in einer explosionsf higen Atmosph re auf Achten...

Страница 29: ...uft berpr fen Sie die Verdrahtung und die Spannung an den Klemmen Ob sich ein 3 Phasen Verdichter in die Gegenrich tung dreht l sst sich an folgenden Ph nomenen er kennen Der Verdichter baut keinen D...

Страница 30: ...BU BN BN 8 P P B C A D PE B2 PE X1 BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW05G OP MS...

Страница 31: ...iagram Schaltplan plan de circuits u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC R...

Страница 32: ...4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 380 400V3N 50Hz L1 L2 PE L3...

Страница 33: ...4X7071 OP MSUM068MLW05E OP MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2 F3 95 9...

Страница 34: ...ved mellem 35 C og 50 C Kondenseringsaggregatet og emballagen m ikke uds ttes for regn eller korroderende atmosf rer Efter udpakningen skal du kontrollere at aggre gatet er helt og ubeskadiget 3 Forh...

Страница 35: ...otation af en trefaset kom pressor kan p vises ved f lgende driftsm nster Aggregatet starter ikke kompressoren opbygger ikke tryk dens lydniveau er unormalt h jt og str mforbruget er unormalt lavt I d...

Страница 36: ...B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW0...

Страница 37: ...wiring diagram Schaltplan plan de circuits u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1...

Страница 38: ...1 2 3 4 5 6 K1 BK GY BN M 3 M1 xxA 5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK...

Страница 39: ...X7072 114X7071 OP MSUM068MLW05E OP MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2...

Страница 40: ...eten i temperaturer p mellan 35 C och 50 C Uts ttintef rpackningenf rregnellerfr tande milj er Kontrollera att enheten r hel och oskadad efter uppackningen 3 F rsiktighets tg rder vid montering Anv nd...

Страница 41: ...Eventuell motrotation av en trefaskompressor kan identifieras med hj lp av f ljande enheten startar inte kompressorn bygger inte upp tryck ljudniv n r onormalt h g och str mf rbruk ningen r onormalt...

Страница 42: ...6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G...

Страница 43: ...DEPT NAME 1 1 wiring diagram Schaltplan plan de circuits u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C...

Страница 44: ...95 96 97 98 1 2 3 4 5 6 K1 BK GY BN M 3 M1 xxA 5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1...

Страница 45: ...8 114X7070 114X7072 114X7071 OP MSUM068MLW05E OP MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M...

Страница 46: ...o vertical Armazene a unidade a uma temperatura entre os 35 C e 50 C N o exponha a embalagem chuva ou a uma atmosfera corrosiva Ap sdesembalar verifiqueseaunidadeest completa e n o est danificada 3 In...

Страница 47: ...rminaiseafasedesequ ncia Umaeventualrota oinversadocompressortrif sico podeserdetectadoatrav sdosseguintesfen menos a unidade n o arranca o compressor n o acumula press o tem um n vel de som estranham...

Страница 48: ...N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW05G OP MSHM018SCW05G OP MSHM026AJW05G OP MSHM0...

Страница 49: ...49499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC RCU OP MSUM068MLW05G OP MSUM080MLW05G...

Страница 50: ...5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 380 400V3N 50Hz L1 L2...

Страница 51: ...MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2 F3 95 96 97 98 1 2 3 4 5 6 K1 BK GY BN M...

Страница 52: ...bijtende omgeving Controleer na het uitpakken of het apparaat volle dig en intact is 3 Voorzorgsmaatregelen bij de installatie Soldeer niet zolang de koelgroep onder druk staat Gebruik het apparaat no...

Страница 53: ...rde draairichting van een 3 fasi ge compressor kan worden gedetecteerd door de volgende kenmerken het apparaat start niet de compressor bouwt geen druk op hij produceert ab normaal veel lawaai en verb...

Страница 54: ...A D PE B2 PE X1 BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW05G OP MSHM018SCW05G OP MSHM...

Страница 55: ...lan de circuits u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC RCU OP MSUM068MLW05G...

Страница 56: ...3 M1 xxA 5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 380 400V3N 50H...

Страница 57: ...05E OP MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2 F3 95 96 97 98 1 2 3 4 5 6...

