© Danfoss A/S (AC-MC / jmn), 2014-02 

DKRCC.PI.CD0.A3.22 / 520H8467 

3

Wire dimensions: 10 AWG max.  

Cable entry: 

7

/

8

 in. cable entry for 

1

/

2

 in. male pipe thread  

connection (conduit boss) or similar (Pg 13.5 or Pg 16 ) 

screwed cable entry.

Contact function test (Manual trip)

When the electrical leads are connected the contact function 

can be manually tested regardless of temperature conditions 

in the system. 

The manual trip lever is located in the left side of the KPU. It 

must be operated with fingers only. Do not use screwdriver 

as it will damage the thermostat.

NOTE: 

While operating the manual trip on KPU switches with 

manual reset it is necessary to push the reset knob.

A:

 Manual trip. Push the lever. Use fingers only!

B:

 Manual reset button (only on versions sold with manual 

reset function)

C:

 Terminal block

D:

 Grounding screw

Wiring Option A:

– Cut-Out on temperature fall

Wiring Option B:

– Cut-Out on temperature rise

[°C] [°F]

KPU 61

KPU 62

[°C]

[°F] LSP

B

C

[°F]

D

[°C]

KPU 63

LSP

[°C]

[°F] LSP

KPU 68

KPU 69

[°C] [°F]

[°C] [°F]

15

10

0

-10

-20

-30

-70

15

 °F

Diff

ere

nti

al l

ine

s

Diff

ere

ntia

l lin

es

-130

0

20

40

60

80 100

120

-90 -80 -70 -60 -50 -40 -30 -20 -15

-110 -90

-70 -50

-30

-10

10

-55 -50 -40 -30

-20 -10

0

10

20

-50

-30

-10

10

30

50

70

-10

 

-20

-30

-40

-50

35

 

25

15

5
0

-5

60

40

20

0

-20

20

0

-20

-40

-60

100

80

60

40

20

-20

-25 -20 -10

0

10

20

30

40

50

20 °

F

30 °

F

20 °

F

15

 °F

5 °

F

20 °

F

10 °

F

10

 °F

5 °

F

Diff

ere

nti

al l

ine

s

HSP

HSP

HSP

Determination of differential

For KPU thermostats with vapor charge and automatic reset, 

use the following graphs to determine the correct differential.

Example:

HSP = 45 °F    

DIFF (from graph):

LSP = 32 °F  =>  13 °F (value which has to be set on diff. scale)

Содержание KPU 61

Страница 1: ...61B 060L5204 B 80 man min 1 20 60 5 fixed 2 250 KPU 61B 060L5205 B 200 man min 1 20 60 5 fixed 2 250 KPU 61 060L5210 B 80 auto 20 60 4 18 2 250 KPU 62 060L5206 C1 0 auto 20 60 4 18 2 250 KPU 63 060L5213 A 80 auto 60 15 10 25 2 250 KPU 63 060L5214 B 80 auto 60 15 10 25 2 250 KPU 68 060L5215 C1 0 auto 25 95 5 22 2 250 KPU 69 060L5217 B 80 auto 25 95 5 22 2 250 Adsorption KPU 62 060L5207 C2 0 auto 20...

Страница 2: ... times as these actions can weaken the material and increase the likelihood of the tube cracking 4 Form and locate the capillary tube away from sharp or abrasive objects that might damage it 5 Never allow the capillary tube of a vapor charged thermostat to run alongside of a suction line in a wall entry 6 Ensure minimal length of capillary tube exposed to temperature for KPU with straight capillar...

Страница 3: ...he lever Use fingers only B Manual reset button only on versions sold with manual reset function C Terminal block D Grounding screw Wiring Option A Cut Out on temperature fall Wiring Option B Cut Out on temperature rise C F KPU 61 KPU 62 C F LSP B C F D C KPU 63 LSP C F LSP KPU 68 KPU 69 C F C F 15 10 0 10 20 30 70 15 F Differential lines Differential lines 130 0 20 40 60 80 100 120 90 80 70 60 50...

Страница 4: ...used for service on non electrical parts Interrupt mains power before servicing electrical parts Adjustment thermostat with automatic reset Scale plate directly indicates High Switching Point and Differential Adjustment thermostat with manual reset Scale plate directly indicates Low Switching Point which is Cut Out There is no pointer for Differential Differential value is fixed and printed on the...

Отзывы: