1.4 Front View
MCB 152
Safe Option
PROFIsafe
SW. ver. xx.xx
Option B
130B9860
LED:
1
1
2
3
4
5
6
7
8
9 10 11 12
2
3
4
Y33/
DI1 A
GND
GND
GND
GND
DI1 B
NC
NC
24 V
S 37
DI2 A
DI2 B
130BE100.10
Illustration 1.2 Safety Option MCB 152 Front View.
1.5 Hardware and Software Requirements
The following software versions are required as a minimum
for using Safety Option MCB 152:
•
LCP software version 7.0.
•
FC 302 firmware version 7.26.
•
PROFINET software version 3.00.
•
MCT 10 Set-up Software version 3.23. A license
key is required to use the full set of features.
1.5.1 Compatibility
The safety option is compatible with all VLT
®
AutomationDrive FC 302 frequency converters in the
power range from 0.37 kW-75 kW. Compliance to higher
power ranges is pending. Contact the local supplier for
latest information.
1.6 Additional Resources
The following documentation on safety option installation
and configuration is available:
•
MCT 10 Set-up Software Operating Instructions
describe how to configure the safety option.
•
VLT
®
AutomationDrive FC 301/FC 302 Operating
Instructions
describe the frequency converter.
•
VLT
®
AutomationDrive PROFINET MCA 120 Instal-
lation Guide
describes how to install the
PROFINET option.
•
VLT
®
Frequency Converters Safe Torque Off
Operating Instructions
describe the use of
DanfossVLT
®
frequency converters in functional
safety applications.
Supplementary publications and manuals are available
from Danfoss. See
vlt-drives.danfoss.com/Support/Technical-
for listings.
1.7 Document Version
This manual is regularly reviewed and updated. All
suggestions for improvement are welcome.
shows
the document version.
Edition
Remarks
MG37F1xx
New document
Table 1.1 Document Version
1.8 Compliance and Certifications
The safety option is certified for use in safety applications
up to and including
•
SIL 2 according to EN IEC 61508 and EN IEC
62061.
•
Performance Level PL d.
•
Category 3 according to EN ISO 13849-1.
Safety requirements are based on the standards valid at
the time of certification. The IFA (Institute for Occupational
Safety & Health) has approved the safety option for use in
safety-related applications where the de-energised state is
considered to be the safe state. All of the examples related
to I/O included in this manual are based on achieving de-
energisation as the safe state.
Approvals
Safety Option MCB 152 is tested and certified by PNO.
1.9 Disposal
Do not dispose of equipment containing
electrical components together with
domestic waste.
Collect it separately in accordance with
local and currently valid legislation.
Introduction
Operating Instructions
MG37F102
Danfoss A/S © 10/2014 All rights reserved.
5
1