Danfoss District Energy 

VI.GP.B1.02 

DKDHR

Instructions 

 

 

Kompakt H 28/35/42

7.11 Mounting of immersion sensor 

Please note: Only for ECL 300 variants

The immersion sensor for accurate temperature measurement and 

control in the cylinder is supplied separately and must be mount-

ed and connected to the controller on site.

Temperature range immersion sensor: 0 to 100 °C

Temperature range immersion pocket: 0 to 180 °C

2-wire cable (2 x 0.34 mm²) spliced is preassembled in the control-

ler. 

1) Mount sensor pocket (separately delivered) in top or bottom of 

cylinder.

2) Lay immersion sensor and cable from substation to cylinder and 

mount immersion sensor in immersion pocket.

In case the length of the sensor cable is not long enough for your 

property, it is recommendable to change the whole cable. The 

minimum area for the cable is 0,4 mm² and max. length is 125 m.

For electrical connections please refer to enclosed schedule.

8.0  Filling, Start-up

Electrical connections

Application Sensor 1 (Cylinder top) Sensor 2 (Cylinder bottom)

P17

S1

Clamp 17

16

S2

Clamp

18

16

C37/47

S6

Clamp 22

16

S5

Clamp

21

16

C67

S6

Clamp 22

16

S5

Clamp

21

16

Sensor 2 (Return temp. sensor)

P16

S3

Clamp 19

16

S4

Clamp

20

16

C66

S5

Clamp 21

16

S6

Clamp

22

16

Check and tighten all connections before adding water to the 

system, as vibrations during transport may have caused leaks.  

After having added water to the system, tighten all the connec-

tions before performing leak test. 

Then heat up the system and tighten the connections once again.

Before adding water to the system and first start-up, check if:

-  pipes are connected according to the circuit diagram,

-  expansion vessel, if any, is connected,

-  heat meter is mounted,

-  shut-off valves are closed,

-  threaded and flanged connections are tightened.

Adding water to the system:

1.  Pump must be switched off when water is added to the system.

2.  Fill heat exchanger and system with water until the manometer 

  shows a working pressure, which corresponds to the system 

   5 m (approx. 1,5 - 2,0 bar)

3.  Deaerate the system completely.

4.  Start the pump.

Содержание Kompakt H28

Страница 1: ...rom the pallet 10 7 4 Lifting the substation 10 7 5 Mounting 11 7 6 Variable connection possibilities 11 7 7 Tightening of connections 11 7 8 Connection of expansion vessel 11 7 9 Heat meters Fitting...

Страница 2: ...perature The stations work at a maximum supply temperature from the district heating network of 120 C and the stations work with a op erating pressure of 16 bar which may put the user at risk of burns...

Страница 3: ...ve 8 Circulation pump HE P1 11 Safety valve HE 3 5 bar 13 Thermometer 14 Manometer 15 Manometer 17 Air vent 19 Connection for expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat...

Страница 4: ...ly for DHW cylinder P3 11 Safety valve HE 3 5 bar 13 Thermometer 14 Manometer with shut off valve 15 Manometer 17 Air valve 19 Connection for expansion vessel 23 Sensor pocket for heat meter 24 Fittin...

Страница 5: ...Twin pump for HE P1 11 Safety valve HE 3 5 bar 13 Thermometer 14 Manometer with shut off valve 15 Manometer 17 Air valve 19 Connection for expansion vessel 23 Sensor pocket for heat meter 24 Fitting...

Страница 6: ...tated in this instruction manual Instructions for the fitted components will be supplied together with the substation 24 1 25 8 29 30 24 Primary Secundary Cylinder supply Cylinder return HE return HE...

Страница 7: ...s basically as stated in this instruction manual Instructions for the fitted components will be supplied together with the substation 1 25 29 30 4 8 31 32 24 24 Primary Secundary Cylinder supply Cylin...

Страница 8: ...d in this instruction manual Instructions for the fitted components will be supplied together with the substation 1 25 29 30 8 24 24 Primary Secundary Cylinder supply Cylinder return HE return HE supp...

