User Guide
|
MCX-RTU Rooftop
RS8KE102 | 34
© Danfoss | ADAP-KOOL® | 2018.11
IO List
I/O CONFIGURATION
AI
ANALOG INPUTS
Min
Max
Type
1
Zone Temperature
-30.0°C
170.0°C
PT1000
2
Supply Air
-30.0°C
170.0°C
PT1000
3
Return Air
-30.0°C
170.0°C
PT1000
4
Zone RH
0.0 %
100.0 %
0-5 V
5
Outdoor RH
0.0 %
100.0 %
0-5 V
6
Indoor CO2
0 ppm
2000 ppm
0-5 V
7
Building Pressure
0.0
100.0
0-5 V
8
Mixed Air
-30.0°C
170.0°C
PT1000
9
Outdoor Air
-30.0°C
170.0°C
PT1000
10
Light Level
-1.00
1.00
00-5 V
11
Compr 1 Press
0.0bar
34.5 bar
0-5 V
12
Compr 2 Press
0.0 bar
34.5 bar
0-5 V
13
Compr 3 Press
0.0 bar
34.5 bar
0-5 V
14
Compr 4 Press
0.0 bar
34.5 bar
0-5 V
15
Aux AI 1 (Located on Expansion Module)
0.0
200.0
0-5 V
16
Aux AI 2 (Located on Expansion Module)
0.0
200.0
0-5 V
17
Aux AI 3 (Located on Expansion Module)
0.0
200.0
0-5 V
18
Aux AI 4 (Located on Expansion Module)
0.0
200.0
0-5 V
19
Aux AI 5 (Located on Expansion Module)
0.0
200.0
0-5 V
20
Aux AI 6 (Located on Expansion Module)
0.0
200.0
0-5 V
21
Aux AI 7 (Located on Expansion Module)
0.0
200.0
0-5 V
22
Outdoor CO2 (Located on Expansion Module)
0
2000
0-5 V
DI
DIGITAL INPUTS
Min
Max
Type
1
Fan Proof
0
1
N.O.
2
Phase Loss
0
1
N.C.
3
Shutdown 1
0
1
N.O.
4
Shutdown 2
0
1
N.O.
5
Fan Drive Fault
0
1
N.O.
6
Compr1 Drive Fault
0
1
N.O.
7
Compr2 Drive Fault
0
1
N.O.
8
Compr3 Drive Fault
0
1
N.O.
9
Compr4 Drive Fault
0
1
N.O.
10
Filter Clogged Fault
0
1
N.O.
11
Damper Override
0
1
N.O.
12
Title24 Override
0
1
N.O.
13
Schedule Override
0
1
N.O.
14
Cool 1 Proof
0
1
N.O.
15
Cool 2 Proof
0
1
N.O.
16
Cool 3 Proof
0
1
N.O.