FC 300 Profibus
Parameters
-
Output frequency = JOG freq.:
The motor runs
at JOG frequency until communication resumes.
-
Output frequency = Max. freq..
The motor runs
at maximum frequency until communication
resumes.
-
Stop with trip:
The motor stops. You need to
reset the frequency converter, see explanation
above.
Select set-up x:
This type of time-out function is used for changing
set-up on a control word time-out. If communcation
resumes causing the time-out situation to disappear,
par. 8-05
End-of-time-out Function
defines whether
to resume the set-up used before the time-out or to
hold the set-up endorsed by the time-out function.
Note that the following parameters have to be
configured for the set-up change to occur on a
time-out. Par. 0-10
Active set-up
has to be set to
Multi set-up
along with the relevant linking set in
par. 0-12
This Set-up Linked To
.
8-05 End-of-time-out Function
Option:
*
Hold set-up
[0]
Resume set-up
[1]
Function:
Defines the action after receiving a valid control
word upon a time-out. This only applies if set-up
1-4 is been selected in par. 8-04.
Hold:
The drive holds the set-up selected in par.
8-04 and displays a warning, until par. 8-06 toggles.
Then the drive resumes its original set-up.
Resume:
The drive resumes to the original set-up.
8-06 Reset Control Word Time-out
Option:
*
Do not reset
[0]
Do reset
[1]
Function:
Used for returning the drive to the original set-up
after a Control word time-out. When setting the
value to
“Do Reset”
[1], it returns to
“Do not reset”
[0].
8-07 Diagnosis Trigger
Option:
*
Disable
[0]
Trigger on alarms
[1]
Trigger alarms/warn.
[2]
Alarm diagnostics
[3]
Function:
Enables and controls the drive diagnosis function
and permits expansion of the diagnosis data to 24
byte.
-
Disable:
Extended diagnosis data are not sent
even if they appear in the frequency converter.
-
Trigger on alarms:
Extended diagnosis data are
sent when one or more alarms appear in alarm
par. 16-04 or 9-53.
-
Trigger alarms/warn:
Extended diagnosis data
are sent if one or more alarms/warnings appear
in alarm par. 16-04, 9-53, or warning parameter
16-05.
-
Alarm diagnostics:
The extended diagnosis
sequence works as follows: If an Alarm or
warning appears, the frequency converter
informs the master by sending a high priority
message via the output data telegram.
Consequently, the master sends a request for
extended diagnosis information to the frequency
converter. The frequency converter replies.
When the Alarm/warning disappears, the
frequency converter informs the master again,
and on the following request from the master
returns a standard DP diagnosis frame (6 bytes).
The content of the extended diagnosis frame is as follows:
Byte
Content
Description
0 - 5
Standard DP
Diagnose Data
Standard DP Diagnose Data
6
PDU length xx
Header of extended diagnostic
data
7
Status type =
0x81
Header of extended diagnostic
data
8
Slot = 0
Header of extended diagnostic
data
9
Status info = 0
Header of extended diagnostic
data
10 - 13
VLT par. 16-05
VLT warning word
14 - 17
VLT par. 16-06
VLT status word
18 - 21
VLT par. 16-04
VLT alarm word
22 - 23
VLT par. 9-53
Communication warning word
(Profibus)
Enabling diagnosis may cause increased bus traffic.
Diagnosis functions are not supported by all fieldbus
types.
8-10 Control Word Profile
Option:
*
FC profile
[0]
58
MG.33.C2.02 - VLT is a registered Danfoss trademark
Содержание FC 300 Profibus
Страница 4: ...FC 300 Profibus Copyright FC 300 Profibus 4 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 6: ...FC 300 Profibus Safety Note FC 300 Profibus 6 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 18: ...FC 300 Profibus How to Install 18 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 24: ...FC 300 Profibus How to Configure the System 24 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 56: ...FC 300 Profibus How to Access FC 300 Parameters 56 MG 33 C2 02 VLT is a registered Danfoss trademark...