Страница 9: ...s basically as stated in this instruction manual Instructions for the fitted components will be supplied together with the substation 1 25 29 30 4 8 31 32 24 24 Primary Secundary Cylinder supply Cylin...

Страница 10: ...doorposts etc The substation includes delicate components 7 3 Removing the substation from the pallet The substation is screwed on a mounting frame which is screwed on the pallet Loosen the screws poi...

Страница 11: ...en the connections and take the substation into continuous use Please note that the connections may be supplied with EPDM rub ber gaskets in general connection sizes from to and incl 1 for Kompakt H s...

Страница 12: ...door temperature sensor S1 The outdoor temperature sensor is delivered separately and must be mounted on site according to the enclosed illustrations The outdoor sensor is always to be mounted on the...

Страница 13: ...illing Start up Electrical connections Application Sensor 1 Cylinder top Sensor 2 Cylinder bottom P17 S1 Clamp 17 16 S2 Clamp 18 16 C37 47 S6 Clamp 22 16 S5 Clamp 21 16 C67 S6 Clamp 22 16 S5 Clamp 21...

Страница 14: ...system The operating pressure should never exceed 2 5 bar The safety valves open at 3 5 bar If system pressure drops dramatically within a short time heating system should be examined for leakage thi...

Страница 15: ...2 Select controller mode 3 Adjust room and hot water temperature 4 Set personal day plan 5 Advantages of the ECL Card 6 Hot points 7 Definitions The documentation for the ECL Comfort controller is co...

Страница 16: ...50 DN 15 50 DN 32 50 p 0 2 p 0 2 p 0 2 p 0 2 p 0 2 p 0 2 p 0 2 AVQM PN 16 AVQM PN 25 AVQMT PN 25 AVQMT AVT PN 25 ENglIsh Flow and temperature controller with integrated control valve AVQM AVQMT www d...

Страница 17: ...IBC VI HB C1 00 Danfoss 5 02 1 Instructions VM2 VB2 2 way 065R9074 065R9074 DN L mm 15 65 20 70 25 75 32 100 40 110 50 130 DN L1 mm 15 131 20 142 25 159 32 196 40 196 50 228 DN L2 mm 15 139 20 154 25...

Страница 18: ...eating is automatically switched off in pe riods without heat demand To prevent the pump from blocking in periods without heat demand the controller automatically switches on the pump for some minutes...

Страница 19: ...Instructions for setting of pump Four control modes are available AUTO mode self regulating from one proportional pressure curve to another to optimise comfort and reduce energy consumption to a mini...

Страница 20: ...e included here Before you start Installation 10 Identifying the system type 11 Mounting the ECL Comfort controller 12 Electrical connections 230 V a c 13 Electrical connections 24 V a c 14 Placing th...

Страница 21: ...sed Measures after maintenance work After maintenance work and before switching the system on again Check that all screwed connections are tight Checkthatallsafetyfeatures covers thatwereremoved haveb...

Страница 22: ...ions of the 2 way valve clean valve housing if required Automatic controls wrongly set or defec tive possibly power failure Check if the setting of the controller is correct see separate instructions...

Страница 23: ...ing heating surface Make sure that the heat is distributed evenly across the full heating surface open all radiators and keep the radiator in the system from heating up at the bottom Higher temperatur...

Страница 24: ...linder You may check the specifications of the manufacturer conc cylinder capacity Not enough pressure on the hot water Strainer in cold water meter clogged Clean strainer possibly in consultation wit...

Страница 25: ...pressure controller clean the valve seat and the capillary tubes Automatic controls wrongly set Check that the controller has been cor rectly set see separate instructions Temperature sensor placed i...

Страница 26: ...7 Electromagnetic compatibility Generic standard Immunity for residential commercial and light industry EN 61000 6 2 2007 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3...

Страница 27: ...27 27 Danfoss District Energy VI GP B1 02 DKDHR Instructions Kompakt H 28 35 42...

Страница 28: ...Produced by Danfoss Redan A S 10 2010 Danfoss Redan A S Omega 7 S ften DK 8382 Hinnerup Phone 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Отзывы: