5 Commissioning
5.1 Before Commissioning
When commissioning/recommissioning:
•
Secure the site in accordance with regulations
(barrier, warnings, signs, etc.). Only qualified
personnel is allowed to commission/
recommission the system.
•
Refer to the guidelines, information and specifi-
cations stated in the operating instructions of the
relevant control system.
•
Make sure that no personal injury and/or material
damage can occur, even if the machine moves
unintentionally.
Refer to
VLT
®
AutomationDrive FC 301/FC 302 Operating
Instructions
for further information on the frequency
converter.
Refer to
MCT 10 Set-up Software Operating Instructions
for
further information on the Safe Plug-in.
5.2 Commissioning Requirements
The following components are required to perform the
necessary steps for the commissioning of the safety option.
•
MCT 10 Set-up Software (licensed version).
•
A connection between the PC and the control
card of the frequency converter.
Follow these general steps to perform the commissioning:
1.
Configure the safety option in MCT 10 Set-up
Software with the Safe plug-in. Configure only
the safety functions that are connected to the
safety option inputs.
2.
Ensure that the serial number and the ordering
number of the safety option on the frequency
converter match the serial number in
15-63 Option Serial No
and the ordering number
in
15-62 Option Ordering No
. Use array index 1 to
see the number related to the safety option.
3.
Ensure that the frequency converter is ready for
commissioning (see
VLT
®
AutomationDrive FC
301/FC 302 Operating Instructions
)
NOTICE
If RS485 is used, set the protocol for serial communi-
cation to
[1] FCMC
in
8-30 Protocol
(only accessible
through the LCP). Ensure the correct settings of the
communication parameters (baud rate, etc.).
5.3 Commissioning Procedure
5.3.1 Power-up/Self-test
When the power is applied, the frequency converter
automatically detects the safety option. During the start-
up, the safety option performs a self-test. If the safety
option is in blank initial state, the message
Safe Opt.
initialized - SO RESET requested
or
SO in Self-test
appears on
the LCP. After the self-test, the LEDs light up according to
the device status.
5.3.2 Commissioning in Online Mode
This section describes the example of the safety option
commissioning procedure with MCT 10 Set-up Software. In
this example:
•
A VLT
®
PROFINET MCA 120 option is installed in
the frequency converter and PROFIsafe communi-
cation is required for the application.
To commission the safety option:
1.
In MCT 10 Set-up Software, establish a
connection between the PC and the frequency
converter.
2.
In MCT 10 Set-up Software, select the
Safe
plug-
in.
130BE071.10
3.
Select
PROFIsafe
in
Safe input
⇒
Safe
Fieldbus
⇒
Telegram Selection
, and enter the
destination address in the
Destination Address
field.
130BE078.10
4.
Select the appropriate safe function for digital
input 1 in the
DI1
group.
130BE079.10
Commissioning
Safety Option MCB 152
16
Danfoss A/S © 10/2014 All rights reserved.
MG37F102