Stepper Motor Output

 

•  All valves are driven in a bipolar mode with a 24 V supply chopped to control the current (Current driver). 
•  The stepper motor is connected to the “Stepper Valve” terminals (see terminal assignment) with a standard M12  
    connection cable. 
•  To configure stepper motor valves  other than Danfoss stepper motor valves, the correct valve parameters must
    be set as described in the Valve configuration section (see manual for details).
•  The default valve setting in EKE 1B is: none.
•  The correct valve must be defined in “Valve configuration”, i.e. parameter I067. An overview of valve types is 
    given in the “Parameter identification” section.

  Valve Cable Connection  

   ETS Colibri / KVS Colibri/ ETS / KVS / CCM / CCMT / CTR

Danfoss M12 Cable

White

Black

Red 

Green

ETS/KVS / CCM Pins

3

4

1

2

ETS Colibri® / KVS Colibri / CCMT / CTR/ Pins

A1

A2

B1

B2

EKE terminals

A1

A2

B1

B2

Pin designation used in above table are shown in the product data sheet.

  ETS 6 

 

   

Wire color

Orange

Yellow 

Red

Black

Gray

EKE terminals

A1

A2

B1

B2

Not connected

Guideline for long M12 cables on Danfoss stepper motor valves

•  Long cables will lead to degradation of performance.
•  You can overcome this degradation by changing the settings for the valve driver. This guideline is based on  
       the cable type being the same type as the standard Danfoss stepper motor cable.

Recommended wire size and cable distance between EKE controller and stepper motor valve
Cable length

1 m – 15 m

15 m – 30 m

30 m – 50 m

Wire diameter

0.52 / 0.33 mm

2

(20 / 22 AWG)

0.33 mm

2

(20 AWG)

0.82 mm

2

(18 AWG)

Parameter setting for long M12 cable

Product

0 m – 15 m cable

15 m – 30 m cable

30 m – 50 m cable

Update following parameter 

ETS 12C - ETS 100C
KVS 2C - KVS 5C

Use default values

I028

 Valve drive current= 

925 mA peak

I028

 Valve drive current = 1000 mA peak

I065

 Valve duty cycle = 90%

ETS 12.5 - ETS 400 
KVS 15 - KVS 42
CTR 20
CCMT 2 - CCMT 8
CCM 10 - CCMT 40

Use default values

I028

 Valve drive current= 

200 mA peak

I028

 Valve drive current= 300 mA peak

ETS 6

Use default values

I028

 Valve drive current= 

270 mA peak

I028

 Valve drive current= 350 mA peak

CCMT 0

Use default values

I028

 Valve drive current= 

270 mA peak

I028

 Valve drive current= 350mA peak

CCMT 1

Use default values

I028

 Valve drive current= 

400 mA peak

I028

 Valve drive current= 500 mA peak

CCMT 16 - CCMT 42

Use default values

I028

 Valve drive current= 

450 mA peak

I028

 Valve drive current= 500 mA peak

Содержание EKE 1B

Страница 1: ...eat must be accurately controlled typically in commercial air conditioning heat pumps commercial refrigeration food retailing and industrial applications Compatible valves Danfoss ETS 6 ETS ETS Colibr...

Страница 2: ...cle Normally Open 3 A Inductive AC 15 250 V AC 100 k cycle Normally Closed 2 A General purpose 250 V AC 100 k cycle Stepper motor Bipolar unipolar 1 Stepper valves A1 A2 A3 A4 Bipolar and unipolar ste...

Страница 3: ...e user INSTALLATION WARNINGS Recommended mounting position vertical Installation must comply with local standards and legislation Before working on the electrical connections disconnect the device fro...

Страница 4: ...C1 NC1 PWR 24V Vbat STEPPER VALVE DIGITAL OUTPUT Superheat controller EKE 1B 080G5350 DKRCC PI RS0 C6 02 4 DIN rail mounting demounting The unit can be mounted onto a 35 mm DIN rail simply by snapping...

Страница 5: ...troller EKE 1B 080G5350 DKRCC PI RS0 C6 02 5 Connection overview EKE 1B Master controller Pressure transmitter e g AKS 32R Power supply 24 V AC 20 24 V DC 20 2 5 A T fuse optional Batt backup optional...

Страница 6: ...tant Note Mount the sensor on a clean paint free surface Remember to use heat conducting paste and insulate the sensor For precise measurements mount the sensor max 5 cm from the outlet of the evapora...

Страница 7: ...min max m m2 Analog inputs Current Voltage max 10 0 14 1 5 Temperature sensor max 10 Stepper valve connection max 30 0 14 1 5 Power supply max 5 0 2 2 5 Digital input max 10 0 14 1 5 Digital output 0...

Страница 8: ...er motor valves Long cables will lead to degradation of performance You can overcome this degradation by changing the settings for the valve driver This guideline is based on the cable type being the...

Страница 9: ...PC you must Connect terminals R and H on MMIMYK CAN port using a termination wire Place cable holder close to MMIMYK to keep USB connector firmly in place Keep USB cable length 1 m Place MMIMYK and ro...

Страница 10: ...n controller and display is 3 m over CAN RJ CANbus requires termination in both ends of the cable by a 120 Ohm resistor to ensure reliable communication Connecting external MMIGRS2 display MMIGRS2 dis...

Страница 11: ...ation and d Output configuration When using the Setup Wizard repeat the following sequence for all parameter settings a From Setup wizard select relevant parameters b Press ENTER to highlight 1st opti...

Страница 12: ...ressure Select Superheat Control Set Min Max Ref value Select Other features Finish main switch ON Select the predefined refrigerant Parameter O030 Refrigerant Select Pressure transmitter type AKS 32R...

Страница 13: ...2 R413A 41 449A 6 R13 15 R227 24 R170 33 R422D 42 452A 7 R13b1 16 R401 25 R290 34 427A 8 R23 17 R507 26 R600 35 R438A I081 S2 sensor configuration 3266 0 0 Not defined 1 EKS 221 2 ACCPBT NTC10K 3 MBT...

Страница 14: ...Danfoss DCS az 2018 06 DKRCC PI RS0 C6 02 14 For your own notes...

Страница 15: ...logging Pressure Transducer Temperature Sensor AKS Pressure Tranducer Available with ratiometric and 4 20 mA NSK Ratiometric pressure probe XSK Pressure probe 4 20 mA PT 1000 AKS is a High precision...

Отзывы: