User Guide
|
MCX-RTU Rooftop
RS8KE102 | 20
© Danfoss | ADAP-KOOL® | 2018.11
HRC
Parameters >
Heat Reclaim
Function
Default
Units
Rb1
HR1 PreDelay
Heat Reclaim 1 Pre Delay (0-240)
240
m
Ra1
HR1 PostDelay
Heat Reclaim 1 Post Delay (0-240)
240
m
Rt2
HR2 Target
Heat Reclaim 2 Target Temperature (10.0-
40.0°C)
22.2
°C/°F
Rb2
HR2 PreDelay
Heat Reclaim 2 Pre Delay (0-240)
240
m
Ra2
HR2 PostDelay
Heat Reclaim 2 Post Delay (0-240)
240
m
Rt3
HR3 Target
Heat Reclaim 3 Target Temperature (10.0-
40.0°C)
20.0
°C/°F
Rb3
HR3 PreDelay
Heat Reclaim 3 Pre Delay (0-240)
240
m
Ra3
HR3 PostDelay
Heat Reclaim 3 Post Delay (0-240)
240
m
Rt4
HR4 Target
Heat Reclaim 4 Target Temperature (10.0-
40.0°C)
19.4
°C/°F
Rb4
HR4 PreDelay
Heat Reclaim 4 Pre Delay (0-240)
240
m
Ra4
HR4 PostDelay
Heat Reclaim 4 Post Delay (0-240)
240
m
HRr
HR Range +/-
Heat Reclaim Range +/- (0.0-10.0K)
0.2
K/F
HR1
HR Ambient
Lockout
Heat Reclaim Mode Ambient Lockout (0.0-
85.0°C)
37.8
°C/°F
HR2
HR Lockout
Range +/-
Heat Reclaim Mode Ambient Lockout
Range +/- (0.0-10.0K)
1.1
K/F
RnS
HR Night Set-
back
Heat Reclaim Mode Night Setback (0.0-
30.0K)
2.8
K/F
HRs
HR SupplyAir
Heat Reclaim Mode Supply Air Target for
VS Fan (0.0-100.0°C)
30.6
°C/°F
Rm1
HR Min Fan
Speed
Heat Reclaim Mode Min Fan Speed (0.0-
100.0)
50.0
%
Rm2
HR Max Fan
Speed
Heat Reclaim Mode Max Fan Speed (0.0-
100.0)
75.0
%
HET
Parameters >
Aux Heat
Function
Default
Units
Ht1
HT1 Target
Aux Heat 1 Target Temperature (10.0-
40.0°C)
20.8
°C/°F
Hb1
HT1 PreDelay
Aux Heat 1 Pre Delay (0-240)
240
m
Ha1
HT1 PostDelay
Aux Heat 1 Post Delay (0-240)
240
m
Ht2
HT2 Target
Aux Heat 2 Target Temperature (10.0-
40.0°C)
20.3
°C/°F
Hb2
HT2 PreDelay
Aux Heat 2 Pre Delay (0-240)
240
m
Ha2
HT2 PostDelay
Aux Heat 2 Post Delay (0-240)
240
m
Ht3
HT3 Target
Aux Heat 3 Target Temperature (10.0-
40.0°C)
18.9
°C/°F
Hb3
HT3 PreDelay
Aux Heat 3 Pre Delay (0-240)
240
m
Ha3
HT3 PostDelay
Aux Heat 3 Post Delay (0-240)
240
m
Ht4
HT4 Target
Aux Heat 4 Target Temperature (10.0-
40.0°C)
18.3
°C/°F
Hb4
HT4 PreDelay
Aux Heat 4 Pre Delay (0-240)
240
m
Ha4
HT4 PostDelay
Aux Heat 4 Post Delay (0-240)
240
m
HTr
HT Range +/-
Aux Heat Range +/- (0.0-10.0K)
0.5
K/F
HT1
HT Ambient
Lockout
Aux Heat Mode Ambient Lockout (0.0-
85.0°C)
37.8
°C/°F
HT2
HT Lockout
Range +/-
Aux Heat Mode Ambient Lockout Range
+/- (0.0-10.0K)
1.1
K/F