Details of Profibus Connectivity
NB!:
When using Profibus interface, the complete
control of the DMS is done by the Profibus. The
DMS control terminals cannot be used.
■
Profibus DP Slave 6 E/DC 24 V, 4 A/DC 24 V/1A
connection
bus connection
spring terminal block 2 x 2 x 2.5sq.mm.
69: A-Line RxD/TxD-N, green wire 68:B-Line
RxD/TxD-P, red wire
termination
switchable, SW2 both on
supply power to the
module
voltage range incl. ripple
20-30VDC
ripple
max. 10%
current consumption
nom. 90 mA
connection
spring terminal block 2 x 2 x 2.5sq.mm.
201: DC 0 V, 202:DC 24 V
supply power input and
output
voltage range incl. ripple
20-30VDC
connection
spring terminal block 2 x 2 x 2.5sq.mm.
203: DC 0 V, 204:DC 24 V
galvanic isolation
isolation voltage
DC 500 V between bus and electronics
DC 2.5kV between module supply and
inputs/ outputs
Bus interface
Bus system
Profibus DP
module type
Slave I/O module
standard
DIN 19245
data width in the process image
1 Byte inputs, 1 Byte outputs
fieldbus controller
LSPM2
identifier
0409 hex
addressing
Node ID: 1-99 set by DIP switch SW3
baud rate
up to 12Mbaud, automatic detection
■
Table of bits in control and status word
Terminal
connection
Function
Profibus
control word
Profibus status
word
Output 1
18
Start CW
Bit 0
Output 2
19
Start CCW
Bit 1
Output 3
27
Reset/
Coasting stop inverse
Bit 2
0 V
125 (203)
+ 24 V
126 (204)
Input 1
M12, I1
Input
Bit 0
Input 2
M12, I2
Input
Bit 1
Input 3
M12, I3
Input
Bit 2
Input 4
M12, I4
Input
Bit 3
Input 5
46
Ready
Bit 4