24 DKDHR 

VI.GP.B1.02 

Danfoss District Energy

Instructions 

 

 

Kompakt H 28/35/42

16.2 Troubleshooting - Domestic hot water

Problem

Possible cause

Solution

No domestic hot water

Defective or wrongly set differential 

pressure controller.

Check the functions of the differential 

pressure controller - clean valve seat if 

required.

Strainer on DH supply clogged.

Clean strainer.

Defective actuator - or possibly dirt in 

the valve housing.

Check the functions of the actuator - 

clean valve seat if required.

Automatic controls wrongly set or defec-

tive - possibly power failure.

Check if the setting of the controller is 

correct, - see separate instructions.

Check the power supply; remember to 

check all 3 phases on large installations.

Temporary setting of motor to “manual” 

control - see instructions for automatic 

controls.

Calified heating element.

Clean DHW cylinder with acid solution or 

replace heating element.

Inadequate cylinder capacity.

Wait for heating / loading of the cylinder. 

You may check the specifications of the 

manufacturer conc. cylinder capacity.

Not enough pressure on the hot water

Strainer in cold water meter clogged.

Clean strainer - possibly in consultation 

with the water supply company.

Long waiting time

Circulation pump out of operation.

Check whether the pump is running - 

whether the pump is receiving power. 

control that there is no air in the pump 

housing - see pump manual.

Temperature too low

See “No domestic hot water”.

See “No domestic hot water”.

Non-return valve on the circulation line 

defective (leads to mixing - and the 

circulation water pipes become cold dur-

ing tapping).

Replace non-return valve.

Outdoor sensor placed incorrectly.

Mount temperature sensor correctly 

in accordance with the manufacturer 

instructions for the cylinder. 

You may contact Danfoss Redan A/S for 

further information.

Temperature too high

Defective actuator - possibly dirt in the 

valve housing.

Check the functions of the actuator - 

clean valve seat if required.

Automatic controls wrongly set or defec-

tive.

Check if the setting of the controller is 

correct, - see separate instructions.

Defective immersion sensor.

Replace immersion sensor.

Содержание Kompakt H28

Страница 1: ...rom the pallet 10 7 4 Lifting the substation 10 7 5 Mounting 11 7 6 Variable connection possibilities 11 7 7 Tightening of connections 11 7 8 Connection of expansion vessel 11 7 9 Heat meters Fitting...

Страница 2: ...perature The stations work at a maximum supply temperature from the district heating network of 120 C and the stations work with a op erating pressure of 16 bar which may put the user at risk of burns...

Страница 3: ...ve 8 Circulation pump HE P1 11 Safety valve HE 3 5 bar 13 Thermometer 14 Manometer 15 Manometer 17 Air vent 19 Connection for expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat...

Страница 4: ...ly for DHW cylinder P3 11 Safety valve HE 3 5 bar 13 Thermometer 14 Manometer with shut off valve 15 Manometer 17 Air valve 19 Connection for expansion vessel 23 Sensor pocket for heat meter 24 Fittin...

Страница 5: ...Twin pump for HE P1 11 Safety valve HE 3 5 bar 13 Thermometer 14 Manometer with shut off valve 15 Manometer 17 Air valve 19 Connection for expansion vessel 23 Sensor pocket for heat meter 24 Fitting...

Страница 6: ...tated in this instruction manual Instructions for the fitted components will be supplied together with the substation 24 1 25 8 29 30 24 Primary Secundary Cylinder supply Cylinder return HE return HE...

Страница 7: ...s basically as stated in this instruction manual Instructions for the fitted components will be supplied together with the substation 1 25 29 30 4 8 31 32 24 24 Primary Secundary Cylinder supply Cylin...

Страница 8: ...d in this instruction manual Instructions for the fitted components will be supplied together with the substation 1 25 29 30 8 24 24 Primary Secundary Cylinder supply Cylinder return HE return HE supp...

Страница 9: ...s basically as stated in this instruction manual Instructions for the fitted components will be supplied together with the substation 1 25 29 30 4 8 31 32 24 24 Primary Secundary Cylinder supply Cylin...

