The grey
side of the
ECL Card
Ex
tended ser
vic
e
32a
Service parameter(s) 10-11
10 Choice of room panel / remote control
Setting range
Factory setting
0 ... 5
0
Decides the communication with the room panel or remote
control.
Please note that the room panel / remote control is only active
if the system device bus is active. The bus is active when the
outdoor temperature sensor is connected.
Choose between
0:
No room panel / remote control
1:
Room panel ECA 60 / 62 or remote control
ECA 61 / 63 with address A
2:
Room panel ECA 60 / 62 or remote control
ECA 61 / 63 with address B
3 ... 5:
Not used
11 Setback temperature dependent on outdoor
temperature
Setting range
Factory setting
OFF / -29 ... 10 °C
-15 °C
Below this outdoor temperature, the setback temperature setting
has no influence.
-29 ... 10:
The setback temperature depends on the
outdoor temperature, when the outdoor
temperature is above the set limit. The
lower the outdoor temperature, the less the
temperature reduction. When the outdoor
temperature is below the set limit, there is
no temperature reduction.
OFF:
The setback temperature does not depend
on the outdoor temperature.
100%
0%
-20
-10
-29
0
20
10
Reduction
Outdoor
temperature °C
Setting line 11
Содержание ECL Comfort P30
Страница 4: ......
Страница 9: ...Installation 11b...