Страница 58: ...oa pystyasennossa S ilyt koneikkoa 35 50 C eenl mp tilassa l altista pakkausta sateelle tai sy vytt ville olosuhteille Kunkoneikkoonpurettupakkauksesta tarkista ett kaikki osat ovat mukana eik laite o...

Страница 59: ...nen kompressoripy riiv r nsuuntaan koneikko eik ynnisty kompressorieikehit painetta laite pit tavallista kovempaa nt ja se kuluttaa tavallista v hemm n s hk Jos kompressori py rii v r n suuntaan sammu...

Страница 60: ...5G 114X7081 114X7082 A model 06 02 14 RH CC RCU 5 3A 6 3A 6 8A 5 8A 5 5A OP MSHM010SCW05G OP MSHM012SCW05G OP MSHM015SCW05G OP LSHM015SCW05G OP LSHM018SCW05G 9 8 7 6 5 4 1 0 2 3 DATE SHEET OF DRAWING...

Страница 61: ...de circuits u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC RCU OP MSUM068MLW05G OP...

Страница 62: ...N M 3 M1 xxA 5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 380 400V3N...

Страница 63: ...5E OP MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2 F3 95 96 97 98 1 2 3 4 5 6 K...

Страница 64: ...1 7 bar IP54 2 R134a 2 23 bar 2 5 bar Voltage 380 400V3N 50Hz LRA 30 5 7 5 MCC Serial No Barcode Serial No 123456CG0514 118UXXXX A B C D E F G K H I J OPTYMA SLIM PACK OP LSHM MSUM MSHM A C D E F G H...

Страница 65: ...al Compressors 09 14 schrader 19mm 5 32 bar 6 LP HP 500 m Hg 0 67 mbar 7 10 2 5 Hz MLZ LLZ NTZ Danfoss 3 L1 L2 L3 L1 L2 L3 T1 T2 T3 8 4 5 bar R404A R507A R22 2 bar R134a 9 12 10 3 HP LP 3 11 slugging...

Страница 66: ...NORM DIN61346 DEPT NAME 1 wiring diagram Schaltplan plan de circuits u249499 u249499 21 22 K1 3A 1 2 F3 95 96 97 98 118R0143 BK 2 4 3 BU BN BN BN BN PE X1 M 1 M2 S1 BK BN 1 2 1 E1 BU N2 5 6 BN P 1 2 P...

Страница 67: ...26A 114X7061 114X7063 114X7065 OP MSUM034MLW05G OP MSUM046MLW05G OP MSUM057MLW05G a model RH Commercial Compressors 16 06 14 C3 9 8 7 6 5 4 1 0 2 3 DATE SHEET OF DRAWING NO DRW APP REV DATE APPR NORM...

Страница 68: ...E APPR NORM DIN61346 DEPT NAME 1 1 u249499 u249499 118R0113 23 11 12 CC RCU wiring diagram Schaltplan plan de circuits Commercial Compressors 3A 1 2 F3 95 96 97 98 1 2 3 4 5 6 K1 BK GY BN M 3 M1 xxA 5...

Страница 69: ...P MSUM099MLW05E OP MSUM108MLW05E OP LSHM067LLW05E OP LSHM084LLW05E OP LSHM098LLW05E 12A 15A 15A 114X7092 114X7075 114X7091 OP LSHM067LLW05E OP LSHM084LLW05E OP LSHM098LLW05E 114X7068 114X7070 114X7072...

Страница 70: ...og 50 C Ikke utsett pakken for regn eller korroderende milj Kontroller at enheten er komplett og uten skader n r du pakker den opp 3 Forholdsregler ved installasjon Ikke slaglodd s lenge kuldeaggrega...

Страница 71: ...arter m du kontrollere konformitet i ledningsnettet spenningen p terminalene og sekvensfasen Eventuell reversert rotasjon av en 3 faset kompressor kan oppdages i f lgende tilfeller enheten starter ikk...

Страница 72: ...6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G...

Страница 73: ...DEPT NAME 1 1 wiring diagram Schaltplan plan de circuits u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A...

Страница 74: ...3 95 96 97 98 1 2 3 4 5 6 K1 BK GY BN M 3 M1 xxA 5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A...

Страница 75: ...8 114X7070 114X7072 114X7071 OP MSUM068MLW05E OP MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M...

