Display view

Normal display on the controller can be set to read one of the following readings:

1:  Valve’s opening degree

2: Superheat

o17

Display mode

Only access via data communication

For Danfoss only

Factor for calculating the superheat reference

SHref = (S3-P0) x SHfactor / 100

n96

SH factor

Filter constant  (delay) for calculating the superheat reference

n97

Ref Filter

Other refrigerant

If the refrigerant type cannot be selected directly via settings 1 through 33, it can 

then be defined by the user. Select setting 13 and then set the refrigerant's three 

constants via AKM.

P0Rfg.Fac A1 

P0Rfg.Fac A2

P0Rfg.Fac A3

PcRfg.Fac A1

PcRfg.Fac A2

PcRfg.Fac A3

Service

Service

A number of controller values can be printed for use in a service situation
Read status of input DI (start/stop input)

u10

DI status

Read the temperature at the S3 sensor

u12

S3 Temp

Read the temperature at the S2 sensor

u20

S2 Temp

Read the control’s actual superheat

u21

SH

Read the control’s actual superheat reference

u22

SH Ref

Read the ETS valve’s opening degree

u24

Valve OD %

Reading the calculated closing value for superheating.

U19

SH Close

Reading the condensation pressure calculated for temperature

U20

Cond Temp Tc

Reading the condensation pressure (pressure at Pc)

U21

Cond Press Pc

Reading the evaporating pressure (pressure at P0) 

U25

Evap Press P0

Reading the evaporating pressure calculated for temperature 

U26

Evap Temp T0

Manual control of outputs

For service purposes the valve outputs can be forced

However only when regulation has been stopped.

0:  No override

1: Override: If the relay is defined for solenoid valve use in o36, the solenoid valve will 

open. The opening degree of the ETS or ICMTS valve can then be set via o45.

o18

Manual Ctrl

Manual control of the ETS valve

When ”o18” is activated (=1) the valve’s opening degree can be determined from this 

menu.

o45

Man Valve OD%

Operating status
The controller’s operating status can be called forth by a brief (1s) activation of the 

upper button. If a status code exists it will be shown. (Status codes have lower priority 

than alarm codes. This means that status codes cannot be seen if there is an active 

alarm code.

The individual status codes have the following meanings:

EKC State 

(0 = regulation)

S10 (off): Regulation stopped by the internal start/ stop.

10

S24: Regulation is in start-up mode

24

S44: Delay time, or the time it takes for system stability to be reached. Appears if one 

of the regulating sensors fails.

44

Содержание EKC 313

Страница 1: ...Controller for cascade systems with CO2 EKC 313 User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...e temperature exceeds 100 C Functions Output signal The controller has a voltage output on 0 10 V The signal can be used for Indicating the valve s opening degree when using an ETS valve Controlling t...

Страница 3: ...if the condensing pressure is low Optimised superheat regulation is used when the condensing pressure is above the set value If the condensing pressure falls below the set value the opti mised superhe...

Страница 4: ...result in a reduced opening degree When there is a drop out on the low pressure thermostat during start up the value must be raised a bit If there is pendling during start up the value must be reduced...

Страница 5: ...r second Must only be set when n03 is set to 5 Automatically set when n03 is set to 0 1 2 3 or 4 n38 Steps sec Miscellaneous Miscellaneous Address If the controller is built into a network with data c...

Страница 6: ...eating U19 SH Close Reading the condensation pressure calculated for temperature U20 Cond Temp Tc Reading the condensation pressure pressure at Pc U21 Cond Press Pc Reading the evaporating pressure pr...

Страница 7: ...ings Alarm destinations E1 Fault in controller Controller fault E15 Cut out S2 sensor S2 o c E16 Short circuited S2 sensor S2 s c E17 Cut out S3 sensor S3 o c E18 Short circuited S3 sensor S3 s c E20...

Страница 8: ...y n03 0 7 0 I Integration time Tn n05 5 s 600 s 90 D Differentiation time Td n06 0 s 60 s 0 Max value of superheat reference n09 3 K 60 K 40 Min value of superheat reference n10 3 K 40 K 10 MOP max Of...

Страница 9: ...verted to temperature u26 C Read calculated SH closing value U19 K Read Pc converted to temperature U20 C Read pressure at pressure transmitter Pc U21 bar Working range for pressure transmitter P0 max...

Страница 10: ...nnects when regulation requires a low valve open ing degree Alarm relay 12 and 13 are connected in case of alarm 21 22 23 24 Connecting an ETS valve Terminals 21 through 24 should not be used when usi...

Страница 11: ...3 A inductive Actuator ETS CCM CCMT Step motor ICAD mounted on ICMTS Voltage signal 0 10 V Output signal Voltage signal 0 10 V to either ICAD control or to signal for valves opening degree Data commun...

Страница 12: ...tions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to prevent this However a wrong installati...

Отзывы: