34-54 Master Index
Position
34-55 Curve Position
34-56 Track Error
34-57 Synchronizing
Error
34-58 Actual Velocity
34-59 Actual Master
Velocity
34-60 Synchronizing
Status
34-61 Axis Status
34-62 Program Status Select the process read data for I/O Assembly Instances
101/151. Elements [2] and [3] of this array can be selected.
Elements [0] and [1] of the array are fixed.
10-13 Warning Parameter
Range:
Function:
0
*
[0 - 65535]
View a DeviceNet-specific Warning word. One bit is assigned to
every warning. Please refer to the DeviceNet Operating Instruc-
tions (MG.33.DX.YY) for further information.
Bit:
Meaning:
0
Bus not active
1
Explicit connection timeout
2
I/O connection
3
Retry limit reached
4
Actual is not updated
5
CAN bus off
6
I/O send error
7
Initialization error
8
No bus supply
9
Bus off
10
Error passive
11
Error warning
12
Duplicate MAC ID Error
13
RX queue overrun
14
TX queue overrun
15
CAN overrun
10-14 Net Reference
Read only from LCP.
Select the reference source in Instance 21/71 and 20/70.
[0]
*
Off
Enables reference via analog/digital inputs.
[1]
On
Enables reference via the fieldbus.
10-15 Net Control
Read only from LCP.
FC 100/ 200/ 300 DeviceNet
6. Parameters
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
63
6
Содержание FC 100 Series
Страница 4: ...1 Introduction FC 100 200 300 DeviceNet 4 MG 33 D3 02 VLT is a registered Danfoss trademark 1...
Страница 12: ...2 How to Install FC 100 200 300 DeviceNet 12 MG 33 D3 02 VLT is a registered Danfoss trademark 2...
Страница 18: ...3 How to Configure the System FC 100 200 300 DeviceNet 18 MG 33 D3 02 VLT is a registered Danfoss trademark 3...
Страница 38: ...5 How to Access the Parameters FC 100 200 300 DeviceNet 38 MG 33 D3 02 VLT is a registered Danfoss trademark 5...
Страница 52: ...6 Parameters FC 100 200 300 DeviceNet 52 MG 33 D3 02 VLT is a registered Danfoss trademark 6...
Страница 68: ...7 Application Examples FC 100 200 300 DeviceNet 68 MG 33 D3 02 VLT is a registered Danfoss trademark 7...
Страница 72: ...8 Troubleshooting FC 100 200 300 DeviceNet 72 MG 33 D3 02 VLT is a registered Danfoss trademark 8...