Error 160
Internal interrupt error
Interrupt happened, but interrupt address is no longer
valid. (Internal error which should not ever happen.)

Error 162
Memory error
Error in verifying: After saving something in the EPROM (a
program or parameters) an error was detected during
verification.
Delete the EPROM with a 3-finger reset and try to save the
program or parameters again.
In Stand-alone Mode you can use 

 Controller 

 Memory

 Delete EPROM instead of the 3-finger reset.

If this is not successful please call the technical service
department.

Error 170
Too many DIM arrays
The definition of an array in a DIM command does not
correspond to an already existing array in the MCO 305.
Cause might be that the fields are from older SYNCPOS/
APOSS programs. The current program has other
definitions.
Either adapt the APOSS program to the correct array size
or delete the old arrays, e.g. in Stand-alone Mode with
Controller 

 Memory 

 Delete EPROM or use the

command Controller 

 Reset 

 Arrays.

NOTE

Remember to follow the recommendations concerning
saving programs and parameters before deleting the
EPROM.

Error 171
Array too small
An attempt was made to describe an array element that is
located outside of the defined array limits. Cause might be
an error in the APOSS program. Array sizing does not
agree with the space required (e.g. due to an incorrectly
programmed loop).
Or the array is too small for the number of test drives
triggered by TESTSTART.
Check loop variables.

Error 175
Out of array memory
There is no more memory space for the new array defined
by a DIM command.

Error 176
Array size wrong
The size in a DIM command does not correspond to the
size of the existing array. Either delete existing arrays or
correct the DIM command.

Error 179
Waitndx timeout
Timeout while waiting for index: The command WAITNDX
was executed and the timeout listed was exceeded.

The timeout is probably too short or the index impulse
could not found (see also Error 109).

Error 183
Invalid argument
This command error signals that an TESTSTOP command
contained an invalid argument.
Or a compiler error in other commands like invalid
parameter value, format, or range. (Internal error, which
should not occurred.)

Error 184
Too many ONTIME
Too many interrupts (ON TIME or ON PERIOD commands)
were used within the program.
A maximum of 12 of these ON TIME and/or ON PERIOD
commands are allowed within one program.

Error 187
Out of memory
Not enough memory for variables: When the APOSS
program is started the space for the necessary variables is
reserved dynamically. This space is now no longer
available.
You may have selected a maximum number of variables
which is too high. Reduce the maximum number in
Settings 

 Compiler (Standard = 92).

Or the memory available is occupied with programs or
arrays. Delete the programs with Controller 

 Programs 

Delete all
or delete both the programs and arrays, i.e. by deleting
the entire memory with Controller 

 Memory 

 Delete

EPROM..

Remember to follow the recommendations concerning
saving programs and parameters before deleting the
EEPROM.

Error 188
CAN guarding error
A guarding error happened. This happens either when
requesting guarding messages from slaves or if guarding is
done by a master. In both cases it is caused by a time out.
In the additional error information it could be seen if it
was an error caused by a master guarding (-34).
The additional error information (see Error History) is used
as it is shown in error 102.

Error 189
CAN send or receive error.
This error is a send or receive error caused by a SDOREAD
or SDOWRITE, by a CANIN or CANOUT or by an IN or OUT
command using CAN I/O.
The optional error information either contains the CAN ID
which produced the error (IN, OUT, SDO, …) or the object
number (handle) which was used (CANIN, CANOUT).

Error 190

Troubleshooting

MCO 305 Operating Instructions

32

MG.33.K3.02 - VLT

®

 is a registered Danfoss trademark

7

7

Содержание MCO 305

Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions Programmable Motion Controller MCO 305...

Страница 2: ...4 Basic MCO Parameter Settings 14 3 4 1 Setting of Encoder Parameters 14 3 4 2 Setting of parameters for CANopen feedback encoder 14 3 4 3 Setting of parameters for CANopen Master encoder 15 3 4 4 Se...

Страница 3: ...4 5 1 Download Application Program and Configuration 24 5 2 Backup and Restore 24 5 3 How to Connect and Run Multiple Frequency Converters 25 6 General Specifications 26 6 1 Protection and Features 26...

Страница 4: ...ical literature is also available online at www danfoss com drives 1 2 Symbols and Conventions Symbols The following symbols are used in this manual WARNING Indicates a potentially hazardous situation...

Страница 5: ...ntrol Option MCO Motion Control Tool MCT Parameter par Protective Extra Low Voltage PELV Position Control Loop PID Pulses per Revolution PPR Quad counts qc Revolutions per Minute RPM Second sec Switch...

