User 

Guide RS8FZ402 © Danfoss 2015-07 

EKC 

313

Function overview

Function

Para- 

meter

Parameter by operation via 

data communication

Normal display

Displays either the valve's actual opening degree or the actual superheat value.

(Desired value can be set in o17)

Briefly pushing the bottom button will display one of the two readings.

Briefly pushing both buttons will display the superheat reference (u22).

u24 /

u21

Valve OD %

SH

Control parameters

Injection control

Start/stop of regulation

This setting can be used to start and stop regulation. 

r12

Main Switch

I: Integration time Tn

If the Tn value is increased the regulation becomes slower

n05

Tn sec.

Lower limit value for the condensing pressure.  

If the pressure falls, the valve will start closing.

n98

Tc Ref

Max. opening degree

The valve's opening degree can be limited here. 

The setting is expressed as a % of the total opening degree. The voltage signal of 0-10 

V on the output will be limited correspondingly.

n32

OD% Max

Amplification factor for the superheat

This setting determines the valve’s opening degree as a function of the change in 

evaporating pressure. An increase of the evaporating pressure will result in a reduced 

opening degree. When there is a drop-out on the low-pressure thermostat during 

start-up the value must be raised a bit. If there is pendling during start-up the value 

must be reduced a little.

The value should only be changed by specially trained staff.

n20

Kp T0 

Kp value for amplification factor for PID regulation

n95

Kp Max

Kp value near reference value

Just around the reference this value will be used in stead of the "n95 value"

The value should only be changed by specially trained staff.

n19

Kp Min

Signal safety during start-up

The control function uses the value as start value for the valve’s opening degree at 

each thermostat cutin. By adaptive control the controller continuously calculates a 

new value.

The value should only be changed by specially trained staff.

n17

Start OD%

Start-up time for safety signal

If the controller does not obtain a reliable signal within this period of time the con-

troller will in other ways try to establish a stable signal. (A too high value may result in 

a flooded evaporator).

The value should only be changed by specially trained staff.

n15

StartUp time

MOP

If no MOP function is required, select pos. Off. (A value of max. (60) will correspond to 

Off)

n11

MOP (bar)

Min. value for the superheat reference

n10

SH Min

Max. value for the superheat reference

n09

SH Max

D: Differentiation time Td

n06

Td sec

Содержание EKC 313

Страница 1: ...Controller for cascade systems with CO2 EKC 313 User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...e temperature exceeds 100 C Functions Output signal The controller has a voltage output on 0 10 V The signal can be used for Indicating the valve s opening degree when using an ETS valve Controlling t...

Страница 3: ...if the condensing pressure is low Optimised superheat regulation is used when the condensing pressure is above the set value If the condensing pressure falls below the set value the opti mised superhe...

Страница 4: ...result in a reduced opening degree When there is a drop out on the low pressure thermostat during start up the value must be raised a bit If there is pendling during start up the value must be reduced...

Страница 5: ...r second Must only be set when n03 is set to 5 Automatically set when n03 is set to 0 1 2 3 or 4 n38 Steps sec Miscellaneous Miscellaneous Address If the controller is built into a network with data c...

Страница 6: ...eating U19 SH Close Reading the condensation pressure calculated for temperature U20 Cond Temp Tc Reading the condensation pressure pressure at Pc U21 Cond Press Pc Reading the evaporating pressure pr...

Страница 7: ...ings Alarm destinations E1 Fault in controller Controller fault E15 Cut out S2 sensor S2 o c E16 Short circuited S2 sensor S2 s c E17 Cut out S3 sensor S3 o c E18 Short circuited S3 sensor S3 s c E20...

Страница 8: ...y n03 0 7 0 I Integration time Tn n05 5 s 600 s 90 D Differentiation time Td n06 0 s 60 s 0 Max value of superheat reference n09 3 K 60 K 40 Min value of superheat reference n10 3 K 40 K 10 MOP max Of...

Страница 9: ...verted to temperature u26 C Read calculated SH closing value U19 K Read Pc converted to temperature U20 C Read pressure at pressure transmitter Pc U21 bar Working range for pressure transmitter P0 max...

Страница 10: ...nnects when regulation requires a low valve open ing degree Alarm relay 12 and 13 are connected in case of alarm 21 22 23 24 Connecting an ETS valve Terminals 21 through 24 should not be used when usi...

Страница 11: ...3 A inductive Actuator ETS CCM CCMT Step motor ICAD mounted on ICMTS Voltage signal 0 10 V Output signal Voltage signal 0 10 V to either ICAD control or to signal for valves opening degree Data commun...

Страница 12: ...tions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to prevent this However a wrong installati...

Отзывы: