![background image](http://html1.mh-extra.com/html/danfoss/fc-300-profibus/fc-300-profibus_manual_3480177028.webp)
FC 300 Profibus
How to Control the FC 300
Influence of the Digital Input Terminals upon FC 300 Control Mode, Par. 8-50 to 8-56
The influence of the digital input terminals upon control of the FC 300 can be programmed in par. 8-50 to
8-56. Please note the par. 8-01
Control Site
overrules the settings in par. 8-50 to 8-56, and Terminal
37
Coasting Stop (safe)
overrules any parameter.
Each of the digital input signals can be programmed to logic AND, logic OR, or to have no relation to the
corresponding bit in the control word. In this way a specific control command i.e. stop / coast, can be
initiated by fieldbus only, fieldbus AND Digital Input, or Ether Fieldbus OR Digital input terminal.
In order to control the FC 300 via PROFIBUS, par. 8-50
Coasting select
must be set to either Bus
[1], or to Logic AND [2], and par. 8-01
Control Site
must be set to [0] or [2].
More detailed information and examples of logical relationship options are provided in the
Troubleshooting
chapter
.
28
MG.33.C2.02 - VLT is a registered Danfoss trademark
Содержание FC 300 Profibus
Страница 4: ...FC 300 Profibus Copyright FC 300 Profibus 4 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 6: ...FC 300 Profibus Safety Note FC 300 Profibus 6 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 18: ...FC 300 Profibus How to Install 18 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 24: ...FC 300 Profibus How to Configure the System 24 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 56: ...FC 300 Profibus How to Access FC 300 Parameters 56 MG 33 C2 02 VLT is a registered Danfoss trademark...