6 General Specifications
6.1 Protection and Features
-
All inputs, outputs and supply voltages are
protected against short circuit.
-
All inputs, outputs and supply voltages are
galvanic isolated from high voltages such as
mains supply and motor voltage (PELV).
-
Encoder signals are monitored during operation
and standstill.
-
Customer specific application programs can be
copy protected.
-
All MCO 305 parameters including user defined
application parameters are accessible via the VLT
AutomationDrive LCP.
-
MCO 305 can be combined with other VLT
AutomationDrive options e.g. PROFIBUS and
DeviceNet interface.
-
All digital inputs and outputs are galvanic
isolated from the internal electronics and can be
sourced from an external 24V power supply.
6.2 Technical Data
Type
Plug connectors with screw
terminals.
Maximum cross section, rigid
wire
1.5mm
2
/ AWG 16
Maximum cross section, flexible
wire
1.5mm
2
/ AWG 16
Maximum cross section, wire
with enclosed core
1.5mm
2
/ AWG 16
Minimum cross section
0.08mm
2
/ AWG 28
Table 6.1 Connection Terminals
Number of programmable digital
inputs
10
Terminal block
X57
Terminal number
1, 2, 3, 4, 5, 6, 7, 8, 9, 10
Logic
PNP or NPN
¹
Voltage level
0 - 24V DC
Voltage level, logic.0. PNP
< 5V DC
Voltage level, logic.1. PNP
> 10V DC
Voltage level, logic.0. NPN
> 19V DC
Voltage level, logic.1. NPN
< 14V DC
Maximum voltage on input
28V DC
Table 6.2 Digital Inputs
1) Selected in parameter 5-00 Digital I/O mode. The digital
inputs are galvanic isolated from the internal electronics and
can be sourced by an external 24V power supply.
Number of programmable digital outputs
8 (6)
1
Terminal block
X59
Terminal number
1
1
, 2
1
, 3, 4, 5, 6, 7, 8
Driver type
Push/Pull
Logic
PNP or NPN
2
Voltage level
0 - 24V DC
Max. output current (sink or source) with
internal power supply (total )
40mA
Max. output current (sink or source) with
external power supply (per output)
100mA
Table 6.3 Digital Outputs
1) Terminals X59-1 and X59-2 can be programmed as
input,
33-60 Terminal X59/1 and X59/2 Mode
.
2) Selected in
5-00 Digital I/O Mode
.
Number of digital outputs which can be used as
digital inputs
2
1
Terminal block
X59
Terminal number
1, 2
Logic
PNP or NPN
2
Voltage level
0 - 24V DC
Voltage level, logic.0. PNP
< 10V DC
Voltage level, logic.1. PNP
> 17V DC
Voltage level, logic.0. NPN
> 13V DC
Voltage level, logic.1. NPN
< 6V DC
Maximum voltage on input
28V DC
Table 6.4 Combined Digital Inputs/Outputs
1) Terminals X59-1 and X59-2 can be programmed as
input,
33-60 Terminal X59/1 and X59/2 Mode
.
2) Selected in
5-00 Digital I/O Mode
.
Terminal block
X58
Terminal number
1, 2
Maximum load
65mA
Table 6.5 24V DC Supply Output
The internal 24V power supply can be disconnected via
parameter 33-85, an external 24V power supply must then
be connected to X58-1 and X58-2.
General Specifications
MCO 305 Operating Instructions
26
MG.33.K3.02 - VLT
®
is a registered Danfoss trademark
6