5.5. Reading/Writing to Parameters with Index
Indexed parameters such as 10-11 or 10-12 need special handling since DeviceNet does not sup-
port indexed addressing. The way to handle this in the frequency converter is to use par. 10-30
Parameter Data Types
, which serves as an index pointer. Set up the pointer before each read/
write of an indexed parameter.
NB!
If two masters access this feature at the same time, incorrect data may be gener-
ated.
5.5.1. Example
Write 16-10 in index 2 in par. 10-12
Process Data Config Read
.
First, set up the index pointer in par. 10-30
Array Index
. In this example index 2:
The next step is to write the data (in this ex-
ample 16-10) to par. 10-12.
Class
Instance Attribute Value
110 Dec
1 Dec
130 Dec
2 Dec
6E Hex
1 Hex
82 Hex
2 Hex
Class
Instance Attribute Value
110 Dec
1 Dec
112 Dec
1610 Dec
6E Hex
1 Hex
70 Hex
64A Hex
FC 100/ 200/ 300 DeviceNet
5. How to Access the Parameters
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
51
5
Содержание FC 100 Series
Страница 4: ...1 Introduction FC 100 200 300 DeviceNet 4 MG 33 D3 02 VLT is a registered Danfoss trademark 1...
Страница 12: ...2 How to Install FC 100 200 300 DeviceNet 12 MG 33 D3 02 VLT is a registered Danfoss trademark 2...
Страница 18: ...3 How to Configure the System FC 100 200 300 DeviceNet 18 MG 33 D3 02 VLT is a registered Danfoss trademark 3...
Страница 38: ...5 How to Access the Parameters FC 100 200 300 DeviceNet 38 MG 33 D3 02 VLT is a registered Danfoss trademark 5...
Страница 52: ...6 Parameters FC 100 200 300 DeviceNet 52 MG 33 D3 02 VLT is a registered Danfoss trademark 6...
Страница 68: ...7 Application Examples FC 100 200 300 DeviceNet 68 MG 33 D3 02 VLT is a registered Danfoss trademark 7...
Страница 72: ...8 Troubleshooting FC 100 200 300 DeviceNet 72 MG 33 D3 02 VLT is a registered Danfoss trademark 8...