EKC
313
User
Guide RS8FZ402 © Danfoss 2015-07
9
Service
Read status of input DI
u10
on/off
Temperature at S3 sensor
u12
°C
Temperature at S2 sensor
u20
°C
Read actual superheat SH
u21
K
Read actual superheat reference
u22
K
Read ETS valves opening degree
u24
%
Read pressure at pressure transmitter P0
u25
bar
Read P0 converted to temperature
u26
°C
Read calculated SH closing value
U19
K
Read Pc converted to temperature
U20
°C
Read pressure at pressure transmitter Pc
U21
bar
Working range for pressure transmitter P0 - max. o48
6 bar
199 bar 12
Refrigerant for Pc circuit
Can olny be changed via AKM / service tool
----
0
35
28
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you recon nect the supply voltage