Parameter list - Valid from: (¡58:14, ¡59:45) and onwards

Description

ICAD 

parameter

Min Max

Factory 

Setting

Stored Unit

Pass 

word

Comments

OD (Opening degree)

-

0

100

%

-

ICM/ICMTS valve Opening Degree (CVE pressure setting) is displayed during normal 

operation. 

Running display value (see 

¡01

¡05

).

Main Switch

¡01

1

2

1

-

No

Internal main switch 

1: Normal operation 

2: Manual operation. Valve Opening Degree will be flashing. With the down  

  arrow and the up arrow push buttons the OD can be entered manually.

Mode

¡02

1

2

1

-

No

Operation mode 

1:   Modulating – ICM, ICMTS & CVE positioning according to Analog Input (see

 ¡03

2:   ON/OFF - ICM only. Operating the ICM valve like an ON/OFF solenoid valve  

  controlled via Digital Input. See also 

¡09

.

3:   Neutralzone / 3 point control - ICM only. Increase/Decrease Opening Degree by  

  Digital Input. See fig. 9

AI signal

¡03

1

4

2

-

No

Type of AI signal from external controller 

1: 0 – 20 mA 

2: 4 – 20 mA 

3: 0 – 10 V 

4: 2 – 10 V

Speed

In Modulating Mode

Opening/closing 

speed

In ON/OFF Mode

Opening speed 

In Neutralzone/

3 point control

Opening speed = 10

¡04

1

100

50/ 100

-

No

Speed can be decreased. Max. speed is 100 % - Not active in manual operation (

¡01

 = 2)

For CVE the speed should not exceed 50 (factory setting) 

 

If 

¡26

= 1 - 3 then factory setting =100 

If 

¡26

= 4 - 10 then factory setting =50 

 

If the valve is opening and (

¡04

 < = 33) or the valve is closing and (

¡14

 < = 33) 

=> Low is displayed. 

 

If the valve is opening and (33 < If 

¡04

 < = 66) or the valve is closing and (33 < If 

¡14

 < = 66) 

=> Med is displayed. 

 

If the valve is opening and (

¡04

 > = 67) or the valve is closing and (

¡14

 > = 67)  

=>  High is displayed"

Automatic calibration

¡05

0

2

0

-

No

Not active before 

¡26

 has been operated. 

Always auto reset to 0. 

CA will flash in the display during calibration, 

if Enter push button has been activated for two seconds 

0: No Calibration 

1: Normal forced calibration -  CA flashing slowly 

2: Extended calibration – CA flashing rapidly"

AO signal

¡06

0

2

2

-

No

Type of A0 signal for ICM valve position 

0: No signal 

1: 0 – 20 mA 

2: 4 – 20 mA

Failsafe

¡07

1

4

1

-

No

Define condition at power cut and fail safe supply is installed. 

1: Close valve 

2: Open Valve 

3: Maintain valve position 

4: Go to OD given by 

¡12

"

Fail safe supply

¡08

0

1

0

Yes

Fail safe supply connected and enable of A4 alarm: 

0: No 

1: Yes 

DI function

¡09

1

2

1

No

Define function when DI is ON (short circuited DI terminals) when 

¡02

 = 2 

1: Open ICM valve (DI = OFF = > Close ICM valve) 

2: Close ICM valve (DI = OFF = > Open ICM valve)

Password

¡10

0

199

0

-

-

Enter number to access password protected parameters: 

¡26

 

Password = 11

Old Alarms

¡11

A1

A99

-

-

No

Old alarms will be listed with the latest shown first. Alarm list can be reset by means  

of activating down arrow and up arrow at the same time for 2 seconds.

OD at power cut.

¡12

0

100

50

No

Only active if 

¡07

 = 4 

If fail safe supply is connected and power cut occurs, the valve will go to the specified OD.

Inverse operation

¡13

0

1

0

No

When 

¡02

 = 1

0:   Increasing Analog Input signal => Increasing ICM Opening Degree 

1:   Increasing Analog Input signal => Decreasing ICM Opening Degree   

When 

¡02

 = 3

0:   DI1 = ON, DI2 = OFF => Increasing valve Opening Degree.

     DI1 = OFF, DI2 = ON  => Decreasing valve Opening Degree

  DI1 = DI2 = OFF  

=> ICAD/ICM maintain current position

  DI1 = DI2 = ON  

=> ICAD/ICM maintain current position

1:   DI1 = ON, DI2 = OFF  => Decreasing ICM Opening Degree 

  DI1 = OFF, DI2 = ON  => Increasing ICM Opening Degree

  DI1 = DI2 = OFF  

=> ICAD/ICM maintain current position

  DI1 = DI2 = ON  

=> ICAD/ICM maintain current position

 

The first parameter to be entered shall be: 

¡26

to be continued....

ENGLISH

Содержание ICAD 600A

Страница 1: ...the separate installation guide Mechanical intallation of ICAD on ICM document number AN285252668332 Vor Montage des ICAD auf das ICM bitte die separate Montageanleitung Mechanische Montage des ICAD...

Страница 2: ...r gulation modulante E S anal gica para control modulante ICAD 600A 600A TS 1200A Digital I O for ON OFF valve operation Digitaler E A f r EIN AUS Ventilbetrieb E S num rique pour marche arr t de la v...

Страница 3: ...lue Analog output 0 4 20 mA If Neutral zone 3 point control is selected parameter i02 3 then E and G is used as DI2 Digital ON OFF input Se fig 9 Electrical installation General procedure for ICAD 600...

