10 

User 

Guide RS8FZ402 © Danfoss 2015-07 

EKC 

313

Necessary connections

Terminals:

25-26 

Supply voltage 24 V a.c.

18-19 

Pt 1000 sensor at the heat exchanger discharge on

 

the cool side (S2)

18-20 

Pt 1000 sensor at the heat exchanger input on 

 

the warm side (S3)

14,15,16 Type AKS 2050* pressure transmitter, -1 to 59 bar.

 

Mounted at the heat exchanger's inlet on 

 

the warm side (Pc)

14,16,17 Type AKS 32R* pressure transmitter, -1 to 12 bar. 

 

Mounted at the heat exchanger discharge on 

 

the cold side (P0)

Connections

Application dependent connections

Terminals:

1-2 

DI input for external main switch (also see r12). If no 

switch is mounted, the terminals should be short circuited.

12-13   Relay for controlling solenoid valve in liquid line or the    

 

relay can be used as alarm relay (see o36).

Valve control: 12 and 13 are connected under normal 

operating conditions and interrupted supply voltage. 

Disconnects when regulation requires a low valve open-

ing degree.

Alarm relay: 12 and 13 are connected in case of alarm.

21,22,23,24 Connecting an ETS valve. (Terminals 21 through 24 

should not be used when using an ICMTS valve instead 

of an ETS valve. ICMTS valves should be controlled via the 

0-10 V signal on terminals 5 and 6.)   

5-6 

Voltage output 0-10 V. Can be used for the valve's opening 

degree signal or to control an ICMTS valve.

 

(For a special use with a solid state relay and AKV, the 

output will pulse with 10 V on/off)

3-4  

Data communication

 

Mount only, if a data communication module has been 

mounted.

It is important that the installation of the data communi-

cation cable be done correctly. Cf. separate literature No. 

RC8AC...

At opening degree: 10 V = 100% open valve

At signal to ICAD/ICMTS: 10 V = Open valve

8 VA

Cable connection

060G1034

14 = black

15 = brown

16 = blue

AKS 11: Max. 100°C

AKS 21: Max. 180°C

L > 5 m, see page 12

 5,6   25,26 

l

Earthing will damage the 

controller

*) For explosive applications an intrinsically safe pressure transmitter can 

be used. Connection is shown on page 12.

Содержание EKC 313

Страница 1: ...Controller for cascade systems with CO2 EKC 313 User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...e temperature exceeds 100 C Functions Output signal The controller has a voltage output on 0 10 V The signal can be used for Indicating the valve s opening degree when using an ETS valve Controlling t...

Страница 3: ...if the condensing pressure is low Optimised superheat regulation is used when the condensing pressure is above the set value If the condensing pressure falls below the set value the opti mised superhe...

Страница 4: ...result in a reduced opening degree When there is a drop out on the low pressure thermostat during start up the value must be raised a bit If there is pendling during start up the value must be reduced...

Страница 5: ...r second Must only be set when n03 is set to 5 Automatically set when n03 is set to 0 1 2 3 or 4 n38 Steps sec Miscellaneous Miscellaneous Address If the controller is built into a network with data c...

Страница 6: ...eating U19 SH Close Reading the condensation pressure calculated for temperature U20 Cond Temp Tc Reading the condensation pressure pressure at Pc U21 Cond Press Pc Reading the evaporating pressure pr...

Страница 7: ...ings Alarm destinations E1 Fault in controller Controller fault E15 Cut out S2 sensor S2 o c E16 Short circuited S2 sensor S2 s c E17 Cut out S3 sensor S3 o c E18 Short circuited S3 sensor S3 s c E20...

Страница 8: ...y n03 0 7 0 I Integration time Tn n05 5 s 600 s 90 D Differentiation time Td n06 0 s 60 s 0 Max value of superheat reference n09 3 K 60 K 40 Min value of superheat reference n10 3 K 40 K 10 MOP max Of...

Страница 9: ...verted to temperature u26 C Read calculated SH closing value U19 K Read Pc converted to temperature U20 C Read pressure at pressure transmitter Pc U21 bar Working range for pressure transmitter P0 max...

Страница 10: ...nnects when regulation requires a low valve open ing degree Alarm relay 12 and 13 are connected in case of alarm 21 22 23 24 Connecting an ETS valve Terminals 21 through 24 should not be used when usi...

Страница 11: ...3 A inductive Actuator ETS CCM CCMT Step motor ICAD mounted on ICMTS Voltage signal 0 10 V Output signal Voltage signal 0 10 V to either ICAD control or to signal for valves opening degree Data commun...

Страница 12: ...tions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown Every possible safeguard is incorporated into our products to prevent this However a wrong installati...

Отзывы: