Service parameter(s) 37-85

32h

37  Time constant for return temperature limitation

Setting range

Factory setting

OFF / 1 ... 50

25

Controls how fast the actual return temperature adapts to the 

desired return temperature limitation.

Adjust the time constant for the return limitation. 
The setting will eliminate the difference
between the acceptable and the actual return
temperature. 
The difference is integrated to adjust the desired 
flow temperature.

OFF:

    The desired flow temperature will not be 

adjusted any further.

1: 

 

 The desired flow temperature will be 
adjusted quickly.

50: 

   The desired flow temperature will be 

adjusted slowly.

52  Closed valve / normal operation 

Setting range

Factory setting

ON / OFF

OFF

The heating circuit can be closed when the controller acts as slave 

and when DHW charging is active in the master. 

ON: 

   The valve in the heating circuit is closed* 

during active DHW charging in the master 
controller.

OFF: 

   The flow temperature control remains 

unchanged during active DHW charging in 
the master controller.

*  The desired flow temperature is set to 10 °C. 

The setting in line 52 must be considered if this controller is a 
slave.

85  Priority for return temperature limitation

Setting range

Factory setting

ON / OFF

OFF

Choose whether the return temperature limitation should 

overrule the set min. flow temperature limit (line 2).

ON:

  The min. flow temperature limit is overruled.

OFF:

  The min. flow temperature limit is not 

overruled.

Содержание ECL Comfort P30

Страница 1: ...7B C5 02 2005 10 VI 7B C5 02 2005 10 www danfoss com User s Guide Installer s Guide www danfoss com ECL Comfort Installer s Guide ECL Comfort User s Guide 087R8017 VI7BC502 087R8017 VI7BC502 Mixing c...

Страница 2: ...gs Shift button Adjust ment Controller mode Controller mode Manual operation used only at maintenance and service Scheduled operation Constant comfort temperature Constant setback temperature Standby...

Страница 3: ...ype 11 Mounting the ECL Comfort controller 12 Electrical connections 230 V a c 13 Electrical connections 24 V a c 14 Connecting and placing the temperature sensors 15 Adapting the ECL Comfort controll...

Страница 4: ......

Страница 5: ...and onwards The application P30 is very exible These are the basic principles Typically the ow temperature is always adjusted according to your requirements The ow temperature sensor S3 is the most i...

Страница 6: ...possible to con gure additional systems In this section you nd the most frequently used systems If your system is not quite as shown below nd the diagram which has the best resemblance with your syste...

Страница 7: ...10b 10 3 Boiler system with 3 way valve 10 4 Boiler system with 4 way rotary valve System diagrams in this instruction are principal drawings and do not contain all components which are necessary in...

Страница 8: ...sition the controller in the box Secure the controller with the xing screw Mounting on a DIN rail Mounting kit Order code No 087B1145 A mounting kit is necessary to mount the box with the controller o...

Страница 9: ...Installation 11b...

Страница 10: ...ty thermostat Establish these jumpers 1 5 10 and 2 to common N terminal 230 V a c connections with safety thermostat This circuit diagram is only valid if Danfoss actuators are used Establish these ju...

Страница 11: ...tor close alt thermo actuator 0 2 A 230 V a c 5 Phase for motor output 9 P1 Circulation pump 4 2 A 230 V a c 10 Phase for pump relay R1 Wire cross section 0 75 1 5 mm2 Electrical connections Max 2 x 1...

Страница 12: ...y thermostat Establish these jumpers 1 5 10 and 2 to common N terminal 24 V a c connections with safety thermostat This circuit diagram is only valid if Danfoss actuators are used Establish these jump...

Страница 13: ...V a c 5 24 V a c supply voltage for motor output 9 K1 Relay for circulation pump 4 2 A 24 V a c 10 24 V a c supply voltage for relay K1 K1 auxilliary relay coil 24 V a c Wire cross section 0 75 1 5 m...

Страница 14: ...nd 16 S2 Room temperature sensor ESM 10 19 and 16 S3 Flow temperature sensor ESM 11 ESMC ESMU 20 and 16 S4 Return temperature sensor ESM 11 ESMC ESMU Establish the jumper from 16 to common terminal Wi...