Страница 4: ...ts that ICAD is operating the ICM valve like an ON OFF solenoid valve with medium speed according to a digital input signal Description ICAD alarm text Definition of event Comments No Valve type selec...

Страница 5: ...re 26 has been operated Always auto reset to 0 CA will flash in the display during calibration if Enter push button has been activated for two seconds 0 No Calibration 1 Normal forced calibration CA f...

Страница 6: ...m is ON Time interval between boost is set in 19 The boost cyklus continues until the valve is back in operation Delay after boost before A9 alarm See Note 1 19 0 30 1 Minutes No Time delay between tw...

Страница 7: ...ON DI2 OFF 01 DI1 OFF DI2 ON 11 DI1 ON DI2 ON DO Close 55 0 1 DO Closed status ON when OD 3 DO Open 56 0 1 DO Open status ON when OD 97 DO Alarm 57 0 1 DO alarm status ON when a Alarm is detected Disp...

Страница 8: ...m Typ EKC EKE Abb 7 oder ber Steuerger te von Drittanbietern z B SPS geregelt Analoge Eingangssignale anschlie en Strom mA oder Spannung V Siehe Parameterliste f r die Konfiguration der analogen Einga...

Страница 9: ...betreibt Beschreibung ICAD Alarmtext Definition des Zustands Anmerkungen Kein Ventiltyp ausgew hlt A1 Alarm EIN Bei der Inbetriebnahme wird A1 angezeigt Reglerst rung A2 Alarm EIN Interne St rung in d...

Страница 10: ...rierung blinkt CS im Display auf wenn die Drucktaste Enter zwei Sekunden lang gedr ckt wurde 0 Keine Kalibrierung 1 Normal erzwungene Kalibrierung CS blinkt langsam 2 Erweiterte Kalibrierung CS blinkt...

Страница 11: ...intervall zwischen den Boosts wird in 19eingestellt Der Boost Zyklus wird solange fortgesetzt bis das Ventil wieder in Betrieb ist Verz gerung nach Boost vor A9 Alarm Siehe Hinweis 1 19 0 30 1 Minuten...

Страница 12: ...I1 AUS DI2 EIN 11 DI1 EIN DI2 EIN DO geschlossen 55 0 1 DO Status geschlossen Nur EIN wenn OD 3 DO offen 56 0 1 DO Status ge ffnet Nur EIN wenn OD 97 DO Alarm 57 0 1 DO Alarmstatus EIN wenn ein Alarm...

Страница 13: ...gique uniquement Fig 7 R gulation de modulation Vanne command e partir du syst me lectronique Danfoss de type EKC EKE fig 7 ou partir d un autre syst me lectronique tel que l API Connectez les signaux...

Страница 14: ...tion d un signal d entr e digitale du march Texte d alarme ICAD D finition d un v nement Commentaires Aucun type de vanne s lectionn A1 Alarme activ e Au d marrage A1 est affich D faut du r gulateur A...

Страница 15: ...alibrage si le bouton Entr e a t enfonc pendant deux secondes 0 aucun calibrage 1 calibrage forc normal CA clignote lentement 2 talonnage tendu CA clignote rapidement Signal AO 06 0 2 2 Non Type de si...

Страница 16: ...19 Le cycle d acc l ration continue jusqu restauration du fonctionnement de la vanne Temporisation apr s acc l ration avant alarme A9 Voir remarque 1 19 0 30 1 Minutes Non Temporisation entre deux ac...

Страница 17: ...ARR T 01 DI1 ARR T DI2 MARCHE 11 DI1 MARCHE DI2 MARCHE DO ferm e 55 0 1 tat ferm de DO En MARCHE lorsque OD 3 DO ouverte 56 0 1 tat ouvert de DO En MARCHE lorsque OD 97 Alarme de DO 57 0 1 tat d alarm...

Страница 18: ...ntrolarse con electr nica Danfoss EKC EKE fig 7 o electr nica de otro fabricante como por ejemplo un controlador PLC Conecte las se ales de entrada anal gicas Corriente mA o tensi n V Consulte la List...

Страница 19: ...ula solenoide ON OFF de velocidad media de acuerdo con una se al de entrada digital Descripci n Texto de alarma del actuador ICAD Definici n del evento Observaciones No se ha seleccionado ning n tipo...

Страница 20: ...n 1 Calibraci n normal forzada el mensaje CA parpadear lentamente 2 Calibraci n ampliada el mensaje CA parpadear r pidamente Se al AO 06 0 2 2 No Tipo de se al AO de posici n de la v lvula ICM 0 Sin...

Страница 21: ...v lvula vuelve a ponerse en funcionamiento Retardo tras el impulso antes de la alarma A9 Consulte la nota 1 19 0 30 1 Minutos No Retardo entre dos impulsos Vinculado a la funci n 18 Valor m ximo de de...

Страница 22: ...a DO en estado de cierre ON cuando OD 3 Salida DO abierta 56 0 1 Salida DO en estado de apertura ON cuando OD 97 Alarma de salida DO 57 0 1 Salida DO en estado de alarma ON cuando se detecta una alarm...

Страница 23: ...Danfoss DCS ms 2020 01 AN19798642980802 000701 23...

Страница 24: ...Danfoss DCS ms 2020 01 AN19798642980802 000701 24...

Отзывы: