NOTICE
Any misuse of the password may lead to safety issues.
No password is required to access the commissioning
parameters of the safety option. The password is required
when writing the parameters to the option via the
Write to
Drive
feature.
If a user forgets the password, the safety option can be
reset using MCT 10. To reset the safety option:
•
In MCT 10 Set-up Software, click
Administration
.
•
In the
Reset
tab, select
Yes, I want to reset Safety
Option Configuration in the drive
, enter the default
password and click
Reset
.
The password must consist of 8 characters and is case-
sensitive. Alphanumeric characters and symbols are valid
for the password.
Use the
Change Password
menu item to change the safety
option parameter password.
6.2 Status over Fieldbus
The safety option status can be retrieved as part of the
status word. Its behaviour changes based on the selected
control word profile.
Select
[91] Safe Opt. Reset. req
and
[90] Safe Function active
in
8-13 Configurable Status Word STW
to achieve the
following:
•
Indicate that a reset of the safety option is
required. These signals are also available as DO
outputs.
•
Indicate that a safety function is active.
6.2.1 Safety Option Reset via Control Word
To reset the safety option using the control word, select
[3] Safe Option Reset
in
8-14 Configurable Control Word CTW
.
This option is available only in bits 12-15 of
8-14 Config-
urable Control Word CTW
.
6.2.2 Safety Option Status
42-80 Safe Option Status
indicates the actual status (active
safe function, any requests and the error number) of the
safety option and is accessible as a read only parameter
from any interface and is configurable as a read process
data for a specific fieldbus.
NOTICE
42-80 Safe Option Status
shows only the active safety
function.
Bit
Description
0
Normal_up
1
PUST
2
STO active
3-6
Not applicable
7
Reserved for further SF
8
Safe output status
9
For internal use only. Safety option uses this bit
to reset all safety parameters to default values.
10
Safe fieldbus acknowledge request
11
Int_fail
12
Reset required
13
Pending fail safe state
14
Ext_fail
15
Safe function pending
16
General reset
17
Customisation_confirmed
18
Customisation_aborted
19
Customisation_requested
20
Not applicable
21
PUST warning
22
DI_1_offline_warning
23
DI_2_offline_warning
24
Error code
25
Error code
26
Error code
27
Error code
28
Error code
29
Error code
30
Error code
31
Error code
Table 6.3 Status Bits for Safety Option Status
Bit 00, Safety function deactive/active
Bit 00 = 0, Safety function, fail safe reaction is active or
pending or warning is active
Bit 00 = 1, Normal operation.
Bit 01, Power up self test
Bit 01 = 1, Safety option is in PUST state.
Bit 02, Safe Torque Off
Bit 02 = 0, Safe Torque Off is not active.
Bit 02 = 1, Safe Torque Off is active.
Bit 07
Reserved for future safety functions.
Bit 08
Bit 08 = 0, Safe output at 24 V.
Bit 08 = 1, Safe output at 0 V.
Bit 10
Bit 10 = 0, No operator acknowledgement requested.
Bit 10 = 1, Operator acknowledgement from safe PLC
requested.
Bit 11, Internal error
Bit 11 = 0, No internal error is active.
Configuring the Safety Opti...
Operating Instructions
MG37F102
Danfoss A/S © 10/2014 All rights reserved.