Extended Diagnosis
Using the extended diagnosis function, alarm and warning information can be received from the frequency
converter. The setting of par. 8-07
Diagnosis trigger
determines which frequency converter events should
trigger the extended diagnosis function.
When par. 8-07
Diagnosis trigger
is set to Disable [0], no extended diagnosis data are sent regardless of
whether they appear in the frequency converter.
When par. 8-07
Diagnosis trigger
is set to Alarms [1], extended diagnosis data are sent when one or more
alarms arrive in the alarm par. 16-90
Alarm word
or 9-53
Warning word
.
When par. 8-06 is set to Alarms/Warnings [2], extended diagnosis data are sent if one or more
alarms/warnings arrive in the alarm par. 16-90
Alarm word
or 9-53
Warning word
, or in the warning par.
16-92
Warning word
.
The extended diagnosis sequence is as follows: If an alarm or warning appears, the frequency converter
will indicate that to the master by sending a high priority message via the output data telegram. This will
cause the master to send a request for extended diagnosis information to the frequency converter, to
which the frequency converter will reply. When the alarm or warning disappears, the frequency converter
will again indicate that to the master, and on the following request from the master, return a standard
DP diagnosis frame (6 bytes).
The content of the extended diagnosis frame is as follows:
Byte
Bit no.
Name
0 to 5
Standard DP Diagnosis data
6
PDU length
7
0-7
Status type =0x81
8
8-15
Slot = 0
9
16-23
Status Information
10
24-31
Frequency converter alarm word (par. 16-04)
11
32-39
Frequency converter alarm word (par. 16-04)
12
40-47
Frequency converter alarm word (par. 16-04)
13
48-55
Frequency converter alarm word (par. 16-04)
14
56-63
Reserved for future use
15
64-71
Reserved for future use
16
72-79
Reserved for future use
17
80-87
Reserved for future use
18
88-95
Frequency converter warning word (par. 16-05)
19
96-103
Frequency converter warning word (par. 16-05)
20
104-111
Frequency converter warning word (par. 16-05)
21
112-119
Frequency converter warning word (par. 16-05)
22
120-127
Reserved for future use
23
128-135
Reserved for future use
24
136-143
Reserved for future use
25
144-151
Reserved for future use
26
152-159
PROFIBUS warning word (par. 9-53)
27
160-167
PROFIBUS warning word (par. 9-53)
28
168-175
Reserved for future use
29
176-183
Reserved for future use
30
184-191
Reserved for future use
31
192-199
Reserved for future use
83
MG.33.C2.02 - VLT is a registered Danfoss trademark
Содержание FC 300 Profibus
Страница 4: ...FC 300 Profibus Copyright FC 300 Profibus 4 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 6: ...FC 300 Profibus Safety Note FC 300 Profibus 6 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 18: ...FC 300 Profibus How to Install 18 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 24: ...FC 300 Profibus How to Configure the System 24 MG 33 C2 02 VLT is a registered Danfoss trademark...
Страница 56: ...FC 300 Profibus How to Access FC 300 Parameters 56 MG 33 C2 02 VLT is a registered Danfoss trademark...