Apart from wizard setup, users can also use the following section which describes quick parameter
settings for general applications.
Quick guide for parameter selection
Make sure that main switch is OFF before changing
the settings. The setting will depend on the system
requirement.
Parameter:
R012
Main Switch
Select predefined Danfoss valve type ETS, ETS C, KVS,
KVS C, CCM, CCMT, CTR, or user defined.
Parameter:
I067
Valve configuration
Analog signal type
e.g 1- 5V / 0 - 10V.
Parameter
I033
Driver
reference configuration,
I034
Ext ref voltage low,
I035
Ext ref. voltage high
Start : Main switch= Off
Select valve type
Application mode
Driver- Controller
Select how you want to use EKE: driver or superheat
controller.
Parameter:
R102
Operation mode
Select Refrigerant
Select Pressure transmitter
Define Min/Max Pressure
Select Superheat Control
Set Min/Max Ref value
Select Other features
Finish: main switch = ON
Select the predefined refrigerant
.
Parameter:
O030
Refrigerant
Select Pressure transmitter type –AKS 32R, Sensata
112CP, OEM Ratio, NSK, AKS 32 1 - 5 V,
OEM Voltage, Bus shared
Parameter:
I085
- Pe transmitter configuration.
Check parameter list for other sensors.
Define min and max Pressure transmitter in barg.
Parameter:
O020
- Pe min.,
O021
Pe max., Check
parameter list for other sensors.
Select application control type SH control. 1: MSS,
2: LoadAp, 3: Fixed, 4: Delta SH.
Parameter:
N021
SH reference mode.
Set the value for the selected control min./max.
superheat reference.
Parameter
N009
SH max.,
N010
- SH min.
Optional – Force start up, MOP, LOP, Alarm,
Thermostat function.
Check parameter list for details.
Remember to turn on main switch to start ‘ON’ .
Parameter
R012
Main switch
.
Driver
Controller
Select Temperature sensor
Select Temperature sensor type: EKS, ACCPBT, MBT,
Sensata 112CP, Bus shared
Parameter:
I081
- S2 sensor configuration.
Check parameter list for other sensors
.