manual switch

1.

2.

1.

Adjustment

NOTE: 

Adjust the tharmostat to settings specified by the 

manufacturer of the controlled equipment. When 

checking thermostat operation, or operating 

the controlled equipment, do not exceed the 

manufacturer’s temperature ratings for the controlled 

equipment or for any of its components.

To avoid inaccurate thermostat operation, do not 

adjust the KPU’s pointers beyond the highest or lowest 

indicator marks on the scale plate. 

Before adjustment loosen the locking screw.

For setting use Universal Refrigeration Wrench or the setting 

knob, if available. Movement of the setting knob is limited 

by the locking screw, which allows only small corrections to 

the settings. Therefore, if the setting knob is to be used for 

adjustments, completely remove the locking screw. After 

adjustment, tighten the locking screw.

Manual switch

Available only on KPU 61 (060L5210) and KPU 62 (060L5207), 

the manual switch is a two-position switch used to shut down 

the refrigeration system. The two positions are:

1.

 AUTO: position for automatic operation. 

2.

 STOP: contacts 1 and 2 are locked in the closed position.

CAUTION:

The manual switch only stops automatic operation, 

and can only be used for service on non-electrical 

parts. Interrupt mains power before servicing 

electrical parts.

Adjustment: thermostat with automatic reset

Scale plate directly indicates High Switching Point  

and  Differential.

Adjustment: thermostat with manual reset

Scale plate directly indicates Low Switching Point, which is  

Cut-Out. There is no pointer for Differential. 

Differential value is fixed and printed on the scale plate.

1. 

Set High Switching Point by 

adjusting range screw. Turn the 

screw clockwise to lower the set 

point.

2.

 Then set Differential by adjusting 

differential screw. Turn the screw 

clockwise to increase Differential.

3. 

Low Switching Point is equal  

to High Switching 

Point less Differential:                                       

LOW = HIGH - DIFFERENTIAL

1. 

Set Cut-Out (Low Switching Point) 

by adjusting range screw. Turn  

the screw clockwise to lower  

the set point.

2.

 High Switching Point (Cut-In) 

equals Low Switching Point  

(Cut-Out) plus Differential:   

CUT IN = CUT OUT + DIFFERENTIAL

IMPORTANT:

The scale plate is only for reference and for more 

precise setting a temperature gauge should be used.

IMPORTANT: 

After installing and adjusting the thermostat, check 

your settings by running the controlled equipment 

several times (at least three times) under normal 

operating conditions.

A:

 Setting knob

B:

 Locking screw

C:

 Range adjusting screw

D:

 Differential adjusting screw

E:

 Cover screw

DKRCC.PI.CD0.A3.22 / 520H8467  

© Danfoss A/S (AC-MC / jmn), 2014-02

Содержание KPU 61

Страница 1: ...61B 060L5204 B 80 man min 1 20 60 5 fixed 2 250 KPU 61B 060L5205 B 200 man min 1 20 60 5 fixed 2 250 KPU 61 060L5210 B 80 auto 20 60 4 18 2 250 KPU 62 060L5206 C1 0 auto 20 60 4 18 2 250 KPU 63 060L5213 A 80 auto 60 15 10 25 2 250 KPU 63 060L5214 B 80 auto 60 15 10 25 2 250 KPU 68 060L5215 C1 0 auto 25 95 5 22 2 250 KPU 69 060L5217 B 80 auto 25 95 5 22 2 250 Adsorption KPU 62 060L5207 C2 0 auto 20...

Страница 2: ... times as these actions can weaken the material and increase the likelihood of the tube cracking 4 Form and locate the capillary tube away from sharp or abrasive objects that might damage it 5 Never allow the capillary tube of a vapor charged thermostat to run alongside of a suction line in a wall entry 6 Ensure minimal length of capillary tube exposed to temperature for KPU with straight capillar...

Страница 3: ...he lever Use fingers only B Manual reset button only on versions sold with manual reset function C Terminal block D Grounding screw Wiring Option A Cut Out on temperature fall Wiring Option B Cut Out on temperature rise C F KPU 61 KPU 62 C F LSP B C F D C KPU 63 LSP C F LSP KPU 68 KPU 69 C F C F 15 10 0 10 20 30 70 15 F Differential lines Differential lines 130 0 20 40 60 80 100 120 90 80 70 60 50...

Страница 4: ...used for service on non electrical parts Interrupt mains power before servicing electrical parts Adjustment thermostat with automatic reset Scale plate directly indicates High Switching Point and Differential Adjustment thermostat with manual reset Scale plate directly indicates Low Switching Point which is Cut Out There is no pointer for Differential Differential value is fixed and printed on the...

Отзывы: