![Danfoss FC 100 Series Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/danfoss/fc-100-series/fc-100-series_manual_3792948053.webp)
6. Parameters
8-01 Control Site
Option:
Function:
[0]
*
Digital and ctrl. word Control by using both digital input and control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Control word only
Control by using control word only.
The setting in this parameter overrides the settings in par. 8-50 to 8-56.
8-02 Control Word Source
Option:
Function:
[0]
None
[1]
FC RS485
[2]
FC USB
[3]
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
[30]
External Can
Select the source of the control word: one of two serial interfa-
ces or four installed options. During initial power-up, the fre-
quency converter automatically sets this parameter to
Option
A
[3] if it detects a valid fieldbus option installed in slot A. If the
option is removed, the frequency converter detects a change in
the configuration, sets par. 8-02 back to default setting
FC
RS485
, and the frequency converter then trips. If an option is
installed after initial power-up, the setting of par. 8-02 will not
change but the frequency converter will trip and display: Alarm
67
Option Changed
.
This parameter cannot be adjusted while the motor is running.
8-03 Control Word Timeout Time
Range:
Function:
1.0s
*
[0.1 - 18000.0 s]
Enter the maximum time expected to pass between the recep-
tion of two consecutive telegrams. If this time is exceeded, it
indicates that the serial communication has stopped. The func-
tion selected in par. 8-04
Control Word Time-out Function
will
then be carried out. The time-out counter is triggered by a valid
control word.
8-04 Control Word Timeout Function
Option:
Function:
[0]
*
Off
[1]
Freeze Output
[2]
Stop
FC 100/ 200/ 300 DeviceNet
6. Parameters
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
53
6
Содержание FC 100 Series
Страница 4: ...1 Introduction FC 100 200 300 DeviceNet 4 MG 33 D3 02 VLT is a registered Danfoss trademark 1...
Страница 12: ...2 How to Install FC 100 200 300 DeviceNet 12 MG 33 D3 02 VLT is a registered Danfoss trademark 2...
Страница 18: ...3 How to Configure the System FC 100 200 300 DeviceNet 18 MG 33 D3 02 VLT is a registered Danfoss trademark 3...
Страница 38: ...5 How to Access the Parameters FC 100 200 300 DeviceNet 38 MG 33 D3 02 VLT is a registered Danfoss trademark 5...
Страница 52: ...6 Parameters FC 100 200 300 DeviceNet 52 MG 33 D3 02 VLT is a registered Danfoss trademark 6...
Страница 68: ...7 Application Examples FC 100 200 300 DeviceNet 68 MG 33 D3 02 VLT is a registered Danfoss trademark 7...
Страница 72: ...8 Troubleshooting FC 100 200 300 DeviceNet 72 MG 33 D3 02 VLT is a registered Danfoss trademark 8...