3 How to Install
3.1 How to Get Started
Please consult the
VLT AutomationDrive Operating
Instructions
for correct installation of VLT AutomationDrive,
these instructions cover installation of MCO 305.
3.1.1 Initialisation to Default Settings
Initialize the frequency converter to default setting in two
ways:
Recommended initialisation (via
14-22 Operation Mode
)
1.
Select
14-22 Operation Mode
2.
Press [OK]
3.
Select “Initialization”
4.
Press [OK]
5.
Cut off the mains supply and wait until the
displays turns off.
6.
Reconnect the mains supply – the frequency
converter is now reset.
NOTE
MCO 305 programs and arrays are not affected.
14-22 Operation Mode
initialises all except:
14-50 RFI Filter
8-30 Protocol
8-31 Address
8-32 FC Port Baud Rate
8-35 Minimum Response Delay
8-36 Max Response Delay
8-37 Max Inter-Char Delay
15-00 - 15-05 Operating Data
15-20 - 15-22 Historic log
15-30 - 15-32 Fault log
33-90 X62 MCO CAN node ID
33-91 X62 MCO CAN baud rate
Manual initialisation
1.
Disconnect from mains and wait until the display
turns off.
2.
Press [Status] – [Main Menu] – [OK] at the same
time:
3.
Reconnect mains supply while pressing the keys.
4.
Release the keys after 5 sec.
5.
The frequency converter is now programmed
according to default settings.
NOTE
When carrying out manual initialization, serial communi-
cation and fault log settings are reset. All MCO 305
programs and arrays are deleted!
This method initializes all except:
15-00 Operating Hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
How to Install
MCO 305 Operating Instructions
MG.33.K3.02 - VLT
®
is a registered Danfoss trademark
7
3
3