Страница 15: ...e sensor is mounted Return temperature sensor ESMU ESM 11 or ESMC The return sensor should always be placed in on a pipe with return water ow Room temperature sensor ESM 10 ECA 60 62 room panel or ECA...

Страница 16: ...poses section 32 line 141 Connection example without ECA 9010 If the override switch has goldplated contacts you can choose one of the following solutions or a combination of both Closed switch Closed...

Страница 17: ...r initializing the display will return to the standard display C on the yellow side of the ECL Card 8 0 3 6 9 12 15 18 21 24 1 0 2 3 5 C 3 The controller is now ready to control the chosen system You...

Страница 18: ...ttons to adjust the settings In some displays more than one setting or value can be adjusted Use the shift button to switch between the options Changing from one side of the ECL Card to the other When...

Страница 19: ...years months and days Set the correct time and date In case of a power break which lasts longer than 12 hours the time and the date have to be set again All other settings are stored as programmed Us...

Страница 20: ...a sensor is not mounted or is disconnected the display will indicate it as If the sensor is short circuited the display will indicate it as If you are in doubt remove the controller and check the ohmi...

Страница 21: ...the relevant button is pushed If pushed for more than 3 seconds the actuator continues to close or open the valve The thermo actuator activates the valve as long as the button is pushed If pushed for...

Страница 22: ...o values The setting of the desired room temperature has an in uence on the calculated ow temperature heat curve no matter if a room temperature sensor is connected or not Floor heating systems This c...

Страница 23: ...c set up 20b Parallel displacement Setting range Factory setting 15 20 0 If you want to adjust the parallel displacement of the heat curve push the shift button The symbol for the parallel displacemen...

Страница 24: ...l be ignored 18 C Temp Actual Accumulated outdoor temp outdoor temp Heating OFF Time Heating Heating This function can save energy by stopping the heating system when the outdoor temperature gets abov...

Страница 25: ...range Factory setting 10 110 C min 10 max 90 C The mentioned setting range and factory settings may vary from the settings related to your ECL Card The left end of the setting range blinks Adjust the...

Страница 26: ...ce The bar below the max value blinks Adjust the max in uence There are two basic principles for control of the room temperature in uence A Max room temperature limitation Use this limitation if your...

Страница 27: ...red ow temperature will be corrected to eliminate this di erence Example 1 The actual room temperature is 2 degrees too low The in uence at max limitation right corner of the display is set to 35 The...

Страница 28: ...bility 6 Running time of the motorized control valve Setting range Factory setting 5 250 sec 35 sec Set the running time of the motorized control valve according to the example This is the time it tak...

Страница 29: ...he integration time line 5 to its max value 999 sec Decrease the value for the proportional band line 4 until the system starts hunting with a constant amplitude it might be necessary to force the sys...

Страница 30: ...terminals See section 14 Mount the controller and switch on the power Insert the ECL Card with the yellow side facing you and push if necessary See section 15 Choose manual operation as controller mod...

Страница 31: ...date line A See section 17 Check that all settings in the controller sections 30 and 31 are set or that the factory settings comply with your requirements If your system di ers from the diagram shown...

Страница 32: ...section 20 1 Limit for heating cut out 10 30 C 18 C See section 21 2 Flow temperature min max limits 10 110 C min 10 max 90 C See section 22 3 Room temperature in uence 0 99 99 0 min 0 max 40 See sec...

Страница 33: ...lve exercise ON OFF OFF 24 Gear motor thermo actuator ON OFF ON 30 Return temperature limitation 10 110 C 50 C C 35 Return temperature in uence max limitation 9 9 0 9 9 2 0 36 Return temperature in ue...

Страница 34: ...h repeatedly to reach the lines numbered 10 and onwards Line 0 0 1 Value Range indicator Now you can move to any line of your choice Set the parameter value Check that you have entered all the require...

