Parameter

PNU

Default Description

R012

 Main switch

3001

0

0 = regulation Off | 1 = regulation On

R102

 Operation mode

3002

0

0 = Superheat control | 1 = Valve driver

I033

 Driver reference 

          configuration

3131

0 = Voltage to OD | 1 = Current to OD | 2 = Modbus to OD | 
3 = Modbus to steps

I034 

Ext ref. voltage low

3130

0

Range 0 – 10 V. To be used with 

I033

I035 

Ext ref. voltage high

3129

10

Range 0 – 10 V. To be used with 

I033

I067

 Valve configuration

3132

 0

0

 

= no valve,

 

1

 

= UserDef

2

 = ETS 12C, 

3

 = ETS 24C, 

4

 = ETS 25C,

 

5

 = ETS 50C, 

6

 = ETC 100C

7

 

= ETS 6,

 

8

 

=

 

ETS 12.5

9

 

= ETS 25

10

 

= ETS 50

11

 

= ETS 100,

12

 

= ETS 250

13

 = ETS 400

14

 = KVS 2C, 

15

 = KVS 3C, 

16

 = KVS 5C

17

 

= KVS 15,

 

18

 

= KVS 42

 

19

 = CCMT 0, 

20

 = CCMT 1

21

 

= CCMT 2,

 

22

 

= CCMT 4,

 

23

 

= CCMT 8,

 

24

 

= CCMT 16,

 

25

 

= CCMT 24, 

26

 

= CCMT 30,

 

27

 

= CCMT 42

 

28

 = CCM 10, 

29

 = CCM 20, 

30

 = CCM 30, 

31

 = CCM 40

32

 

= CTR 20

O030

 Refrigerant

3017

0

0 = Undef

9 = R500

18 = R402A 27 = R600a

36 = XP10

1 =  R12

10 = R503

19 = R404A 28 = R744

37 = R407F

2 = R22

11 = R114

20 = R407C

29 = R1270

38 = R1234ze

3 = R134A 12 = R142b

21 = R407A 30 = R417A

39 = R1234yf

4 = R502

13 = R User

22=R407B

31 = R422A

40 = 448A

5 = R717

14 = R32

23 = R410A 32 = R413A

41 = 449A

6 = R13

15 = R227

24 = R170

33 = R422D

42 = 452A

7 = R13b1 16 = R401

25 = R290

34 = 427A

8 = R23

17 = R507

26 = R600

35 = R438A

I081 

S2 sensor configuration

3266

0

0 = Not defined | 1 = EKS 221 | 2 = ACCPBT NTC10K | 3 = MBT 153 10K | 
4 = 112CP | 5 = Bus Shared

I083 

S3 sensor configuration

3106

0

0 = Not defined | 1 = EKS 221 | 2 = ACCPBT NTC10K | 3 = MBT 153 10K | 
4 = 112CP | 5 = Bus Shared

I084

 S4 sensor configuration 

3262

0

0 = Not defined | 1 = EKS 221 | 2 = ACCPBT NTC10K | 3 = MBT 153 10K | 
4 = 112CP | 5 = Bus Shared

I085

 Pe transmitter configuration

3270

0

0 = Not defined | 1 = AKS 32R | 2 = ACCPBP Ratio | 3 = 112CP | 4 = OEM Ratio| 
5 = NSK | 6 = AKS 32 1-5V | 7 = OEM Voltage | 8 = Bus shared

O020

 Pe transmitter min. (in bar g)

3115

-1

Define pressure range in bar gauge

O021

 Pe transmitter max. (in bar g)

3116

12

Define pressure range in bar gauge

N021

 SH reference mode

3027

2

0 = Fixed SH | 1 = Loadap | 2 = MSS | 3 = Delta temp

N107

 SH fixed setpoint ( K)

3028

7

Range 2 – 40 K

N009

 SH max. ( K)

3029

9

Range 4 – 40 K

N010

 SH min. ( K)

3030

4

Range 2 – 9 K

N116

 SH ref. delta temp. factor ( %)

3035

65

Range 20 – 100

EKE 1B – Commonly used parameter  identification

 

PNU

 - equivalent to the Modbus register no. (Modbus a1).