Страница 76: ...28 bar LP 1 7 bar IP54 2 R134a 2 23 bar 2 5 bar Voltage 380 400V3N 50Hz LRA 30 5 7 5 MCC Serial No Barcode Serial No 123456CG0514 118UXXXX A B C D E F G OPTYMA SLIM PACK OP LSHM MSUM MSHM A B C D E F...

Страница 77: ...Danfoss Commercial Compressors 09 14 19 mm 5 32 bar 6 500 m Hg 0 67 mbar 7 10 2 5 Hz Danfoss MLZ LLZ NTZ 3 L1 L2 L3 L1 L2 L3 T1 T2 T3 8 4 5 bar R404A R507A R22 2 bar R134a 9 12 10 3 3 11 1 5 12 100 C...

Страница 78: ...ORM DIN61346 DEPT NAME 1 wiring diagram Schaltplan plan de circuits u249499 u249499 21 22 K1 3A 1 2 F3 95 96 97 98 118R0143 BK 2 4 3 BU BN BN BN BN PE X1 M 1 M2 S1 BK BN 1 2 1 E1 BU N2 5 6 BN P 1 2 PE...

Страница 79: ...114X7065 OP MSUM034MLW05G OP MSUM046MLW05G OP MSUM057MLW05G a model RH Commercial Compressors 16 06 14 C3 9 8 7 6 5 4 1 0 2 3 DATE SHEET OF DRAWING NO DRW APP REV DATE APPR NORM DIN61346 DEPT NAME 1 1...

Страница 80: ...APPR NORM DIN61346 DEPT NAME 1 1 u249499 u249499 118R0113 23 11 12 CC RCU wiring diagram Schaltplan plan de circuits Commercial Compressors 3A 1 2 F3 95 96 97 98 1 2 3 4 5 6 K1 BK GY BN M 3 M1 xxA 5...

Страница 81: ...E OP MSUM108MLW05E OP LSHM067LLW05E OP LSHM084LLW05E OP LSHM098LLW05E 12A 15A 15A 114X7092 114X7075 114X7091 OP LSHM067LLW05E OP LSHM084LLW05E OP LSHM098LLW05E 114X7068 114X7070 114X7072 114X7071 OP M...

Страница 82: ...i grupul n pozi ie vertical Depozita i grupul ntre 35 C i 50 C Nu expune i ambalajul n ploaie sau atmosfer coroziv Dup despachetare asigura i v c grupul este complet i nedeteriorat 3 M suri de precau...

Страница 83: ...fazelor Eventuala rotire invers a compresorului trifazic poate fi detectat dup urm toarele fenomene grupul nu porne te compresorul nu acumuleaz presiune acesta produce prea mult zgomot i consum prea p...

Страница 84: ...B C A D PE B2 PE X1 BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW05G OP MSHM018SCW05G OP...

Страница 85: ...an plan de circuits u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC RCU OP MSUM068ML...

Страница 86: ...BN M 3 M1 xxA 5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 380 400V...

Страница 87: ...8MLW05E OP MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2 F3 95 96 97 98 1 2 3 4...

Страница 88: ...n ho voz ku nebo paletov ho zved ku Pou ijte vhodn a bez pe n zdvihac za zen Jednotkuskladujteap epravujtevesvisl poloze Jednotku skladujte p i teplot ch od 35 do 50 C Chra te obal p ed de t m a koroz...

Страница 89: ...kotlakou a n zkotlakou stranou Zapn te jednotku Mus se ihned rozb hnout Pokud se kompresor nerozeb hne zkontro lujte spr vnost elektrick ho zapojen nap t na p vodn ch svork ch a po ad f z P padn obr c...

Страница 90: ...N 8 P P B C A D PE B2 PE X1 BK N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW05G OP MSHM018SC...

Страница 91: ...Schaltplan plan de circuits u249499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC RCU OP M...

Страница 92: ...BK GY BN M 3 M1 xxA 5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 38...

Страница 93: ...P MSUM068MLW05E OP MSUM080MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2 F3 95 96 97 98...

Страница 94: ...507A 1 28 bar LP 1 7 bar IP54 2 R134a 2 23 bar 2 5 bar Voltage 380 400V3N 50Hz LRA 30 5 7 5 MCC Serial No Barcode Serial No 123456CG0514 118UXXXX A B C D E F G K H I J OPTYMA SLIM PACK OP LSHM MSUM MS...

