Service parameters (10-199)
31
Circuit I
Lines Setting ranges
Factory settings Your settings
10
Choice of room panel / remote control
0 ... 5
0
11
Setback temperature dependent
on outdoor temperature
OFF / -29 ... 10 °C
-15 °C
°C
12
Boost
0 ... 99%
0%
%
14
Optimizing time constant
OFF / 10 ... 59
OFF
15
Adaptive function of room
temperature
OFF / 1 ... 30
OFF
20
Optimization based on room /
outdoor temperature
ON / OFF
OFF
21
Total stop
ON / OFF
OFF
22
Pump exercise
ON / OFF
ON
23
Valve exercise
ON / OFF
OFF
24
Gear motor / thermo actuator
ON / OFF
ON
30
Return temperature limitation
10 ... 110 °C
50 °C
°C
35
Return temperature influence
- max. limitation
-9.9 ... 0 ... 9.9
-2.0
36
Return temperature influence
- min. limitation
-9.9 ... 0 ... 9.9
0.0
37
Time constant for return temperature
limitation
OFF / 1 ... 50
25
52
Closed valve / normal operation
ON / OFF
OFF
85
Priority for return temperature
limitation
ON / OFF
OFF
141
Override input selection
OFF / 1 ... 4
OFF
174
Motor protection
OFF / 10 ... 59 min.
OFF
min.
189
Min. activation time, gear motor
2 ... 10
6
196
Service pin LON
ON / OFF
OFF
197
LON reset
ON / OFF
ON
198
Daylight saving time changeover
ON / OFF
ON
199
Master / slave address
0 ... 9, 15
15