Страница 6: ...ng to national and local regulations Motor overload protection is not included in the default settings To add this function set par 1 90 Motor thermal protection to value ETR trip or ETR warning For t...

Страница 7: ...be followed The information and instructions of Operating Instructions are not sufficient for a correct and safe use of the Safe Stop functionality 2 6 General Warning WARNING Touching the electrical...

Страница 8: ...ocol 8 31 Address 8 32 FC Port Baud Rate 8 35 Minimum Response Delay 8 36 Max Response Delay 8 37 Max Inter Char Delay 15 00 15 05 Operating Data 15 20 15 22 Historic log 15 30 15 32 Fault log 33 90 X...

Страница 9: ...to be used in slot C0 but can be combined with another option in slot C1 Mounting kit depending on frame Order no Bookstyle A2 and A3 40 mm for one C option 130B7530 A2 and A3 60 mm for C0 C1 option...

Страница 10: ...Illustration 3 2 Compact A5 B except B3 C D E F How to Install MCO 305 Operating Instructions MG 33 K3 02 VLT is a registered Danfoss trademark 9 3 3...

Страница 11: ...debug terminals RS485 are located on the top of the c option cover If these connections are used cut out the plastic parts above the connectors and mount the cable relief 130BA248 11 Illustration 3 3...

Страница 12: ...Name Encoder 2 Feedback X55 1 24V Supply 2 8V Supply 3 5V Supply 4 GND 5 A 6 A not 7 B 8 B not 9 Z Clock 10 Z not Clock not 11 DATA 12 DATA not Terminal block Terminal number Descriptive Name Encoder...

Страница 13: ...tions Examples 5V incremental encoder 1 2 3 12 130BA163 10 7 5 4 6 8 9 10 11 24V 8V 5V GND A A B B Z Z D D Illustration 3 6 5V Incremental Encoder RS 422 Supplied by MCO 305 Illustration 3 7 5V Increm...

Страница 14: ...rfaces are interconnected termination must be on 32 40 Encoder Termination ON at both ends of the bus Termination must be off 32 40 Encoder Termination OFF in all other MCOs How to Install MCO 305 Ope...

Страница 15: ...s must always be checked and if necessary adjusted Depending on the requirements of the application it might be necessary to adjust other parameters as well For the other parameters use the default se...

Страница 16: ...this value 3 4 5 Setting of Home Parameters Homing is not necessary in standard synchronization applications and applications using an absolute encoder When using an incremental encoder the controlle...

Страница 17: ...ons by means of the test program Select the file Enc S m via the MCT 10 APOSS and with that the file is opened automatically 3 5 1 Execute the Encoder Test Program In the Development menu click on Exe...

Страница 18: ...al Signal Type and 32 02 Absolute Protocol Encoder resolution 32 01 Incremental Resolution or 32 03 Absolute Resolution Encoder velocity par 19 00 and Motion type par 19 00 These parameters must thus...

Страница 19: ...or immediately with the EMERGENCY STOP button if it vibrates heavily or sets off uncontrolled the motor sets off uncontrolled but the encoder test previously was successful then decrease 32 60 Proport...

Страница 20: ...s you can directly influence to what degree and how quickly a deviation from a theoretical set path as specified by the setpoint series should be counteracted The following behavior indicate that the...

Страница 21: ...d accurate response to changes in the setpoint reference 2 A closed loop PID control The PID controller monitors the difference between the actual position and the setpoint position Based on this info...

Страница 22: ...al speed reference is maxed out for long periods of time This feature is also very helpful in applications where the power to the motor is turned off and on while the option card is controlling the VL...

Страница 23: ...lution in 32 00 Incremental Signal Type and 32 01 Incremental Resolution and 32 81 Shortest Ramp If these settings change again at a later point the controller may need optimizing again Par Typical Se...

Страница 24: ...ood and increasing overshoot and oscillations in the system which is bad If you are using the Integral part of the PID controller remember to reduce the 32 63 Limit Value for Integral Sum as much as p...

Страница 25: ...NOTE MCO 305 programs can only be read out when they have be downloaded including source code Use the following steps to back up parameters and data by PC 1 Go on line with the drive via the Network f...

Страница 26: ...tings menu allows selecting the interface Run programs in several frequency converters If you want to load the program into several controllers link the program with the corresponding VLT AutomationDr...

Страница 27: ...e on input 28V DC Table 6 2 Digital Inputs 1 Selected in parameter 5 00 Digital I O mode The digital inputs are galvanic isolated from the internal electronics and can be sourced by an external 24V po...