Страница 95: ...EI 026 A5 50 Danfoss Commercial Compressors 09 14 19 5 32 6 500 0 67 7 10 2 5 Danfoss MLZ LLZ NTZ 3 L1 L2 L3 L1 L2 L3 T1 T2 T3 8 4 5 R404A R507A R22 2 R134a 9 12 10 3 3 11 1 5 12 100 C 13 Danfoss 14...

Страница 96: ...W05G OP MSHM012SCW05G OP MSHM015SCW05G OP LSHM015SCW05G OP LSHM018SCW05G 9 8 7 6 5 4 1 0 2 3 DATE SHEET OF DRAWING NO DRW REV DATE APPR NORM DIN61346 DEPT NAME 1 wiring diagram Schaltplan plan de circ...

Страница 97: ...57MLW05G 19A 25A 26A 114X7061 114X7063 114X7065 OP MSUM034MLW05G OP MSUM046MLW05G OP MSUM057MLW05G a model RH Commercial Compressors 16 06 14 C3 9 8 7 6 5 4 1 0 2 3 DATE SHEET OF DRAWING NO DRW APP RE...

Страница 98: ...E APPR NORM DIN61346 DEPT NAME 1 1 u249499 u249499 118R0113 23 11 12 CC RCU wiring diagram Schaltplan plan de circuits Commercial Compressors 3A 1 2 F3 95 96 97 98 1 2 3 4 5 6 K1 BK GY BN M 3 M1 xxA 5...

Страница 99: ...M099MLW05E OP MSUM108MLW05E OP LSHM067LLW05E OP LSHM084LLW05E OP LSHM098LLW05E 12A 15A 15A 114X7092 114X7075 114X7091 OP LSHM067LLW05E OP LSHM084LLW05E OP LSHM098LLW05E 114X7068 114X7070 114X7072 114X...

Страница 100: ...pioggia o ad atmosfere corrosive Dopo il disimballaggio controllare che l unit sia completa e priva di danni 3 Precauzioni per l installazione Non brasare se l unit di condensazione sotto pressione No...

Страница 101: ...e inversa di un compressore a 3 fasi pu essere rilevata se si osserva uno dei se guenti fenomeni il compressore non si avvia non in grado di pressurizzarsi sufficientemente il livello di rumorosit ecc...

Страница 102: ...N1 C3 A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 17 12 13 model 02 06 14 RH CC RCU 114X7084 114X7083 114X7080 OP LSHM026AJW05G OP LSHM034AJW05G OP MSHM018SCW05G OP MSHM026AJW05G OP MSHM0...

Страница 103: ...49499 u249499 2 4 3 BN BN BN A1 A2 K1 MG73BF SM500 16 18 15 L1 L2 L3 P N 26 28 25 A1 S1 21 22 K1 5 6 BN P 1 2 PE B1 BN 7 BU BN BN 8 P P B C A D PE B2 PE X1 F2 CC RCU OP MSUM068MLW05G OP MSUM080MLW05G...

Страница 104: ...xA 5 6 3 4 1 2 F2 BK BU BN BN PE X1 M 1 M2 S1 BK 2 1 E1 BU BK BN P 1 2 PE B1 BU BN PE X1 P P B C A D PE B2 2 4 3 BN BN BN 1 N2 N1 5 6 BN 7 BN 8 21 22 K1 A1 A2 K1 BN BK GY BU PE X1 380 400V3N 50Hz L1 L...

Страница 105: ...MLW05E OP MSUM099MLW05E OP MSUM108MLW05E 16 06 14 Commercial Compressors 118R0160 wiring diagram Schaltplan plan de circuits BK BU BN WH WH 1 M GNYE M2 3A 1 2 F3 95 96 97 98 1 2 3 4 5 6 K1 BK GY BN M...

Страница 106: ...FRCC EI 026 A5 ML Danfoss Commercial Compressors 09 14 106 Instructions...

Страница 107: ...FRCC EI 026 A5 ML Danfoss Commercial Compressors 09 14 107 Instructions...

Страница 108: ...der provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trade marks in this material are property of the respective companies...

Отзывы: