![Danfoss FC 100 Series Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/danfoss/fc-100-series/fc-100-series_manual_3792948019.webp)
3. How to Configure the System
3.1. Configure the DeviceNet Network
All DeviceNet stations that are connected to
the same bus network must have a unique
station address. The DeviceNet address of the
frequency converter can be selected via:
-
Hardware switches (default 63)
-
Parameter 10-02
MAC ID
(default
63)
-
Class code 0X03, Instance 1, Attrib-
ute 1
3.1.1. Setting the DeviceNet Address using the Hardware Switches
Setting the DeviceNet Address using the Hardware Switches: Using the hardware switches it is
possible to select an address range from 0-63 (factory setting 63) according to the table below:
Switch
8
7
6
5
4
3
2
1
Address value
-
-
+32
+16
+8
+4
+2
+1
Ex. address 5
-
-
OFF
OFF
OFF
ON
OFF
ON
Ex. address 20
-
-
OFF
ON
OFF
ON
OFF
OFF
Ex. address 35
-
-
ON
OFF
OFF
OFF
ON
ON
NB!
Switch off the power supply before changing the hardware switches.
The address change will come into effect at the next power-up, and can be read in par. 10-02
MAC ID
.
3.1.2. Setting the DeviceNet Address via Par. 10-02
MAC ID
The address can be set via par. 10-02
MAC ID
if the hardware switches are set to 63 (factory
setting). The address change will come into effect at the next power-up.
3.1.3. Setting the DeviceNet Address with the Object Class Code
0x03, Attribute 1, Instance 1
The address can be set via the DeviceNet object class code 0x03 attribute 1 command if the
hardware switch is set to 63 (factory setting). A new address becomes effective immediately after
the class code 0x03, Instance 1, Attribute 1 command.
FC 100/ 200/ 300 DeviceNet
3. How to Configure the System
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
19
3
Содержание FC 100 Series
Страница 4: ...1 Introduction FC 100 200 300 DeviceNet 4 MG 33 D3 02 VLT is a registered Danfoss trademark 1...
Страница 12: ...2 How to Install FC 100 200 300 DeviceNet 12 MG 33 D3 02 VLT is a registered Danfoss trademark 2...
Страница 18: ...3 How to Configure the System FC 100 200 300 DeviceNet 18 MG 33 D3 02 VLT is a registered Danfoss trademark 3...
Страница 38: ...5 How to Access the Parameters FC 100 200 300 DeviceNet 38 MG 33 D3 02 VLT is a registered Danfoss trademark 5...
Страница 52: ...6 Parameters FC 100 200 300 DeviceNet 52 MG 33 D3 02 VLT is a registered Danfoss trademark 6...
Страница 68: ...7 Application Examples FC 100 200 300 DeviceNet 68 MG 33 D3 02 VLT is a registered Danfoss trademark 7...
Страница 72: ...8 Troubleshooting FC 100 200 300 DeviceNet 72 MG 33 D3 02 VLT is a registered Danfoss trademark 8...