Страница 35: ...ddress A 2 Room panel ECA 60 62 or remote control ECA 61 63 with address B 3 5 Not used 11 Setback temperature dependent on outdoor temperature Setting range Factory setting OFF 29 10 C 15 C Below thi...

Страница 36: ...mizing time constant Setting range Factory setting OFF 10 59 OFF Optimizes the start and stop times for the comfort temperature period to obtain the best comfort at the lowest energy consumption The l...

Страница 37: ...his is done by integrating the di erence and adjusting the desired ow temperature OFF The adaptive funtion is cancelled 1 The desired temperature is adapted quickly 30 The desired temperature is adapt...

Страница 38: ...red system temperature is lowered to 10 C The min setting of the temperature line 2 section 22 is overruled Desired system temp C 10 C Time OFF No total stop Desired system temp C 10 C Time 22 Pump ex...

Страница 39: ...setting ON OFF ON Choose the actuator type for your valve ON Gear motor OFF Thermo actuator ABV type Control parameters lines 4 7 are overruled if thermo actuator is chosen OFF 30 Return temperature l...

Страница 40: ...t limit In uence lower than 0 The desired ow temperature is decreased when the return temperature gets higher than the set limit 0 In uence Max limitation 0 Return limit Return temp Max limitation 0 E...

Страница 41: ...t limit In uence lower than 0 The desired ow temperature is decreased when the return temperature gets below the set limit 0 In uence Min limitation 0 Return limit Return temp Min limitation 0 Example...

Страница 42: ...mperature will be adjusted slowly 52 Closed valve normal operation Setting range Factory setting ON OFF OFF The heating circuit can be closed when the controller acts as slave and when DHW charging is...

Страница 43: ...erridden 1 4 Select an unused sensor input S1 S4 for the override Connection example If the override switch has gold plated contacts you can choose one of the following solutions Closed switch Comfort...

Страница 44: ...d after the set activation delay A high value should be used for DHW installations with many consumers 189 Min activation time gear motor Setting range Factory setting 2 10 6 The min pulse length in m...

Страница 45: ...0 The slave receives information about the outdoor temperature S1 system time and signal for DHW demand in the master 1 9 The slave receives information about the outdoor temperature S1 system time an...

Страница 46: ...mode Desired room temperature Temperature which is set as the desired room temperature The temperature can only be controlled by the ECL Comfort controller if a room temperature sensor is installed I...

Страница 47: ...ature Temperature measured by the room temperature sensor room panel or remote control The room temperature can only be controlled directly if a sensor is installed The room temperature in uences the...

Страница 48: ...or thermostat does not limit the room temperature If you still cannot obtain the desired room temperature by adjusting the radiator thermostats the ow temperature is too low Increase the desired room...

Страница 49: ...2 seconds See section 4 How to restore your personal settings Insert the ECL Card with the yellow side facing you Go to line 9 is not displayed which is the second line below line 7 Select copy direct...

Страница 50: ...hangeover ime Periods with comfort temp are shown as black bars Time line Change the schedules Select appropriate day The changeover point blinks Adjust the rst blinking changeover point if required T...

Страница 51: ...he new period appears Adjust the new period Remove a comfort period Select the period to be removed blinking changeover point Push shift and buttons simultaneously for 2 seconds Cancel changes in your...

Страница 52: ...mbols mean Manual operation Used only at maintenance and service Note The protection against frost is switched o when this mode is selected Scheduled operation This is the normal mode The temperature...

Страница 53: ...m temperature for the setback mode Select the desired mode section 2 The setting of the desired room temperature is important even if a room temperature sensor room panel remote control is not connect...

Страница 54: ...control is installed If not two bars will be shown System information display B Line Flow temp State of controlled components 5 1 1 ON 0 3 6 B Return temp Today s schedule display C Line Outdoor temp...

Страница 55: ...r When operating the controller it is advisable to keep the lid open in order to view the entire display The ECL Card is divided vertically into two columns each representing a circuit Horizontally th...

Страница 56: ...ntation for the ECL Comfort controller is composed of numbered sections Only sections that are relevant to your ECL Comfort controller are included here Installer s Guide Grey sections 10 and onwards...

Отзывы: