FC 300 Profibus
Parameters
- Disable: Disables process control via Profibus, and
enables process control via standard RS485.
- Enable cyclic master: Enables process control
via Profibus Master Class 1, and disables process
control via standard RS485 bus or Master class 2.
9-53 Profibus Warning Word
Option:
Bit:
Meaning:
0
Connection with DP-master is not
1
Timeout action active
2
FDL (Field-bus Data link Layer) is not ok
3
Clear data command received
4
Actual value is not updated
5
Baudrate search
6
PROFIBUS ASIC is not transmitting
7
Initializing of PROFIBUS is not ok
8
Drive is tripped
9
Internal CAN error
10
Wrong ID sent by PLC
11
Internal error occured
12
Not configured
13
Clear command received
14
Warning 34 active
Function:
Displays Profibus communication warnings.
9-63 Actual Baud Rate
Option:
Read only
[1]
9.6 kbit/s
[0]
19.2 kbit/s
[1]
93.75 kbit/s
[2]
187.5 kbit/s
[3]
500 kbit/s
[4]
1500 kbit/s
[6]
3000 kbit/s
[7]
6000 kbit/s
[8]
12000 kbit/s
[9]
31.25 kbit/s
[10]
45.45 kbit/s
[11]
No baudrate found
[255]
Function:
Displays the actual PROFIBUS baud rate. The
Profibus Master automatically sets the baud rate.
9-64 Device Identification
Array [10]
Option:
Read only
[255]
Array
[10]
Index
Content
Value
[0]
Manufacturer
128 (for Danfoss)
[1]
Device type
1
[2]
Version
xxyy
[3]
Firmware date year
yyyy
[4]
Firmware date month
ddmm
[5]
No. of axes
variable
[6]
Vendor specific: PB
Version
xxyy
[7]
Vendor specific:
Database Version
xxyy
[8]
Vendor specific: AOC
Version
xxyy
[9]
Vendor specific: MOC
Version
xxyy
Function:
The device identification parameter. The data type
is "Array[n] of Unsigned16“. The assignment of the
first subindexes is defined and shown in the table
above.
9-65 Profile Number
Option:
Read only
0. - 0.
*
0.
Function:
Contains the profile identification. Byte 1 contains
the profile number and byte 2 the version number
of the profile.
9-67 Control Word 1
Range:
Read only
No LCP access
0. - 65535.
*
0.
Function:
Accepts the Control word from a Master Class 2 in
the same format as PCD 1. If control priority is set
to Master Class 2, the Control word for the drive
is taken from this parameter, whereas cyclical and
acyclic reference from a Master Class 2 is ignored.
This parameter is only visible for Profibus Master
Class 2, not for Master Class 1, standard bus or LCP.
9-68 Status Word 1
Range:
Read only
No LCP access
0. - 65535.
*
0.
63
MG.33.C2.02 - VLT is a registered Danfoss trademark
Содержание FC 300 Profibus
Страница 4: ...FC 300 Profibus Copyright FC 300 Profibus 4 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 6: ...FC 300 Profibus Safety Note FC 300 Profibus 6 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 18: ...FC 300 Profibus How to Install 18 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 24: ...FC 300 Profibus How to Configure the System 24 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 56: ...FC 300 Profibus How to Access FC 300 Parameters 56 MG 33 C2 02 VLT is a registered Danfoss trademark...