User Guide
|
MCX-RTU Rooftop
RS8KE102 | 16
© Danfoss | ADAP-KOOL® | 2018.11
OPT
Setup Options
Function
Default
Units
C32
Compr3 AO Type
Select AO Range for Cool3(0-5,1-5,0-10,2-
10,Custom)
1-5
vdc
C33
Compr4 AO Type
Select AO Range for Cool4(0-5,1-5,0-10,2-
10,Custom)
1-5
vdc
C34
Damper AO Type
Select AO Range for Damper(0-5,1-5,0-10,2-
10,Custom)
2-10
vdc
C35
Custom AO Min
Set Min VDC for Custom AO(0.0-10.0vdc)
1.5
vdc
C36
Custom AO Max
Set Max VDC for Custom AO(0.0-10.0vdc)
5.0
vdc
C37
Ovrd Night Set-
back
If Yes, then Night Setback can be
overridden(Yes/No)
No
C42
Invert Fan AO
Invert Fan AO(Normal/Invert)
Normal
C43
Invert Compr 1 AO
Invert Compr1 AO(Normal/Invert)
Normal
C44
Invert Compr 2 AO
Invert Compr2 AO(Normal/Invert)
Normal
C45
Invert Compr
3 AO
Invert Compr3 AO(Normal/Invert)
Normal
C46
Invert Compr
4 AO
Invert Compr4 AO(Normal/Invert)
Normal
C47
Invert Damper
AO
Invert Damper AO(Normal/Invert)
Normal
C48
Zone RH
Select Sensor for Zone
RH(Disable,Local,GlobalRH1-5,Avg)
Local
C49
Zone CO2
Select Sensor for Zone CO2(Disable,Local,
GlobalCO2-1-5)
Local
C50
Outdoor Temp
Select Sensor for Outdoor
Temp(Disable,Local,Global)
Local
C51
Outdoor RH
Select Sensor for Outdoor
RH(Disable,Local,Global)
Local
C52
Outdoor CO2
Select Sensor for Outdoor
CO2(Disable,Local,Global)
Disable
C40
Supply Air
Sensor
Select Sensor for Supply Air(Disable,Local)
Local
C39
Return Air
Sensor
Select Sensor for Return Air(Disable, Local)
Local
C38
Mixed Air Sensor Select Sensor for Mixed Air(Disable, Local)
Local
C41
Zone Cntl Sensor Zone Control uses the Zone or Return Air
sensor
Zone
C53
HT/CL Ctrl Mode
Select HT/CL Ctrl Mode(Standard/Supply
Air)
Standard
C54
Fan VLT Modbus
Enable Fan VLT Modbus Control(Disable/
Enable)
Disable
C55
HTReset AO Type Select AO Range for HTReset AO(0-5,1-5,0-
10,2-10,Custom)
0-10
C56
Invert HTReset
AO
Invert HTReset AO(Normal/Invert)
C57
Zone Control
Zone Sensor
Config(Single;Average;High;Low)
Single
C58
BldPress Sensor
Select Sensor for Building Pressure
Control(Disable;Local;Global)
Local
C59
Condenser Cntl
Enable AO Condenser Control(No/Yes)
No
Содержание MCX-RTU
Страница 1: ...MCX RTU Rooftop unit User Guide ...