DMS Manual
■
Start/ stop profile setting table:
Start/stop
Profile
Start
Performance
Stop
Performance
1
(A1)
2 (A2)
3 (A3)
4
(A4)
Initial
Voltage
(%)
Start
Ramp
Time
(sec) #
Stop
Ramp
time
(sec) #
0
Equivalent to
DOL
Coast to stop
Off
Off
Off
Off
80
0.25
*
1
Fastest
Off
Off
Off
On
80
0.5
*
2
|
Off
Off
On
Off
60
0.75
*
3
|
Off
Off
On
On
60
1.5
*
4
|
Off
On
Off
Off
60
1.0
*
5
|
Off
On
Off
On
50
2
*
6
|
Off
On
On
Off
40
3
*
7
|
Off
On
On
On
50
4
*
8
|
On
Off
Off
Off
60
6
*
9
Slowest
Coast to stop
On
Off
Off
On
60
8
*
10
Fastest
Fastest
On
Off
On
Off
60
2
1
11
|
|
On
Off
On
On
50
3
2
12
|
|
On
On
Off
Off
40
4
3
13
|
|
On
On
Off
On
40
5
3
14
|
|
On
On
On
Off
30
7
5
15
Slowest
Slowest
On
On
On
On
30
9
7
Note: * indicates Stop Ramp time is not controlled
by DMS. Motor will coast to stop.
# In some applications, actual ramp time on the
motor shaft could differ from the settings.
■
Trip Class selection :
This setting is applicable only for the Extended
versions of DMS.
The DMS motor overload protection is an advanced
motor thermal model. Motor temperature is
continuously calculated by the microprocessor.
This uses a sophisticated mathematical model
to accurately reflect motor heat generation and
dissipation during all stages of operation, e.g.
Starting, Running, Stopping & Stopped.
Because it operates continuously, the motor thermal
model eliminates the need for protection systems such
as Excess Start Time, Limited Starts per hour etc.
Calibrate the DMS motor thermal model for theTrip
Class of the connected motor. The Motor Trip
Class is defined as the length of time the motor
can sustain Locked Rotor Current. The motor
Trip Class can be found from the motor curves
or data sheet. For example, if a given motor can
withstand Locked Rotor Current for 10 sec, set
Trip Class 10 (or lower) in the DMS.
If in doubt, use "Trip Class 5", which is the Factory
Default setting for this parameter. With this setting,
the DMS will trip & protect the motor if the Locked
Rotor current sustains for more than 5 secs.
Use the DIP switches A5-A6 to choose the Trip Class.
■
Trip Class selection table :
Trip Class
Time
(sec)
5
(A5)
6
(A6)
Remarks
5
Off
Off
Trip Class 5
10
Off
On
Trip Class 10
20
On
Off
Trip Class 20
0
On
On
Motor Protection off
MG.05.A2.02 - VLT is a registered Danfoss trademark