The grey
side of the
ECL Card
Basic set-up
DHW control -
lines 1-2
27a
Line
Circuit
1
1
ON
2
ON
5
1
1
1 Charging temperature difference
Circuit
Setting range
Factory setting
II
1 ... 30 K
15 K
Set the difference between the desired tank temperature and the
charging temperature during DHW charging.
Set the difference. Set a high value if you want the
DHW to reach the desired temperature within a
short period of time.
A too high charging temperature might cause deposits in the heat
exchanger.
Example:
Desired DHW temperature (section 1): 60 °C
Charging temperature difference:
15 K
Charging temperature (60+15 =):
75 °C