The grey
side of the
ECL Card
Basic set-up
27b
Line
Circuit
1
1
ON
2
ON
6
2
2 DHW temperature difference
Circuit
Setting range
Factory setting
II
1 ... 30 K
6 K
Set the difference between the cut-in (start) temperature and cut-
out (stop) temperature for DHW charging.
Set the DHW temperature difference.
Charging temp. difference - line 1
DHW temp. difference - line 2
Charging temp.
Desired DHW temp.
The DHW temperature difference is symmetrical around the
desired DHW temperature, i.e. half the value is above and half the
value is below this temperature.
Time
Actual DHW temp.
Charging
Temp.