Actual value are read/written as 16-bit integer values without decimals. This is the default value as read via Modbus.

For a detailed parameter list and explanation, please check the EKE data sheet.

Содержание EKE 1B

Страница 1: ...eat must be accurately controlled typically in commercial air conditioning heat pumps commercial refrigeration food retailing and industrial applications Compatible valves Danfoss ETS 6 ETS ETS Colibr...

Страница 2: ...cle Normally Open 3 A Inductive AC 15 250 V AC 100 k cycle Normally Closed 2 A General purpose 250 V AC 100 k cycle Stepper motor Bipolar unipolar 1 Stepper valves A1 A2 A3 A4 Bipolar and unipolar ste...

Страница 3: ...e user INSTALLATION WARNINGS Recommended mounting position vertical Installation must comply with local standards and legislation Before working on the electrical connections disconnect the device fro...

Страница 4: ...C1 NC1 PWR 24V Vbat STEPPER VALVE DIGITAL OUTPUT Superheat controller EKE 1B 080G5350 DKRCC PI RS0 C6 02 4 DIN rail mounting demounting The unit can be mounted onto a 35 mm DIN rail simply by snapping...

Страница 5: ...troller EKE 1B 080G5350 DKRCC PI RS0 C6 02 5 Connection overview EKE 1B Master controller Pressure transmitter e g AKS 32R Power supply 24 V AC 20 24 V DC 20 2 5 A T fuse optional Batt backup optional...

Страница 6: ...tant Note Mount the sensor on a clean paint free surface Remember to use heat conducting paste and insulate the sensor For precise measurements mount the sensor max 5 cm from the outlet of the evapora...

Страница 7: ...min max m m2 Analog inputs Current Voltage max 10 0 14 1 5 Temperature sensor max 10 Stepper valve connection max 30 0 14 1 5 Power supply max 5 0 2 2 5 Digital input max 10 0 14 1 5 Digital output 0...

Страница 8: ...er motor valves Long cables will lead to degradation of performance You can overcome this degradation by changing the settings for the valve driver This guideline is based on the cable type being the...

Страница 9: ...PC you must Connect terminals R and H on MMIMYK CAN port using a termination wire Place cable holder close to MMIMYK to keep USB connector firmly in place Keep USB cable length 1 m Place MMIMYK and ro...

Страница 10: ...n controller and display is 3 m over CAN RJ CANbus requires termination in both ends of the cable by a 120 Ohm resistor to ensure reliable communication Connecting external MMIGRS2 display MMIGRS2 dis...

Страница 11: ...ation and d Output configuration When using the Setup Wizard repeat the following sequence for all parameter settings a From Setup wizard select relevant parameters b Press ENTER to highlight 1st opti...

Страница 12: ...ressure Select Superheat Control Set Min Max Ref value Select Other features Finish main switch ON Select the predefined refrigerant Parameter O030 Refrigerant Select Pressure transmitter type AKS 32R...

Страница 13: ...2 R413A 41 449A 6 R13 15 R227 24 R170 33 R422D 42 452A 7 R13b1 16 R401 25 R290 34 427A 8 R23 17 R507 26 R600 35 R438A I081 S2 sensor configuration 3266 0 0 Not defined 1 EKS 221 2 ACCPBT NTC10K 3 MBT...

Страница 14: ...Danfoss DCS az 2018 06 DKRCC PI RS0 C6 02 14 For your own notes...

Страница 15: ...logging Pressure Transducer Temperature Sensor AKS Pressure Tranducer Available with ratiometric and 4 20 mA NSK Ratiometric pressure probe XSK Pressure probe 4 20 mA PT 1000 AKS is a High precision...

Отзывы: