FC 300 Instruction Manual
How to Program
"
5-** Digital In/Out
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
5-0* Digital IO mode
5-00
Digital I/O mode
[0] PNP
All set-ups
FALSE
-
Uint8
5-01
Terminal 27 mode
[0] Input
All set-ups
FALSE
-
Uint8
5-02
Terminal 29 mode
[0] Input
All set-ups
FALSE
-
Uint8
5-1* Digital inputs
5-10
Terminal 18 digital input
[8] Start
All set-ups
TRUE
-
Uint8
5-11
Terminal 19 digital input
[10] Reverse
All set-ups
TRUE
-
Uint8
5-12
Terminal 27 digital input
[2] Coast inverse
All set-ups
TRUE
-
Uint8
5-13
Terminal 29 digital input
[14] Jog
All set-ups
TRUE
-
Uint8
5-14
Terminal 32 digital input
[24] Set-up select bit 1
All set-ups
TRUE
-
Uint8
5-15
Terminal 33 digital input
[23] Set-up select bit 0
All set-ups
TRUE
-
Uint8
5-3* Digital outputs
5-30
Terminal 27 digital output
[0] No operation
All set-ups
TRUE
-
Uint8
5-31
Terminal 29 digital output
[0] No operation
All set-ups
TRUE
-
Uint8
5-4* Relays
5-40
Function relay
[0] No operation
All set-ups
TRUE
-
Uint8
5-41
On delay, relay
0.01 s
All set-ups
TRUE
-2
Uint16
5-42
Off delay, relay
0.01 s
All set-ups
TRUE
-2
Uint16
5-5* Pulse input
5-50
Term. 29 low frequency
100 Hz
All set-ups
TRUE
0
Uint32
5-51
Term. 29 high frequency
100 Hz
All set-ups
TRUE
0
Uint32
5-52
Term. 29 low ref./feedb. value
0.000 Unit
All set-ups
TRUE
-3
Int32
5-53
Term. 29 high ref./feedb. value
1500.000 Unit
All set-ups
TRUE
-3
Int32
5-54
Pulse filter time constant #29
100 ms
All set-ups
FALSE
-3
Uint16
5-55
Term. 33 low frequency
100 Hz
All set-ups
TRUE
0
Uint32
5-56
Term. 33 high frequency
100 Hz
All set-ups
TRUE
0
Uint32
5-57
Term. 33 low ref./feedb. value
0.000 Unit
All set-ups
TRUE
-3
Int32
5-58
Term. 33 high ref./feedb. value
1500.000 Unit
All set-ups
TRUE
-3
Int32
5-59
Pulse filter time constant #33
100 ms
All set-ups
FALSE
-3
Uint16
5-6* Pulse output
5-60
Terminal 27 pulse output variable
[0] No operation
All set-ups
FALSE
-
Uint8
5-62
Pulse output maximum frequency #27
5000 Hz
All set-ups
FALSE
0
Uint32
5-63
Terminal 29 pulse output variable
[0] No operation
All set-ups
FALSE
-
Uint8
5-65
Pulse output maximum frequency #29
5000 Hz
All set-ups
FALSE
0
Uint32
5-7* 24V encoder input
5-70
Term 32/33 encoder resolution
1024
All set-ups
FALSE
0
Uint16
5-71
Term 32/33 encoder direction
[0] Clockwise
All set-ups
FALSE
-
Uint8
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
51
MG.33.A4.22 - VLT is a registered Danfoss trademark
Содержание FC 302
Страница 34: ...FC 300 Instruction Manual How to Install 34 MG 33 A4 22 VLT is a registered Danfoss trademark...
Страница 74: ...FC 300 Instruction Manual Troubleshooting 74 MG 33 A4 22 VLT is a registered Danfoss trademark...
Страница 77: ...FC 300 Instruction Manual Index 4 485 V DC 63 77 MG 33 A4 22 VLT is a registered Danfoss trademark...