42-6* Safe Fieldbus
Parameter
Options/Valid
range
Default value
Description
Conversion
index
Data type
42-60 Telegram
Selection
[0] None
[1] PROFIsafe Std.
Tel. 30
[0] None
Select the safe fieldbus type and the telegram
standard for the Safety Option MCB 152.
[0] None
- the safe fieldbus communication is
disabled.
[1] PROFIsafe Std. Tel. 30
- the PROFIsafe
communication is enabled. The telegram
standard is
PROFIsafe Std. Tel. 30
. For more
information, see
chapter 6.1.1 Telegram Configu-
If fieldbus communication is enabled, and if
the reset signal comes via the fieldbus, this
parameter also defines whether the frequency
converter is also reset or only the safety option
is reset.
-
u_int8
42-61 Destination
Address
1-65535
1
Enter the safe fieldbus destination address
within the safe network. This address must be
unique in the network where PROFIsafe
operates. The address should match the
address specified in the PLC software.
-
u_int16
Table 7.3 42-6* Safe Fieldbus
Parameter Set-up
Safety Option MCB 152