FC 300 Profibus
How to Configure the System
The next step is to set up the peripheral input and
output data. Data set up in the peripheral area is
transmitted cyclically via PPO types. In the example
below, a PPO type 6 Word consistent is dragged and
dropped to the first slot.
See the PPO types section in
How to Control the FC
300
for more information.
The configuration tool automatically assigns addresses in the peripheral address area. In this example the
input and output area have the following configuration:
PPO type 6:
PCD read (VLT to PLC)
PCD word
number
1
2
3
4
Input address
256-257
258-259
260-261
262-263
Set-up
STW
MAV
Par. 9-16.2
Par. 9-16.3
PCD write (PLC to VLT)
PCD word
number
1
2
3
4
Output address
256-257
258-259
260-261
262-263
Set-up
CTW
MRV
Par. 9-15.2
Par. 9-15.3
In PCDs 3 and 4 it is possible to assign Process signals. See an example of this in the
Application Examples
chapter.
Download the configuration file to the PLC. The PROFIBUS system should be able to go online and it will start
to exchange data when the PLC is set to Run mode.
22
MG.33.C2.02 - VLT is a registered Danfoss trademark
Содержание FC 300 Profibus
Страница 4: ...FC 300 Profibus Copyright FC 300 Profibus 4 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 6: ...FC 300 Profibus Safety Note FC 300 Profibus 6 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 18: ...FC 300 Profibus How to Install 18 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 24: ...FC 300 Profibus How to Configure the System 24 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 56: ...FC 300 Profibus How to Access FC 300 Parameters 56 MG 33 C2 02 VLT is a registered Danfoss trademark...