FC 300 Instruction Manual
How to Program
"
Basic Parameters
0-01 Language
Option:
*
English UK (ENGLISH)
[0]
German (DEUTSCH)
[1]
French (FRANCAIS)
[2]
Danish (DANSK)
[3]
Spanish (ESPANOL)
[4]
Italian (ITALIANO)
[5]
Chinese (CHINESE)
[10]
Finnish (FINNISH)
[20]
English US (ENGLISH US)
[22]
Greek (GREEK)
[27]
Portuguese (PORTUGUESE)
[28]
Slovenian (SLOVENIAN)
[36]
Korean (KOREAN)
[39]
Japanese (JAPANESE)
[40]
Turkish (TURKISH)
[41]
Traditional Chinese
[42]
Bulgarian
[43]
Serbian
[44]
Romanian (ROMANIAN)
[45]
Hungarian (HUNGARIAN)
[46]
Czech
[47]
Polish (POLISH)
[48]
Russian
[49]
Thai
[50]
Bahasa Indonesian (BAHASA
INDONESIAN)
[51]
Function:
Defines the language to be used in display.
The adjustable frequency drive can be delivered
with 4 various language packages. English and
German are included in all packages. English
cannot be erased or manipulated.
1-20 Motor Power [kW]
Range:
0.50 - 10 HP (0.37-7.5 kW)
[Motor
type de-
pendent]
Function:
The value should equal the nameplate data on the
connected motor. The default value corresponds
to the nominal rated output of the unit.
NOTE
Changing the value in this parameter
affects the setting of other parameters.
Par. 1-20 cannot be changed while
the motor is running.
1-22 Motor Voltage
Range:
200-500 V
[Motor
type de-
pendent]
Function:
The value should equal the nameplate data on the
connected motor. The default value corresponds
to the nominal rated output of the unit.
NOTE
Changing the value in this parameter
affects the setting of other parameters.
Par. 1-22 cannot be changed while
the motor is running.
1-23 Motor Frequency
Option:
*
50 Hz (50 HZ)
[50]
60 Hz (60 HZ)
[60]
Min - Max motor frequency: 20 - 300 Hz
Function:
Select the stated value from the motor name plate.
Alternatively, set the value for motor frequency to
be infinitely variable. If a value different from 50 Hz
or 60 Hz is selected, it is necessary to correct par.
1-50 to 1-54. For 87 Hz operation with 230/400 V
motors, set the name plate data for 230 V/50 Hz.
Adapt par. 2-02
Output speed high limit
and par.
2-05
Maximum reference
to the 87 Hz application.
NOTE
Changing the value in this parameter
affects the setting of other parameters.
Par. 1-23 cannot be changed while
the motor is running.
NOTE
If a delta connection is used, select
the rated motor frequency for the
delta connection.
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
42
MG.33.A4.22 - VLT is a registered Danfoss trademark