Страница 10: ...doorposts etc The substation includes delicate components 7 3 Removing the substation from the pallet The substation is screwed on a mounting frame which is screwed on the pallet Loosen the screws poi...

Страница 11: ...en the connections and take the substation into continuous use Please note that the connections may be supplied with EPDM rub ber gaskets in general connection sizes from to and incl 1 for Kompakt H s...

Страница 12: ...door temperature sensor S1 The outdoor temperature sensor is delivered separately and must be mounted on site according to the enclosed illustrations The outdoor sensor is always to be mounted on the...

Страница 13: ...illing Start up Electrical connections Application Sensor 1 Cylinder top Sensor 2 Cylinder bottom P17 S1 Clamp 17 16 S2 Clamp 18 16 C37 47 S6 Clamp 22 16 S5 Clamp 21 16 C67 S6 Clamp 22 16 S5 Clamp 21...

Страница 14: ...system The operating pressure should never exceed 2 5 bar The safety valves open at 3 5 bar If system pressure drops dramatically within a short time heating system should be examined for leakage thi...

Страница 15: ...2 Select controller mode 3 Adjust room and hot water temperature 4 Set personal day plan 5 Advantages of the ECL Card 6 Hot points 7 Definitions The documentation for the ECL Comfort controller is co...

Страница 16: ...50 DN 15 50 DN 32 50 p 0 2 p 0 2 p 0 2 p 0 2 p 0 2 p 0 2 p 0 2 AVQM PN 16 AVQM PN 25 AVQMT PN 25 AVQMT AVT PN 25 ENglIsh Flow and temperature controller with integrated control valve AVQM AVQMT www d...

Страница 17: ...IBC VI HB C1 00 Danfoss 5 02 1 Instructions VM2 VB2 2 way 065R9074 065R9074 DN L mm 15 65 20 70 25 75 32 100 40 110 50 130 DN L1 mm 15 131 20 142 25 159 32 196 40 196 50 228 DN L2 mm 15 139 20 154 25...

Страница 18: ...eating is automatically switched off in pe riods without heat demand To prevent the pump from blocking in periods without heat demand the controller automatically switches on the pump for some minutes...

Страница 19: ...Instructions for setting of pump Four control modes are available AUTO mode self regulating from one proportional pressure curve to another to optimise comfort and reduce energy consumption to a mini...

Страница 20: ...e included here Before you start Installation 10 Identifying the system type 11 Mounting the ECL Comfort controller 12 Electrical connections 230 V a c 13 Electrical connections 24 V a c 14 Placing th...

Страница 21: ...sed Measures after maintenance work After maintenance work and before switching the system on again Check that all screwed connections are tight Checkthatallsafetyfeatures covers thatwereremoved haveb...

Страница 22: ...ions of the 2 way valve clean valve housing if required Automatic controls wrongly set or defec tive possibly power failure Check if the setting of the controller is correct see separate instructions...

Страница 23: ...ing heating surface Make sure that the heat is distributed evenly across the full heating surface open all radiators and keep the radiator in the system from heating up at the bottom Higher temperatur...

Страница 24: ...linder You may check the specifications of the manufacturer conc cylinder capacity Not enough pressure on the hot water Strainer in cold water meter clogged Clean strainer possibly in consultation wit...

Страница 25: ...pressure controller clean the valve seat and the capillary tubes Automatic controls wrongly set Check that the controller has been cor rectly set see separate instructions Temperature sensor placed i...

Страница 26: ...7 Electromagnetic compatibility Generic standard Immunity for residential commercial and light industry EN 61000 6 2 2007 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3...

Страница 27: ...27 27 Danfoss District Energy VI GP B1 02 DKDHR Instructions Kompakt H 28 35 42...

Страница 28: ...Produced by Danfoss Redan A S 10 2010 Danfoss Redan A S Omega 7 S ften DK 8382 Hinnerup Phone 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Отзывы: