FC 300 Instruction Manual
How to Program
"
6-** Analog In/Out
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
6-0* Analog IO mode
6-00
Live zero Timeout Time
10 s
All set-ups
TRUE
0
Uint8
6-01
Live zero Timeout Function
[0] Off
All set-ups
TRUE
-
Uint8
6-1* Analog input 1
6-10
Terminal 53 low voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-11
Terminal 53 high voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-12
Terminal 53 low current
0.14 mA
All set-ups
TRUE
-5
Int16
6-13
Terminal 53 high current
20.00 mA
All set-ups
TRUE
-5
Int16
6-14
Terminal 53 low ref./feedb. value
0.000 Unit
All set-ups
TRUE
-3
Int32
6-15
Terminal 53 high ref./feedb. value
1500.000 Unit
All set-ups
TRUE
-3
Int32
6-16
Terminal 53 filter time constant
0.001 s
All set-ups
FALSE
-3
Uint16
6-2* Analog input 2
6-20
Terminal 54 low voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-21
Terminal 54 high voltage
10.00 V
All set-ups
TRUE
-2
Int16
6-22
Terminal 54 low current
0.14 mA
All set-ups
TRUE
-5
Int16
6-23
Terminal 54 high current
20.00 mA
All set-ups
TRUE
-5
Int16
6-24
Terminal 54 low ref./feedb. value
0.000 Unit
All set-ups
TRUE
-3
Int32
6-25
Terminal 54 high ref./feedb. value
1500.000 Unit
All set-ups
TRUE
-3
Int32
6-26
Terminal 54 filter time constant
0.001 s
All set-ups
FALSE
-3
Uint16
6-5* Analog output 1
6-50
Terminal 42 output
[0] No operation
All set-ups
TRUE
-
Uint8
6-51
Terminal 42 output min scale
0.00 %
All set-ups
TRUE
-2
Int16
6-52
Terminal 42 output max scale
100.00 %
All set-ups
TRUE
-2
Int16
"
7-** Controllers
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
7-0* Speed PID ctrl.
7-02
Speed PID proportional gain
0.015
All set-ups
TRUE
-3
Uint16
7-03
Speed PID Integral Time
Drive dependent
All set-ups
TRUE
-4
Uint32
7-04
Speed PID differentiation time
Drive dependent
All set-ups
TRUE
-4
Uint16
7-05
Speed PID diff. gain Limit
5.0
All set-ups
TRUE
-1
Uint16
7-06
Speed PID lowpass filter time
10.0 ms
All set-ups
TRUE
-4
Uint16
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
52
MG.33.A4.22 - VLT is a registered Danfoss trademark