FC 300 Instruction Manual
How to Install
How to add the MCB 105 option:
•
The power to the adjustable frequency drive must be disconnected.
•
The power to the live part connections on relay terminals must be disconnected.
•
Remove the LCP, the terminal cover, and the LCP fixture from the FC 30x.
•
Fit the MCB 105 option in slot B.
•
Connect the control cables and fasten the cables with the enclosed cable strips.
•
Make sure the length of the stripped wire is correct (see the following drawing).
•
Do not mix live parts (high voltage) with control signals (PELV).
•
Fit the enlarged LCP fixture and enlarged terminal cover.
•
Replace the LCP.
•
Connect power to the adjustable frequency drive.
•
Select the relay functions in par. 5-40 [6-8], 5-41 [6-8] and 5-42 [6-8].
NB (Array [6] is relay 7, array [7] is relay 8, and array [8] is relay 9)
Do not combine low voltage parts and PELV systems.
30
MG.33.A4.22 - VLT is a registered Danfoss trademark