Страница 28: ...1 more with repeater Maximum cable length 400m Table 6 9 Encoder Output Number of supply voltages 3 Terminal block X55 and X56 Terminal number 1 2 3 4 24V max load 250mA1 8V max load 250mA12 5V max lo...

Страница 29: ...more SDO chn Number of SDO channels exceeded 125 HW end limit Limit switch activated 149 Too many inter Too many interrupt functions 150 No ext 24V External supply is missing 151 Too many gosub Too ma...

Страница 30: ...RD_ERROR_MODULE_NOT_RESPONSE 103 GUARD_ERROR_NO_MODULE 104 Error 103 Illegal axis number An attempt has been made to find an axis which does not exist in the controller Check to see if the program axi...

Страница 31: ...utputs NOTE Using virtual inputs as limit switches is dangerous because it eliminates the direct connection between the limit switch and the controller That may introduce a time delay or other failure...

Страница 32: ...the opposite direction But if you try to move in the wrong direction then the error 198 occurs Limit switches and reference switches allow the usage of any input That means not only 1 8 are supported...

Страница 33: ...meout listed was exceeded The timeout is probably too short or the index impulse could not found see also Error 109 Error 183 Invalid argument This command error signals that an TESTSTOP command conta...

Страница 34: ...t circuit in accordance with the displayed LED An error will be indicated even if no encoder is connected Error 193 Stack overflow Internal error Dynamic stack overflow caused by too many local variab...

Страница 35: ...er recognizes that the data in the array area is formatted incorrectly In order to be able to save a file the following conditions must be fulfilled Identical software versions same configuration e g...

Страница 36: ...nt16 4 Integer 32 Int32 5 Unsigned 8 Uint8 6 Unsigned 16 Uint16 7 Unsigned 32 Uint32 8 1 1 Application Parameters Parameter Group 19 Par No Parameter name Parameter description Default setting Changes...

Страница 37: ...tion TRUE 1 set up Uint8 32 11 POSFACT_N User Unit Denominator 1 TRUE 1 set up Uint32 32 12 POSFACT_Z User Unit Numerator 1 TRUE 1 set up Uint32 32 13 ENCCONTROL Enc 2 Control 0 TRUE 2 set ups Uint8 3...

Страница 38: ...TRUE 1 set up Uint32 32 68 REVERS Reverse Behavior for Slave 0 Reversing TRUE 1 set up Uint8 32 69 TIMER Sampling Time for PID control 1 ms TRUE 1 set up Uint16 32 70 PROFTIME Scan Time for Profile Ge...

Страница 39: ...e M S 1 TRUE 1 set up Int32 33 12 SYNCPOSOFFS Position Offset for Synchronization 0 qc TRUE 1 set up Int32 33 13 SYNC ACCURACY Accuracy Window for Position Synchro nization 1000 qc TRUE 1 set up Int32...

Страница 40: ...End Limit Active 0 Inactive TRUE 1 set up Uint8 33 44 SWPOSLIMACT Positive Software End Limit Active 0 Inactive TRUE 1 set up Uint8 33 45 TESTTIM Time in Target Window 0 ms TRUE 1 set up Uint8 33 46 T...

Страница 41: ...8 33 68 O_FUNCTION_6 Terminal X59 6 Digital Output 0 no function TRUE 1 set up Uint8 33 69 O_FUNCTION_7 Terminal X59 7 Digital Output 0 no function TRUE 1 set up Uint8 33 70 O_FUNCTION_8 Terminal X59...

Страница 42: ...27 PCD 7 Read from MCO 1 set up Uint16 34 28 PCD 8 Read from MCO 1 set up Uint16 34 29 PCD 9 Read from MCO 1 set up Uint16 34 30 PCD 10 Read from MCO 1 set up Uint16 34 4 Inputs Outputs 34 40 Digital...

Страница 43: ...pply 27 Ending The Encoder Check 16 Execute The Encoder Test Program 16 F FFACC 21 FFVEL 21 G General Specifications 26 Warning 6 H High Voltage Warning 5 How To Connect And Run Multiple Frequency Con...

Страница 44: ...ware Version 5 Stationary Precision Is Required 23 Supply Voltage Overview 27 Symbols 3 T Technical Data 26 Terminal Overview 11 Test Program 18 The Maximum Acceleration Is Not Achieved 23 Motor Doesn...

Страница 45: ...www danfoss com drives MG33K302 130R0086 MG33K302 Rev 2011 05 24...

Отзывы: